Plan Review Details - Permit 22010612
Plan Review Stops For Permit 22010612
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-30 Cont ID  
Sent By rmcdouga Date 2022-08-30 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2022-08-30 Time 09:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-03-23 Cont ID  
Sent By rmcdouga Date 2022-03-23 Time 13:49 Rev Time 0.00
Received By rmcdouga Date 2022-03-23 Time 13:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-02-09 Cont ID  
Sent By jleahy Date 2022-02-09 Time 15:36 Rev Time 0.00
Received By jleahy Date 2022-02-09 Time 15:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-30 Cont ID  
Sent By rmcdouga Date 2022-08-30 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2022-08-02 Time 06:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-04-19 Time   Rev Time 0.00
Received By aoliver Date 2022-04-08 Time 07:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-23 Cont ID  
Sent By rmcdouga Date 2022-03-23 Time 13:49 Rev Time 0.00
Received By rmcdouga Date 2022-01-25 Time 10:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-08-04 Cont ID  
Sent By ccole Date 2022-08-04 Time 14:42 Rev Time 0.00
Received By ccole Date 2022-08-04 Time 12:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-04-19 Cont ID  
Sent By ccole Date 2022-04-19 Time 10:20 Rev Time 0.00
Received By ccole Date 2022-04-18 Time 08:56 Sent To  
Notes
2022-04-19 10:21:252ND REVIEW FBC-2020 PLUMBING
 PERMIT- 220106121
 4/19/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET SP-4.01 GENERAL NOTES AND CONDITIONS: UPDATE
 ALL OUTDATED CODE REFERENCES AND COMPLIANCE STANDARDS
 INCLUDING THE APPLICABLE ANSI/APSP CONFORMANCE
 STANDARDS. STATE CLEARLY PRIVATE OR PUBLIC USE POOL-
 FBC B OR FBC RES- SEC. 107.2.1 WPB.
  
 2) SP-401 & SP-403: SP-401 PUMP NOTE #10 INDICATES MAX
 FLOW NOT TO EXCEED 8 FPS IN RETURN, DESIGN VELOCITIES
 NOTE ON SP-4.03 INDICATES 10 FPS- PLEASE CORRECT.
  
 3) SP-4.03 & SP-4.04: THE POOL PIPING PLAN SHOWS 2-INCH
 DRAIN PIPING, DUAL MAIN DRAIN DETAIL INDICATES
 2-1/2-INCH PIPING.
  
 4) SP-4.04: IDENTIFY ALL EQUIPMENT SHOWN IN THE
 ANCHORAGE DETAIL- SEC. 107.2.1 WPB. IT APPEARS THE
 FILTER IS NOT LABELED.
  
 5) A-2.60 & SP.04 EQUIPMENT ROOM COMPLIANCES: CLARIFY
 HOW THE EQUIPMENT ROOM WILL BE VENTILATED AND IF A
 SHIP'S LADDER WILL BE INSTALLED FROM THE HATCH OPENING
 TO THE FLOOR- SEC. 454.1.5.4 FBC B. PLEASE NOTE THAT
 MINIMUM CEILING HEIGHT PER SEC. 454.1.5.6 IS 7-FT.
  
 6) P-109: CLARIFY THE EXACT LOCATION OF THE BACKFLOW
 PREVENTER. PLEASE NOTE THAT THE DEVICE SHALL NOT BE
 INSTALLED IN CONFINED SPACE AND A MINIMUM OF 18-INCHES
 CLEARANCE SHALL BE PROVIDED ON ALL SIDES- SEC. H(5) WPB
 CROSS-CONNECTION MANUAL. A NOTE REQUIRING A SEPARATE
 PERMIT FOR THE BACKFLOW PREVENTER SHALL BE PLACED ON
 THE PLAN- SEC. 105.1 WPB.
  
 7) SP.03 & SP.04: PROVIDE A MEANS OF DECHLORINATION FOR
 THE WASTE WATER DISCHARGING TO THE STORM SYSTEM- SEC.
 90-205 (1) WPB CODE OR ORDINANCES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By lcrespo Date 2022-01-31 Time 11:31 Rev Time 0.00
Received By lcrespo Date 2022-01-31 Time 11:31 Sent To  
Notes
2022-01-31 11:31:5812/17/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW? THE PUMP'S
 MAXIMUM FLOW FROM ITS PUMP CURVE IS NO LONGER ALLOWED
 TO BE USED IN DETERMINING THE MAXIMUM SYSTEM FLOW RATE
 PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE
 2013 EDITION ADDRESSES THE FLOW RATE IN GALLONS PER
 MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM SYSTEM FLOW
 RATE DOES NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF
 THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN COVER). THE
 TDH CALCULATIONS MUST INCLUDE ALL THE SYSTEM
 COMPONENTS, INCLUDING SUCTION AND RETURN PIPING,
 FITTINGS, VALVES, AND FILTER. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
  
 2. WOULD YOU PLEASE SUBMIT THE POOL PUMP CURVE AND
 IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC
 TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS
 NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1.
  
 3. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAIN, HEATER, FILTER, AND PUMP, PER THE WPB AMENDMENTS
 TO FBC SEC. 107.2.1.
  
 4. A SEPARATE PERMIT IS REQUIRED FOR RPZ BACKFLOW
 DEVICE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 5. THE OVERFLOW CANNOT DISCHARGE TO THE SANITARY SYSTEM
 PER WPB CODE OF ORDINANCES CHAPTER 90, ART. III,
 SEC.90-126 (B) (5) UNLESS SPECIFICALLY AUTHORIZED BY
 THE CITY IN WRITING. PLEASE CONTACT THE CITY'S
 ENGINEERING DEPARTMENT AT 561-494-1085. THIS SECTION OF
 THE CODE PROHIBITS DISCHARGING POOL WATER TO THE
 SANITARY SEWER WITHOUT WRITTEN PERMISSION: HTTPS://LIBR
 ARY.MUNICODE.COM/FL/WEST_PALM_BEACH/CODES/CODE_OF_ORDIN
 ANCES?NODEID=PTIICOOR_CH90UT_ARTIIISESEDI_S90-126PRLIDI
  
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-08-11 Cont ID  
Sent By ccole Date 2022-08-11 Time 07:31 Rev Time 0.00
Received By ccole Date 2022-08-11 Time 07:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-08-04 Cont ID  
Sent By ccole Date 2022-08-04 Time 14:59 Rev Time 0.00
Received By ccole Date 2022-08-04 Time 14:42 Sent To  
Notes
2022-08-04 15:00:10SIGNATURE REVIEW
 PERMIT- 22010612
 8/4/2022
  
 RESULTS: DENIED.
  
 1) SHEETS SP-4.03 & SP-4.04 APPEAR TO HAVE SCANNED
 DIGITAL SIGNATURES AND SEALS WHICH ARE INCAPABLE OF
 BEING VERIFIED. ENGINEER?S PLANS AND DETAILS SUBMITTED
 ELECTRONICALLY SHALL BEAR DIGITAL SIGNATURES AND SEALS
 WHICH ARE CAPABLE OF BEING VERIFIED USING APPROVED
 SOFTWARE- FL. STATUTE 471.025 AND SECTION 61G15-23.005.
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-19 Cont ID  
Sent By ccole Date 2022-04-19 Time 10:24 Rev Time 0.00
Received By ccole Date 2022-04-18 Time 08:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-23 Cont ID  
Sent By rmcdouga Date 2022-03-23 Time 13:49 Rev Time 0.00
Received By rmcdouga Date 2022-03-23 Time 13:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-24 Cont ID  
Sent By eschneid Date 2022-02-24 Time 14:19 Rev Time 0.25
Received By eschneid Date 2022-02-24 Time 14:19 Sent To  
Notes
***NONE***