Plan Review Details - Permit 22010542
Plan Review Stops For Permit 22010542
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-03-23 Cont ID  
Sent By cpuell Date 2022-03-23 Time 11:27 Rev Time 0.00
Received By cpuell Date 2022-03-23 Time 11:27 Sent To  
Notes
2022-03-23 11:28:51PLANS INDICATE NO KITCHEN, ADDRESS APPROPRIATE FOR
 PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-19 Cont ID  
Sent By jgomez Date 2022-07-19 Time 16:05 Rev Time 0.00
Received By jgomez Date 2022-07-19 Time 13:37 Sent To  
Notes
2022-07-19 16:07:40BUILDING REVIEW APPROVED WITH PROVISO:
 1- DEFERRED SUBMITTALS: PROVIDE PRODUCT APPROVAL FOR
 (NOTE: PROVIDE FOR REVIEW PRIOR TO INSTALLATION TO
 AVOID CONFLICTS/DELAYS).
 A)FLAT ROOF AND MARK ASSEMBLY TO BE INSTALLED.
 B)SHUTTERS AS SHOWN ON ADDITION/STUDIO (BARN TYPE). AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 2- ALL PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING
 BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-27 Cont ID  
Sent By jgomez Date 2022-06-27 Time 14:32 Rev Time 0.00
Received By jgomez Date 2022-06-27 Time 10:07 Sent To  
Notes
2022-06-27 14:33:19RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010542
  
 NOTE:
 APARTMENT ADDITION: SEC. 606 FBC-EXISTING BUILDING.
 SEC. 1101.1 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 MAIN HOUSE: LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING
 BUILDING. SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 GARAGE CONVERSION: CHANGE OF OCCUPANCY SEC. 605 AND
 SEC. 1001.2.1, SEC. 604 AND SEC. 901.2, SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW WORK SHALL COMPLY WITH
 THE MATERIALS AND METHODS REQUIREMENTS IN THE FLORIDA
 BUILDING CODE.
  
 1- OK.
 2- OK.
 3- OK.
  
 4-ADDITION AND GARAGE CONVERSION TO STUDIO COMMENTS:
  
 ORIGINAL COMMENT:
 A)ENTRY DOOR DOESN'T COMPLY WITH THE MINIMUM CLEAR
 WIDTH REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. REVISE
 AS REQUIRED.
  
 RESPONSE:
 DOOR SCHEDULE WAS NOT REVISED. DOOR SIZE 2'-7 1/4" WIDE
 DOOR DOESN'T PROVIDE THE MINIMUM REQUIRED CLEAR WIDTH
 OF 32". SEE SEC. R311.2 FBC-RESIDENTIAL FOR PROPER WAY
 OF MEASURING THE CLEAR WIDTH AND REVISE DOOR SIZE AS
 REQUIRED.
  
 ORIGINAL COMMENT:
 B)GUEST BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1
 FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE
 IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED.
 CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR
 A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT
 MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED
 AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW
 SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE
 WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS.
  
 RESPONSE:
 SINGLE HUNG WINDOW SIZE 4'-0" WIDE X 4'-11 1/2" HIGH
 DOESN'T SEEM TO COMPLY WITH THE REQUIRED 24" CLEAR
 OPENING HEIGHT. TYPICALLY, 4'-11 1/2" HIGH WINDOWS
 DON'T PROVIDE THE 24" CLEAR OPENING HEIGHT. REVISE SIZE
 AS REQUIRED OR PROVIDE MANUFACTURER'S CUT SHEETS
 SHOWING THAT SPECIFIED WINDOW SIZE PROVIDES 24" CLEAR
 OPENING HEIGHT.
  
 5-MAIN HOUSE COMMENTS:
  
 ORIGINAL COMMENT.
 A)BOTH BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1
 FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE
 IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED.
 CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR
 A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT
 MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED
 AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW
 SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE
 WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS.
  
 RESPONSE:
 SINGLE HUNG WINDOW SIZE 4'-0" WIDE X 5'-0" HIGH DOESN'T
 SEEM TO COMPLY WITH THE REQUIRED 24" CLEAR OPENING
 HEIGHT. TYPICALLY, 5'-0" HIGH WINDOWS DON'T PROVIDE THE
 24" CLEAR OPENING HEIGHT. REVISE SIZE AS REQUIRED OR
 PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THAT
 SPECIFIED WINDOW SIZE PROVIDES 24" CLEAR OPENING
 HEIGHT.
  
 ORIGINAL COMMENT:
 B)SPECIFY SIZE OF INTERIOR DOORS. NEED TO SHOW
 COMPLIANCE WITH BATHROOM MINIMUM CLEAR DOOR OPENING AS
 REQUIRED BY SEC. R320.1.1 FBC-RESIDENTIAL.
  
 RESPONSE:
 SIZES OF INTERIOR DOORS WAS NOT PROVIDED. UNABLE TO
 CHECK COMPLIANCE.
 NOTE: ONLY 2'-8" DOOR OR WIDER DOORS COMPLY TO PROVIDE
 THE REQUIRED CLEAR OPENING WHEN DOOR IS OPEN.
  
 6- OK.
 7- OK.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON
 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 PARTIALLY ADDRESSED. NEW NOA 20-0518.02 WAS SUBMITTED
 BUT APPROVED ASSEMBLY TO BE INSTALLED WAS NOT
 IDENTIFIED. CLEARLY MARK APPROVED ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED RAS 117 CALCULATIONS IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES.
  
 B) OK.
  
 ORIGINAL COMMENT:
 C)SHUTTERS: CLARIFY WHY SUBMITTING "ASTRO GUARD"
 FLEXIBLE WIND ABATEMENT SYSTEM. WHERE IS THIS SYSTEM
 GOING TO BE INSTALLED?. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 RESPONSE:
 NO CLARIFIED AND NO INSTALLATION SCHEDULE WAS PROVIDED
 (IF SHUTTERS WILL BE INSTALLED).
  
 ORIGINAL COMMENT:
 D)ROOF TILE SHOWN IN THE ADDITION.
 NOTE: CLEARLY MARK/SPECIFY TILE FASTENING METHOD. IF
 SPECIFYING SCREWS, THEN SPECIFY THE NUMBER AND SIZE OF
 SCREWS TO BE USED FOR ALL ROOF ZONES. IF USING
 ADHESIVE, THEN CLEARLY MARK/SPECIFY PADDY SIZE.
  
 RESPONSE:
 PARTIALLY COMPLIED. NEED TO CLEARLY MARK/SPECIFY
 ADHESIVE PADDY SIZE.
  
 E) OK.
  
 DEFERRED SUBMITTAL.
 F)SHUTTERS AS SHOWN ON ADDITION/STUDIO (BARN TYPE). AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 NOTE:
 PLEASE MAKE SURE PRODUCT APPROVALS UPLOADED TO
 PROJECTDOX HAVE THE CORRECT FILE NAME. FOR EXAMPLE
 THERE IS ONE NAMED CASEMENT WINDOW BUT THE DRAWINGS
 UPLOADED TO THIS FILE ARE FOR ALUMINUM FRENCH DOORS.
 REVISE AS REQUIRED. COORDINATE WITH PERMIT LIBRARIAN IF
 NECESSARY.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ALSO TO PRODUCT APPROVALS ALREADY
 SUBMITTED.
  
 10- OK. PER RESPONSE LETTER ENERGY CALCULATIONS WILL
 NOT BE SUBMITTED. HISTORIC CONTRIBUTING STRUCTURES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By jgomez Date 2022-03-22 Time 18:14 Rev Time 0.00
Received By jgomez Date 2022-03-21 Time 14:35 Sent To  
Notes
2022-03-22 14:27:15RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22010542
  
 NOTE:
 APARTMENT ADDITION: SEC. 606 FBC-EXISTING BUILDING.
 SEC. 1101.1 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 MAIN HOUSE: LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING
 BUILDING. SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 GARAGE CONVERSION: CHANGE OF OCCUPANCY SEC. 605 AND
 SEC. 1001.2.1, SEC. 604 AND SEC. 901.2, SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW WORK SHALL COMPLY WITH
 THE MATERIALS AND METHODS REQUIREMENTS IN THE FLORIDA
 BUILDING CODE.
  
