| 2022-02-02 14:52:55 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22010567 |
| | ADD: 1501 PRESIDENTIAL WAY # 3B |
| | CONT: PETRA BUILDERS GROUP |
| | TEL: 561-933-1818 |
| | EMAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 02/2022 |
| | ACTION: DENIED |
| | |
| | 1) THE TITLE SHEET T.1 SHOWS THE OCCUPANCY AS BUSINESS |
| | AND THE OCCUPANT LOAD FACTOR AS 100. PLEASE BE AWARE |
| | UNDER THE 2020 FBC-BUILDING CODE THE OCCUPANT LOAD |
| | FACTOR IS 150. 920SF/150= 7 OCCUPANTS 2020 FBC-BUILDING |
| | CODE TABLE 1004.5. |
| | |
| | 2) SHEET A2.1: |
| | 2A) NOTE # 4 INDICATES 12-INCH-WIDE COUNTER @ 36 INCHES |
| | A. F. F. 2020 ACCESS. CODE 904.3.3 CHECK WRITING |
| | SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL |
| | COMPLY WITH 902.3HEIGHT. |
| | THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM |
| | AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2B) NOTE # 5 INDICATES 12-INCH-WIDE COUNTER @ 42 INCHES |
| | A. F. F. ) 902.3 HEIGHT. THE TOPS OF WORK SURFACES |
| | SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. |
| | |
| | 2C) FOR BOTH COMMENTS 2A & 2B PLEASE PROVIDE THE CLEAR |
| | FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A SIDE |
| | APPROACH OR 306 A FORWARD APPROACH SHALL BE PROVIDED, |
| | KNEE AND TOE CLEARANCE COMPLYING WITH 306. |
| | |
| | 2D) PLEASE PROVIDE COMPLIANCE WITH ACCESS. CODE 304.2 |
| | CLEAR FLOOR SPACE (CIRCLE OR T SHAPE) FOR TURNING FROM |
| | DOOR 101 TO HALL 112 TOWARDS TREATMENT ROOM 110. |
| | |
| | 2E) ROOM 107 STERILE SHOWS AN OPEN SPACE PULL OUT SHELF |
| | AND OUTLET BEHIND. THE BOTTOM OF THE SHELF IS AT A |
| | HEIGHT OF 5 FEET ABOVE A. F. F. THIS DOES NOT MEET THE |
| | REACH RANGES AND OPERABLE PARTS. SHEET A.5 DETAIL 4. |
| | 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1 |
| | UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| | 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| | OBSTRUCTED HIGH REACH. |
| | |
| | 309 OPERABLE PARTS 309.3 HEIGHT. OPERABLE PARTS SHALL |
| | BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| | SPECIFIED IN 308. |
| | 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH |
| | ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING, |
| | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED |
| | TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM. |
| | 2F)(1) ROOM 109 LAB GIVE DETAIL 3 ON A.5 WITH THE |
| | COUNTERTOP HEIGHT OF 3FEET WITH A SINK ALSO IN IT. |
| | 2020 ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF |
| | WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2F)(2) 2020 FBC-ACCESSIBILITY CODE SECTION 606.3 |
| | HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH |
| | THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE |
| | 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 2G) NOTE: SPRAY POLYISO OPEN CELL FOAM TO UNDERSIDE OF |
| | DECK, USE CERTIFIED CONTRACTOR FOR THIS APPLICATION. |
| | PLEASE PROVIDE HOW THE APPLICATOR IS TO GAIN ACCESS TO |
| | THE UNDERSIDE OF ROOF DECK. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. PLEASE SHOW COMPLIANCE WITH |
| | SECTION 1203.3 UNVENTED ATTIC AND UNVENTED ENCLOSED |
| | RAFTER ASSEMBLIES 2020 FBC-B. |
| | |
| | 2H) NOTE: SPRAY POLYISO OPEN CELL FOAM TO UNDERSIDE OF |
| | DECK PLEASE PROVIDE A ICC-ES EVALUATION REPORT OR |
| | EQUIVALENT REPORT. PLEASE PROVIDE COMPLIANCE WITH |
| | 2603.4.1.6 PROTECTION REQUIRED AN IGNITION BARRIER AND |
| | SECTION 2603.4 THERMAL BARRIERS. ADDITIONAL |
| | REQUIREMENTS MAY BE REQUIRED ONCE REPORT IS SUBMITTED. |
| | |
| | 2I) RESTROOM 105 SEE SHEET A.3 ROOM FINISH SCHEDULE. |
| | THE SCHEDULE INDICATES THE RESTROOM WALLS ARE TO HAVE A |
| | PAINT FINISH. 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. |
| | THIS COMMENT IS A RESULT OF THE BUILDING OFFICIAL |
| | INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS & |
| | SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED |
| | A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | |
| | 2I)(1) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF |
| | SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT |
| | LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL |
| | ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A |
| | TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 2I)(2) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET |
| | WALLS SHALL COMPLY WITH 1210.2. |
| | |
| | 2I)(3) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS |
| | AND PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY |
| | WITH SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 2I)(4) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED |
| | AS A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND |
| | WALLS AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| | FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| | THE MANUFACTURE?S RECOMMENDATIONS. |
| | |
| | 3J) RESTROOM 105 SHEET A.3 DOOR SCHEDULE DOES NOT STATE |
| | A MEANS OF LOCKING THE DOOR FOR PRIVACY IS REQUIRED. |
| | 2020 FBC-BUILDING SECTION 2902.3.5 DOOR LOCKING. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |