Plan Review Details - Permit 22010634
Plan Review Stops For Permit 22010634
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-07-21 Cont ID  
Sent By jgomez Date 2022-07-21 Time 13:48 Rev Time 0.00
Received By jgomez Date 2022-07-21 Time 13:22 Sent To  
Notes
2022-07-21 13:48:45BUILDING REVIEW APPROVED WITH PROVISO. (NOTE: PROVIDE
 INFORMATION FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
 1- PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE
 DRAINAGE DOESN'T AFFECT NEIGHBORS.
 2- SOFFIT CONSTRUCTION: PROVIDE SPECIFICATIONS FOR TYPE
 OF METAL PLASTER BASE FOR CEILINGS SHOWING COMPLIANCE
 WITH TABLE 3 OF ASTM C1063.
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED.
 B) OVERHEAD GARAGE DOOR MEETING THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT ON SHEET D-1.
 C) INSWING ENTRY DOOR AS SHOWN ON PLANS.
 D) NEW HORIZONTAL ROLLING WINDOW AS SHOWN ON PLANS.
 PLANS SHOW 2 PANEL WINDOW SIZE 111"X58".
 E) CLARIFY WHY SUBMITTING NOA FOR SINGLE HUNG WINDOWS.
 NOTE: IF REPLACING WINDOWS IN EXISTING BEDROOMS, THEN
 SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE AND
 TYPE OF PROPOSED WINDOW.
 4- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVALS.
 5- PROVIDE CURRENT ICYNENE ICC EVALUATION REPORT.
 (ARCHITECT TO APPROVE THE REPORT).
 6- REVISE ENERGY CALCULATIONS:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME.
 B) DESIGN LOCATION SPECIFIED ON PAGE 1 IS INCORRECT.
 C) ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC. REVISE
 CALCULATIONS AS REQUIRED.
 D) WALL INSULATION R-VALUE SPECIFIED ON ITEM #10(A)
 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH.
 E) ITEM #16 ON PAGE 1 IS TAKING CREDIT FOR CEILING FANS
 AND CROSS VENTILATION. REVISE AS REQUIRED OR PROVIDE
 COMPLETE INFORMATION SHOWING HOW COMPLYING WITH THESE
 CREDITS.
 F) HOT WATER SYSTEM SPECIFIED ON PAGE 1 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED.
 G) PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
 H) ATTIC AREA SPECIFIED ON PAGE 2 IS INCORRECT. SEE
 PLANS AND REVISE.
 I) DOORS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED DOORS
 (METAL, WOOD, INSULATED FIBERGLASS, ETC.)
 J) WINDOWS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 ALSO, CHECK MATERIAL OF SPECIFIED WINDOWS (VINYL OR
 METAL).
 NOTE: COORDINATE WITH ITEM #6(I).

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-07-15 Cont ID  
Sent By jgomez Date 2022-07-15 Time 17:48 Rev Time 0.00
Received By jgomez Date 2022-07-15 Time 14:58 Sent To  
Notes
2022-07-15 17:49:18RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010634
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- LOT DRAINAGE:
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS
 AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NOT ADDRESSED.
  
  
 3- OK.
 4- OK.
 5- OK.
 6- OK.
 7- OK.
  
 ORIGINAL COMMENT:
 8- WIND RESISTANCE OF EXTERIOR SOFFITS: ARCHITECT OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ONLY SPECIFIES STUCCO OVER
 PAPER BACKED METHAL LATHE. THERE ARE NO SPECIFICATIONS
 FOR WHAT KIND OF SHEATHING IS SUPPORTING THE METHAL
 LATH. ALSO, REVISE SIZE OF SPECIFIED FASCIA. SIZE
 SPECIFIED IS SMALLER THAN THE 2X10 JOISTS.
  
 PREVIOUS RESPONSE:
 THERE IS NOT INFORMATION PROVIDED FOR SOFFIT
 CONSTRUCTION. PROVIDE SPECIFICATIONS SHOWING COMPLIANCE
 WITH ASTM C1063.
  
 RESPONSE TO CURRENT SUBMITTAL:
 REVISED TYPICAL WALL SECTION ON SHEET FD-1 ONLY
 SPECIFIES "METAL LATHE" AS THE METAL BASE TO SUPPORT
 THE STUCCO. THIS METAL BASE DOESN'T COMPLY WITH TABLE 3
 OF ASTM C1063 BASED ON THE CEILING RAFTERS SPACING. SEE
 TABLE 3 OF ASTM C1063 AND REVISE AS REQUIRED.
  
 9- OK.
  
 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NO INFORMATION SUBMITTED.
 AND, NOT RESPONSE FROM CONTRACTOR IF SUBMITTING LATER A
 A DEFERRED SUBMITTAL.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C)FROSTED GLASS GARAGE DOOR AS SPECIFIED ON PLANS.
  
 RESPONSE:
 DESIGN PRESSURES OF GARAGE DOOR ON FLORIDA PRODUCT
 APPROVAL FL16545-R13 SUBMITTED DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT ON SHEET D-1.
 NEED TO RESUBMIT. NEED PRODUCT APPROVAL OF GARAGE DOOR
 THAT MEETS OR EXCEEDS THE CALCULATED DESIGN PRESSURES.
  
 ORIGINAL COMMENT:
 D) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NO INFORMATION SUBMITTED.
 AND, NOT RESPONSE FROM CONTRACTOR IF SUBMITTING LATER
 AS A DEFERRED SUBMITTAL.
  
 E)OK.
  
 F)NEW HORIZONTAL ROLLING WINDOW.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. REVISED PLANS SHOW 2 PANEL
 WINDOW SIZE 111"X58". NOA 20-0813.06 SUBMITTED DOESN'T
 COVER THIS SIZE FOR 2 PANEL WINDOW. REVISE AS REQUIRED
 OR PROVIDE ANOTHER PRODUCT APPROVAL.
  
 NEW COMMENT:
 G)SINGLE HUNG WINDOWS: CLARIFY WHY SUBMITTING PRODUCT
 APPROVAL FOR SINGLE HUNG WINDOWS. PLANS DON'T SHOW ANY
 SINGLE HUNG WINDOWS. SEC. 107.2.1 CITY AMENDMENTS.
 NOTE: IF REPLACING WINDOWS IN EXISTING BEDROOMS, THEN
 SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE AND
 TYPE OF PROPOSED WINDOW.
  
 11-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 12- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 A) ICC EVALUATION REPORT ESR-2629 IS EXPIRED. THIS
 REPORT WAS SUBJECT TO RENEWAL ON 12/2019. NEED TO
 PROVIDE CURRENT REPORT.
  
 B) ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13-ENERGY CALCULATIONS SUBMITTED:
 A)OK.
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 PARTIALLY DONE. STILL NEEDS OWNER'S NAME, BUILDER'S
 NAME.
  
 ORIGINAL COMMENT:
 C)DESIGN LOCATION SPECIFIED ON PAGE 1 IS INCORRECT.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D)OK.
  
 ORIGINAL COMMENT:
 F)ITEM #5 ON PAGE 1 SPECIFIES WORST CASE SCENARIO.
 ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC AS
 REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 G) OK.
  
 ORIGINAL COMMENT:
 H)WALL INSULATION R-VALUE SPECIFIED ON ITEM #10(A) FOR
 CONCRETE BLOCK WALL DOESN'T MATCH PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISED INFORMATION IS INCORRECT AGAIN. COORDINATE WITH
 ARCHITECT. SEE PLANS AND REVISE AS REQUIRED.
  
 I)OK.
  
 ORIGINAL COMMENT:
 J)ITEM #16 ON PAGE 1 IS TAKING CREDIT FOR CEILING FANS
 AND WHOLE HOUSE FAN. PLANS DON'T SHOW ANY OF THIS.
 REVISE AS REQUIRED OR PROVIDE COMPLETE INFORMATION
 SHOWING HOW THE HOUSE IS COMPLYING WITH THESE CREDITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISED INFORMATION IS NOW IS TAKING CREDIT FOR CEILING
 FANS AND CROSS VENTILATION. PLANS DON'T SHOW ANY OF
 THIS. REVISE AS REQUIRED OR PROVIDE COMPLETE
 INFORMATION SHOWING HOW THE HOUSE IS COMPLYING WITH
 THESE CREDITS.
 NOTE: COORDINATE WITH ARCHITECT TO AVOID MORE
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 K)HOT WATER SYSTEM SPECIFIED ON PAGE 1 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. PLANS SHOW TANKLESS WATER
 HEATER.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 ORIGINAL COMMENT:
 L)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NO NAME PROVIDED. ONLY INITIALS WERE
 PROVIDED. NEED THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY THE CITED SECTION.
  
 M) OK.
  
 ORIGINAL COMMENT:
 N)ATTIC VENT INFORMATION ON PAGE 2 IS INCORRECT. REVISE
 AS REQUIRED. TYPICALLY, THE RATIO IS 1/150 NOT 1/300.
 SEC. R806.2 FBC-RESIDENTIAL. OR PERSON PREPARING THE
 ENERGY CALCULATIONS TO PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. FBC-RESIDENTIAL.
  
 RESPONSE:
 PARTIALLY DONE. THE ATTIC VENT RATIO WAS REVISED BUT
 THE ATTIC AREA WAS NOT. SEE PLANS FOR PITCHED ROOF
 AREAS AND REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 O)DOORS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED DOORS
 (METAL, WOOD, INSULATED FIBERGLASS, ETC.)
  
 RESPONSE:
 REPEAT COMMENT. SEE NOTE ABOUT GLAZING IN DOORS AND
 REVISE AS REQUIRED. SEE PLANS AND REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 P)WINDOWS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED
 WINDOWS (VINYL OR METAL).
  
 RESPONSE:
 COORDINATE WITH ITEM #13(O) ABOVE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-17 Cont ID  
Sent By jgomez Date 2022-05-17 Time 18:12 Rev Time 0.00
Received By jgomez Date 2022-05-17 Time 16:15 Sent To  
Notes
2022-05-17 18:13:26RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010634
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- OK.
  
 ORIGINAL COMMENT:
 2- LOT DRAINAGE:
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS
 AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 3- DESIGN CRITERIA INFORMATION ON SHEET D-1. SPECIFIED
 ROOF DESIGN PRESSURES ARE NOT THE WORST CASE SCENARIO.
 SEE TABLE R301.2(2) AND TABLE R301.2(3)FBC-RESIDENTIAL
 AND REVISE AS REQUIRED.
 NOTE: NEED TO PROVIDE DESIGN PRESSURES FOR FLAT ROOF
 AND FOR PITCHED ROOF.
  
 RESPONSE:
 COMPONENTS AND CLADDING ROOF PRESSURES ARE INCORRECT.
 SEE TABLE R301.2(2) AND TABLE R301.2(3)FBC-RESIDENTIAL
 AND REVISE AS REQUIRED.
  
 ORIGINAL COMMENT:
 4- PROPOSED FLOOR PLAN SHOWS ONE WINDOW OF EXISTING
 BEDROOM #4 TO BE BLOCKED TO ALLOW FOR THE GARAGE
 ADDITION. SPECIFY SIZE AND TYPE OF EXISTING WINDOWS IN
 THIS BEDROOM TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- OK.
 6- OK.
 7- OK.
  
 ORIGINAL COMMENT:
 8- WIND RESISTANCE OF EXTERIOR SOFFITS: ARCHITECT OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ONLY SPECIFIES STUCCO OVER
 PAPER BACKED METHAL LATHE. THERE ARE NO SPECIFICATIONS
 FOR WHAT KIND OF SHEATHING IS SUPPORTING THE METHAL
 LATH. ALSO, REVISE SIZE OF SPECIFIED FASCIA. SIZE
 SPECIFIED IS SMALLER THAN THE 2X10 JOISTS.
  
 RESPONSE:
 THERE IS NOT INFORMATION PROVIDED FOR SOFFIT
 CONSTRUCTION. PROVIDE SPECIFICATIONS SHOWING COMPLIANCE
 WITH ASTM C1063.
  
 9- OK.
  
 ORIGINAL COMMENT:
 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 NO INFORMATION SUBMITTED. AND, NOT RESPONSE FROM
 CONTRACTOR IF SUBMITTING LATER A A DEFERRED SUBMITTAL.
  
 B)SLIDING GLASS DOORS.
  
 RESPONSE:
 INFORMATION SUBMITTED IS INCOMPLETE. ONLY THE DOOR
 DRAWINGS WERE SUBMITTED. IF THIS A FLORIDA PRODUCT
 APPROVAL , THEN NEED TO PROVIDE COMPLETE PRODUCT
 APPROVAL PACKAGE, INCLUDING THE FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWINGS
 SUBMITTED. IF DOOR DOESN'T HAVE A FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA, THEN DOOR MANUFACTURER MAY
 SUBMIT COMPLETE ENGINEERING PACKAGE FOR REVIEW FOR
 LOCAL PRODUCT APPROVAL.
 NOTE: PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.001 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 C)FROSTED GLASS GARAGE DOOR AS SPECIFIED ON PLANS.
  
 RESPONSE:
 NO INFORMATION SUBMITTED. AND, NOT RESPONSE FROM
 CONTRACTOR IF SUBMITTING LATER A A DEFERRED SUBMITTAL.
  
 D) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 NO INFORMATION SUBMITTED. AND, NOT RESPONSE FROM
 CONTRACTOR IF SUBMITTING LATER A A DEFERRED SUBMITTAL.
  
 E)OK.
  
 F)NEW HORIZONTAL ROLLING WINDOW.
  
 RESPONSE:
 REVISED PLANS SHOW 2 PANEL WINDOW SIZE 111"X58". NOA
 20-0813.06 SUBMITTED DOESN'T COVER THIS SIZE FOR 2
 PANEL WINDOW. REVISE AS REQUIRED OR PROVIDE ANOTHER
 PRODUCT APPROVAL.
  
 11-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 12- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 RESPONSE:
 NO INFORMATION SUBMITTED. AND, NOT RESPONSE FROM
 CONTRACTOR IF SUBMITTING LATER A A DEFERRED SUBMITTAL.
  
 ORIGINAL COMMENT. ENERGY CALCULATIONS WERE NOT REVISED.
 ALL THE COMMENTS APPLY.
 13-ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)DESIGN LOCATION SPECIFIED ON PAGE 1 IS INCORRECT.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)NUMBER OF BEDROOMS IS INCORRECT. SEE PLANS AND REVISE
 AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)ITEM #5 ON PAGE 1 SPECIFIES WORST CASE SCENARIO.
 ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC AS
 REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 F)CONDITIONED FLOOR AREA DOESN'T MATCH PLANS. REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)WALL INSULATION R-VALUE SPECIFIED ON ITEM #10(A) FOR
 CONCRETE BLOCK WALL DOESN'T MATCH PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)CEILING INSULATION R-VALUE SPECIFIED ON ITEM #11(A)
 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)ITEM #16 ON PAGE 1 IS TAKING CREDIT FOR CEILING FANS
 AND WHOLE HOUSE FAN. PLANS DON'T SHOW ANY OF THIS.
 REVISE AS REQUIRED OR PROVIDE COMPLETE INFORMATION
 SHOWING HOW THE HOUSE IS COMPLYING WITH THESE CREDITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)HOT WATER SYSTEM SPECIFIED ON PAGE 1 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. PLANS SHOW TANKLESS WATER
 HEATER. ALSO, CHECK WITH ARCHITECT IF GAS OR ELECTRIC.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 KL)PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 L) NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 UNDER
 "SPACES" IS INCORRECT. COORDINATE WITH NUMBER OF
 BEDROOMS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)ATTIC VENT INFORMATION ON PAGE 2 IS INCORRECT. REVISE
 AS REQUIRED. TYPICALLY, THE RATIO IS 1/150 NOT 1/300.
 SEC. R806.2 FBC-RESIDENTIAL. OR PERSON PREPARING THE
 ENERGY CALCULATIONS TO PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. FBC-RESIDENTIAL.
  
 N)DOORS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED DOORS
 (METAL, WOOD, INSULATED FIBERGLASS, ETC.)
  
 O)WINDOWS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED
 WINDOWS (VINYL OR METAL).
  
 P)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By jgomez Date 2022-03-23 Time 18:38 Rev Time 0.00
Received By jgomez Date 2022-03-22 Time 14:49 Sent To  
Notes
2022-03-23 10:39:44RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010634
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- PROVIDE SITE PLAN SHOWING THE PROPOSED ADDITIONS AND
 SETBACKS AS REQUIRED BY SEC. 107.2.5 CITY AMENDMENTS.
 NOTE: BOUNDARY LINE SURVEY SHALL BE INCLUDED ALSO.
  
 2- LOT DRAINAGE:
 PROPOSED WORK AFFECTS THE LOT DRAINAGE. PROVIDE
 DRAINAGE PLAN SHOWING HOW THE SURFACE DRAINAGE IS KEPT
 WITHIN THE LOT AND NOT DIVERTED TO ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS
 AND SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 3- DESIGN CRITERIA INFORMATION ON SHEET D-1. SPECIFIED
 ROOF DESIGN PRESSURES ARE NOT THE WORST CASE SCENARIO.
 SEE TABLE R301.2(2) AND TABLE R301.2(3)FBC-RESIDENTIAL
 AND REVISE AS REQUIRED.
 NOTE: NEED TO PROVIDE DESIGN PRESSURES FOR FLAT ROOF
 AND FOR PITCHED ROOF.
  
 4- PROPOSED FLOOR PLAN SHOWS ONE WINDOW OF EXISTING
 BEDROOM #4 TO BE BLOCKED TO ALLOW FOR THE GARAGE
 ADDITION. SPECIFY SIZE AND TYPE OF EXISTING WINDOWS IN
 THIS BEDROOM TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL.
  
 5- SHEET A-3:
 A)ROOF PLAN DOESN'T SPECIFY BEAMS FOR NEW ENTRY PORCH.
 PROVIDE BEAM TYPE, SIZE AND STRUCTURAL CONNECTORS. SEC.
 R301.2.1 FBC RESIDENTIAL.
  
 B)SPECIFY HOW THE NEW 2X10 ROOF JOISTS IN THE KITCHEN
 AREA ARE GOING TO BE FASTENED TO THE EXISTING BEAM.
 SEC. R301.2.1 FBC RESIDENTIAL.
 NOTE: ALSO, SPECIFY CONNECTION TO THE NEW (2)11-3/4"
 LVL BEAM
  
 C) SPECIFY CONNECTORS AT EACH END OF NEW (2)11-3/4" LVL
 BEAM LOCATED BETWEEN GREAT ROOM AND LIVING ROOM. SEC.
 R301.2.1 FBC RESIDENTIAL.
  
 D)REVISE ROOF SHEATHING NAIL TYPE AND SPACING SPECIFIED
 ON THE ROOF EDGE DETAIL. NEED TO USE RING SHANK NAILS
 AND ROOF SHEATHING NEEDS TO BE NAILED WITH AT 4 INCHES
 O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 E)ROOF EDGE DETAIL SUBMITTED IS ONLY FOR PITCHED ROOF.
 NEED TO PROVIDE ROOF EDGE DETAIL FOR FLAT ROOF ALSO.
 SEE FIGURE R301.2(7) FBC-RESIDENTIAL FOR FLAT ROOF
 DIAGRAM.
  
 F)BLOCK WALL EXTENSION DETAIL IN THIS DRAWING AND
 TYPICAL WALL SECTION ON DRAWING FD-1 SPECIFY FLAT ROOF
 ASSEMBLY WITH INSULATION (1" ISO INSULATION). SPECIFY
 THE R-VALUE OF THE INSULATION AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 6- DIMENSION PLAN ON SHEET A-2 DOESN'T SPECIFY THE
 WIDTH OF THE NEW HALLWAY
 LEADING FROM THE GARAGE TO THE LIVING ROOM. PROVIDE
 DIMENSION. SEC. R311.7.1 FBC-RESIDENTIAL.
  
 7- SPECIFY ROOF CROSS VENTILATION ON NEW ROOF AREAS AS
 REQUIRED BY SEC. R806 FBC-RESIDENTIAL. SPECIFY SIZE AND
 LOCATION.
  
 8- WIND RESISTANCE OF EXTERIOR SOFFITS: ARCHITECT OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 FOR THE SOFFIT CONSTRUCTION SHOWING COMPLIANCE WITH
 SEC. R704 FBC-RESIDENTIAL.
 NOTE: TYPICAL WALL SECTION ONLY SPECIFIES STUCCO OVER
 PAPER BACKED METHAL LATHE. THERE ARE NO SPECIFICATIONS
 FOR WHAT KIND OF SHEATHING IS SUPPORTING THE METHAL
 LATH. ALSO, REVISE SIZE OF SPECIFIED FASCIA. SIZE
 SPECIFIED IS SMALLER THAN THE 2X10 JOISTS.
  
 9- SPECIFY CARBON MONOXIDE ALARM WITHIN ALL SLEEPING
 ROOMS, INCLUDING EXISTING BEDROOMS AS REQUIRED BY SEC.
 R315.1 FBC-RESIDENTIAL.
 NOTE: THERE IS NO CARBON MONOXIDE ALARM SPECIFIED BY
 BEDROOM #4.
  
 10-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)SLIDING GLASS DOORS.
  
 C)FROSTED GLASS GARAGE DOOR AS SPECIFIED ON PLANS.
  
 D) INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 E)FIXED WINDOW AS SHOWN ON PLANS.
  
 11-ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13-ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)DESIGN LOCATION SPECIFIED ON PAGE 1 IS INCORRECT.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)NUMBER OF BEDROOMS IS INCORRECT. SEE PLANS AND REVISE
 AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)ITEM #5 ON PAGE 1 SPECIFIES WORST CASE SCENARIO.
 ENERGY CALCULATIONS NEED TO BE SITE SPECIFIC AS
 REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION. REVISE AS REQUIRED.
  
 F)CONDITIONED FLOOR AREA DOESN'T MATCH PLANS. REVISE AS
 REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)WALL INSULATION R-VALUE SPECIFIED ON ITEM #10(A) FOR
 CONCRETE BLOCK WALL DOESN'T MATCH PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H)CEILING INSULATION R-VALUE SPECIFIED ON ITEM #11(A)
 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I)ITEM #16 ON PAGE 1 IS TAKING CREDIT FOR CEILING FANS
 AND WHOLE HOUSE FAN. PLANS DON'T SHOW ANY OF THIS.
 REVISE AS REQUIRED OR PROVIDE COMPLETE INFORMATION
 SHOWING HOW THE HOUSE IS COMPLYING WITH THESE CREDITS.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)HOT WATER SYSTEM SPECIFIED ON PAGE 1 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. PLANS SHOW TANKLESS WATER
 HEATER. ALSO, CHECK WITH ARCHITECT IF GAS OR ELECTRIC.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 KL)PROVIDE THE NAME OF THE PERSON DOING THE
 CALCULATIONS AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY
 CONSERVATION.
  
 L) NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 UNDER
 "SPACES" IS INCORRECT. COORDINATE WITH NUMBER OF
 BEDROOMS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 M)ATTIC VENT INFORMATION ON PAGE 2 IS INCORRECT. REVISE
 AS REQUIRED. TYPICALLY, THE RATIO IS 1/150 NOT 1/300.
 SEC. R806.2 FBC-RESIDENTIAL. OR PERSON PREPARING THE
 ENERGY CALCULATIONS TO PROVIDE COMPLETE
 DETAILS/SPECIFICATIONS SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2. FBC-RESIDENTIAL.
  
 N)DOORS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED DOORS
 (METAL, WOOD, INSULATED FIBERGLASS, ETC.)
  
 O)WINDOWS INFORMATION SHOWN ON PAGE 3 DOESN'T MATCH
 PLANS. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 NOTE: GLAZING IN DOORS NEEDS TO BE INCLUDED IN THE
 WINDOW GLAZING AREA. SEE SEC. R405.5.3 FBC-ENERGY
 CONSERVATION). ALSO, CHECK MATERIAL OF SPECIFIED
 WINDOWS (VINYL OR METAL).
  
 P)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-27 Cont ID  
Sent By mpeterso Date 2022-04-27 Time 09:31 Rev Time 0.00
Received By mpeterso Date 2022-04-27 Time 09:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-02-14 Cont ID  
Sent By jleahy Date 2022-02-14 Time 15:17 Rev Time 0.00
Received By jleahy Date 2022-02-14 Time 14:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-21 Cont ID  
Sent By jgomez Date 2022-07-21 Time 14:27 Rev Time 0.00
Received By jgomez Date 2022-07-21 Time 10:50 Sent To I
Notes
2022-07-21 10:53:3407/21/22 RECEIVED EMAIL TO APPROVE BUILDING WITH
 PROVISO. JG.
  
  
 HELLO JULIO,
 IT WAS A PLEASURE MEETING YOU TODAY. THANK YOU FOR
 SEEING US.
 PLEASE APPROVE OUR CONSTRUCTION PLANS FOR 310 EDMOR,
 WITH THE CONTINGENCIES DISCUSSED AS PROVISOS. WE WILL
 BE SUBMITTING THE REVISIONS IN A TIMELY MANNER.
 WE APPRECIATE YOUR ADVICE AND WILL STAY IN TOUCH IF WE
 NEED FURTHER CLARIFICATION.
 KINDEST REGARDS,
 HAYDEE LEVITT
 SENT FROM MY IPAD
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-15 Cont ID  
Sent By jgomez Date 2022-07-15 Time 17:53 Rev Time 0.00
Received By jgomez Date 2022-06-03 Time 08:22 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-17 Cont ID  
Sent By jgomez Date 2022-05-17 Time 18:15 Rev Time 0.00
Received By jgomez Date 2022-04-07 Time 09:29 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-23 Cont ID  
Sent By jgomez Date 2022-03-23 Time 10:55 Rev Time 0.00
Received By jgomez Date 2022-01-26 Time 08:14 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2022-08-12 Cont ID  
Sent By lmarchan Date 2022-08-12 Time 11:42 Rev Time 0.00
Received By lmarchan Date 2022-08-01 Time 16:01 Sent To  
Notes
2022-08-12 11:42:34NO FEES DUE PER IMPACT OFFICE. LEM
2022-08-01 16:01:208/1/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2022-07-21 Cont ID  
Sent By jgomez Date 2022-07-21 Time 14:26 Rev Time 0.00
Received By jgomez Date 2022-07-21 Time 14:26 Sent To  
Notes
2022-07-21 14:26:30 
 IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-07-20 Cont ID  
Sent By jgomez Date 2022-07-20 Time 17:46 Rev Time 0.00
Received By jgomez Date 2022-07-20 Time 17:46 Sent To  
Notes
2022-07-20 17:46:29 
 IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By jgomez Date 2022-03-23 Time 10:44 Rev Time 0.00
Received By jgomez Date 2022-03-23 Time 10:43 Sent To  
Notes
2022-03-23 10:44:16 
 IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-06-10 Cont ID  
Sent By medwards Date 2022-06-10 Time 15:51 Rev Time 0.00
Received By medwards Date 2022-06-10 Time 15:51 Sent To  
Notes
2022-06-10 15:51:43APPROVED WITH PRIVISO ME

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-25 Time 12:34 Rev Time 0.00
Received By medwards Date 2022-04-25 Time 12:34 Sent To  
Notes
2022-04-25 12:35:08PLEASE ADDRESS PREVIOUS REVIEW COMMENTS LISTED BELOW:
  
  
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010634
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECIFICATIONS FOR THE RANGE. IS
 THERE GOING TO BE A HOOD ABOVE THE RANGE? HOW WILL IT
 COMPLY WITH THE MAKE UP REQUIREMENTS OF FBC RES M1503.4
  
 2) PLEASE SHOW THE RETURN AIR PATH BACK TO THE AHU, ARE
 THE DOORS OF THE AHU CLOSET LOUVERED? FBC RES M1602.3
  
 3) PLEASE SHOW THE RETURN AIR PATH FROM THE MASTER
 SUITE BACK TO THE AHU. FBC RES M1602.3
  
 4) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL, SIZE
 AND TERMINATION LOCATION. FBC RES M1506.3
  
 5) PLEASE SHOW THE BATHROOMS EXHAUST TERMINATIONS
 LOCATIONS. FBC RES M1506.3
  
 6) PLEASE SHOW THE CONDENSING UNIT LOCATION. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-09 Cont ID  
Sent By medwards Date 2022-02-09 Time 10:15 Rev Time 0.00
Received By medwards Date 2022-02-09 Time 10:05 Sent To  
Notes
2022-02-09 10:15:471ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010634
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE SPECIFICATIONS FOR THE RANGE. IS
 THERE GOING TO BE A HOOD ABOVE THE RANGE? HOW WILL IT
 COMPLY WITH THE MAKE UP REQUIREMENTS OF FBC RES M1503.4
  
 2) PLEASE SHOW THE RETURN AIR PATH BACK TO THE AHU, ARE
 THE DOORS OF THE AHU CLOSET LOUVERED? FBC RES M1602.3
  
 3) PLEASE SHOW THE RETURN AIR PATH FROM THE MASTER
 SUITE BACK TO THE AHU. FBC RES M1602.3
  
 4) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL, SIZE
 AND TERMINATION LOCATION. FBC RES M1506.3
  
 5) PLEASE SHOW THE BATHROOMS EXHAUST TERMINATIONS
 LOCATIONS. FBC RES M1506.3
  
 6) PLEASE SHOW THE CONDENSING UNIT LOCATION. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-06-06 Cont ID  
Sent By rwbrown Date 2022-06-06 Time 12:01 Rev Time 0.00
Received By rwbrown Date 2022-06-06 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-04-14 Cont ID  
Sent By lcrespo Date 2022-04-14 Time 13:26 Rev Time 0.00
Received By lcrespo Date 2022-04-14 Time 13:26 Sent To  
Notes
2022-04-14 13:26:2704/14/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. ON SHEET A-1, IT SHOWS A TANKLESS WATER HEATER; IS
 IT GAS OR ELECTRIC. WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 3. ON SHEET FD-1;
  
 A. DONE, BUT WITH A NEW COMMENT; THE SANITARY ISOMETRIC
 DIAGRAM IS HARD TO READ AS IT DOES NOT MATCH THE FLOOR
 PLAN. WOULD YOU PLEASE CORRECT TO MATCH PLANS PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL PLUMBING?
  
 THE WASHING MACHINE IS NOT VENTED CORRECTLY PER THE
 2020 FBC SEC. P 3101.2 TRAP SEAL PROTECTION.
  
 THE LAV IN THE IS NOT VENTED CORRECTLY PER THE 2020 FBC
 SEC. P 3101.2 TRAP SEAL PROTECTION.
  
 THE ISOMETRIC DOES NOT MATCH THE LAYOUT OF THE PLUMBING
 FIXTURE. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 B. SECOND REQUEST; IT DOES NOT SHOW THE WASHING
 MACHINE, BAR, OR KITCHEN SINK. WOULD YOU PLEASE SHOW
 AND LABEL PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENT?
  
 C. DONE.
  
 D. SECOND REQUEST; WOULD YOU PLEASE SHOW THE SOURCE OF
 HOT AND PROVIDE AN ISOMERIC WATER DIAGRAM PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 PLUMBING.
  
 E. DONE.
  
 F. DONE.
  
 4. ON SHEET A-1 AND ALL THAT APPLY, WOULD YOU PLEASE
 LABEL THE BATHROOMS. WOULD YOU PLEASE PROVIDE PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 5. FORM R405-2020 SAYS AN ELECTRICAL HEATER, BUT GAS IS
 SHOWN ON PLANS. WOULD YOU PLEASE CORRECT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 6. ON SHEET M-1, THE PLANS SHOW A DIFFERENT LAYOUT IN
 THE MASTER AREA IN COMPARICINE TO E-1 AND FD-1. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By lcrespo Date 2022-01-31 Time 11:36 Rev Time 0.00
Received By lcrespo Date 2022-01-31 Time 11:36 Sent To  
Notes
2022-01-31 12:53:3101/31/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. ON SHEET A-1, IT SHOWS A TANKLESS WATER HEATER, IS
 IT GAS OR ELECTRIC. WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 3. ON SHEET FD-1;
  
 A. THE SANITARY ISOMETRIC DIAGRAM IS HARD TO READ AS IT
 DOES NOT MATCH THE FLOOR PLAN. WOULD YOU PLEASE CORRECT
 TO MATCH PLANS PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (12) RESIDENTIAL PLUMBING?
  
 B. I DOES NOT SHOW THE WASHING MACHINE, BAR, OR KITCHEN
 SINK. WOULD YOU PLEASE SHOW AND LABEL PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENT?
  
 C. TO MANY LAVS, THEY SHOW DOUBLES IN THREE LOCATIONS,
 BUT NONE ARE ON THE FLAT DRAWING. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU PLEASE SHOW THE SOURCE OF HOT AND PROVIDE
 AN ISOMERIC WATER DIAGRAM PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING.
  
 E. THE CONNECTION ON THE BRANCHES IS IN THE WRONG
 DIRECTION PER THE 202 FBC SEC. R 3005.1 DRAINAGE
 FITTINGS AND CONNECTIONS.
  
 F. THERE IS A DOUBLE LAV THAT HAS NO VENT FOR IT. WOULD
 YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2022-07-21 Cont ID  
Sent By jgomez Date 2022-07-21 Time 14:21 Rev Time 0.00
Received By jgomez Date 2022-07-21 Time 14:21 Sent To  
Notes
2022-07-21 14:21:301- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED.
 2- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVALS.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2022-07-15 Cont ID  
Sent By jgomez Date 2022-07-15 Time 14:59 Rev Time 0.00
Received By jgomez Date 2022-07-15 Time 14:59 Sent To  
Notes
2022-07-15 14:59:29ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 REPEAT COMMENT. THREE TIMES. NO INFORMATION SUBMITTED.
 AND, NOT RESPONSE FROM CONTRACTOR IF SUBMITTING LATER A
 A DEFERRED SUBMITTAL.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-05-17 Cont ID  
Sent By jgomez Date 2022-05-17 Time 18:14 Rev Time 0.00
Received By jgomez Date 2022-05-17 Time 18:14 Sent To  
Notes
2022-05-17 18:15:10ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By jgomez Date 2022-03-23 Time 10:49 Rev Time 0.00
Received By jgomez Date 2022-03-23 Time 10:49 Sent To  
Notes
2022-03-23 10:50:27ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A) FLAT ROOF. NOTE: CLEARLY MARK WHICH APPROVED
 INSULATED ASSEMBLY AS SPECIFIED ON PLANS IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 2- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-15 Cont ID  
Sent By jgomez Date 2022-07-15 Time 17:52 Rev Time 0.00
Received By jgomez Date 2022-07-15 Time 17:49 Sent To  
Notes
2022-06-10 15:52:36DIGITAL SIGNATURE FOR MECHANICAL APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-05-17 Cont ID  
Sent By jgomez Date 2022-05-17 Time 16:31 Rev Time 0.00
Received By jgomez Date 2022-05-17 Time 16:30 Sent To  
Notes
2022-05-17 16:32:35SECOND SIGNATURE REVIEW: SAME COMMENT APPLIES.
  
 1- MECHANICAL DRAWING M-1 WAS NOT SIGNED AND SEALED BY
 THE ARCHITECT OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH DIGITAL
 SIGNATURE OR PROVIDE HARD COPY WITH ORIGINAL SEAL AND
 SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By jgomez Date 2022-03-23 Time 10:53 Rev Time 0.00
Received By jgomez Date 2022-03-23 Time 10:50 Sent To  
Notes
2022-03-23 10:55:18SIGNATURE REVIEW:
  
 1- MECHANICAL DRAWING M-1 WAS NOT SIGNED AND SEALED BY
 THE ARCHITECT OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH DIGITAL
 SIGNATURE OR PROVIDE HARD COPY WITH ORIGINAL SEAL AND
 SIGNATURE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2022-06-16 Cont ID  
Sent By vbroglia Date 2022-06-16 Time 14:13 Rev Time 0.00
Received By vbroglia Date 2022-06-16 Time 14:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-04-15 Cont ID  
Sent By vbroglia Date 2022-04-15 Time 10:12 Rev Time 0.00
Received By vbroglia Date 2022-04-15 Time 10:12 Sent To  
Notes
2022-04-15 10:16:24***FAILED UNTIL ACTION REQUIRED IS COMPLETED:***
  
 THE VALUE OF THE CONSTRUCTION ($185,600) EXCEEDS 50% OF
 THE STRUCTURE'S VALUE ($146,095) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY.
  
  
 PLEASE APPLY FOR A LANDSCAPE PERMIT TO ALLOW STAFF TO
 MOVE FORWARD
 PLEASE CONTACT RAY CARANCI AT [email protected] FOR
 LANDSCAPING INQUIRES
  
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By vbroglia Date 2022-02-04 Time 13:29 Rev Time 0.00
Received By vbroglia Date 2022-02-04 Time 13:29 Sent To  
Notes
2022-02-04 13:31:372/4/22 FAILED- PLEASE PROVIDE THE SETBAKS OF THE HOSUE
 TO THE PROPERTY LINE. THERE IS A 5 FEET MIN. AND NEED
 TO EQUAL 15 FEET IN TOTAL WHEN ADDING BOTH SIDE
 SETBACKS.
  
 PLEASE PROVIDE THE HEIGHT OF THE PROPOSED PROJECT IN
 ELEVATION PLANS, STARTING FROM GRADE
  
 VALENTINA BROGLIA
 [email protected]