 1)SEPARATE PERMITS. THERE ARE TWO SEPARATE BUILDINGS IN
 THIS PROPERTY. A SEPARATE PERMIT APPLICATION AND
 SUB-PERMITS ARE REQUIRED FOR EACH BUILDING. PLEASE
 SUBMIT A SEPARATE PERMIT APPLICATION AND SUB-PERMITS
 FOR THE APARTMENT ADDITION/GARAGE CONVERSION TO STUDIO.
 SAME PLANS CAN BE USED. CLEARLY SPECIFY THE VALUATION
 FOR THE APARTMENT ADDITION/GARAGE CONVERSION AND THE
 VALUATION FOR THE MAIN HOUSE ALTERATION.
 NOTE: SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE
 INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS
 RETENTION. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 2- LOT DRAINAGE. PROPOSED WORK AFFECTS THE LOT
 DRAINAGE. PROVIDE DRAINAGE PLAN SHOWING HOW THE SURFACE
 DRAINAGE IS KEPT WITHIN THE LOT AND NOT DIVERTED TO
 ADJACENT PROPERTIES.
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 3- PROVIDE SURVEY SHOWING THE PROPOSED ADDITION AND
 SETBACKS. SEC. 107.2.5 CITY AMENDMENTS. SEC. 107.3.5.3
 CITY AMENDMENTS.
  
 4-ADDITION AND GARAGE CONVERSION TO STUDIO COMMENTS:
 A)ENTRY DOOR DOESN'T COMPLY WITH THE MINIMUM CLEAR
 WIDTH REQUIRED BY SEC. R311.2 FBC-RESIDENTIAL. REVISE
 AS REQUIRED.
  
 B)GUEST BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1
 FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE
 IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED.
 CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR
 A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT
 MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED
 AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW
 SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE
 WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS.
  
 C)ROOF SCUPPERS: SPECIFY SIZE OF NEW SCUPPERS AND
 PROVIDE COMPLETE INFORMATION OF OVERFLOW SCUPPERS
 (LOCATION AND SIZE) AS REQUIRED BY SEC. R903.4.1
 FBC-RESIDENTIAL.
 NOTE: KEEP IN MIND THERE ARE 3 DIFFERENT ROOF AREAS.
  
 D)ROOF PLAN: SPECIFY ROOF PITCH AS REQUIRED BY SEC.
 R905.11.1 SLOPE.
 MODIFIED BITUMEN MEMBRANE ROOFS SHALL HAVE A DESIGN
 SLOPE OF NOT LESS THAN ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) FOR DRAINAGE
  
 5-MAIN HOUSE COMMENTS:
 A)BOTH BEDROOM WINDOWS DON'T SEEM TO COMPLY WITH THE
 EGRESS MINIMUM OPENING AREAS REQUIRED BY SEC. R310.2.1
 FBC-RESIDENTIAL. SIZE SPECIFIED ON THE WINDOW SCHEDULE
 IS NOT SHOWN ON THE WINDOW PRODUCT APPROVAL SUBMITTED.
 CLARIFY IF SIZE SPECIFIED IN THE WINDOW SCHEDULE IS FOR
 A CUSTOM MADE WINDOW. SPECIFY SIZE OF WINDOW THAT
 MATCHES SIZE SHOWN WINDOW PRODUCT APPROVAL SUBMITTED
 AND PROVIDE MANUFACTURER'S CUT SHEETS SHOWING
 COMPLIANCE WITH THE EGRESS REQUIREMENTS.
 NOTE: KEEP IN MIND MULLION SIZE WHEN SPECIFYING WINDOW
 SIZE AND MASONRY OPENING SIZE. COORDINATE MULLION SIZE
 WITH PRODUCT APPROVAL COMMENT FOR WINDOW MULLIONS.
  
 B)SPECIFY SIZE OF INTERIOR DOORS. NEED TO SHOW
 COMPLIANCE WITH BATHROOM MINIMUM CLEAR DOOR OPENING AS
 REQUIRED BY SEC. R320.1.1 FBC-RESIDENTIAL.
  
 C) FOOTING SCHEDULE IS MISSING SPECIFICATIONS FOR NEW
 MF20.12 FOOTING SHOWN ON THE FOUNDATION PLAN. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 6- SHEET S-103:
 A)REVISE WIND LOAD SCHEDULE. SHOW NEW ROOF AREAS AS
 REQUIRED BY CURRENT 2020 CODE FIGURE R3101.2(7)
 FBC-RESIDENTIAL.
  
 B)REVISE DIAGRAMS SHOWN BELOW THE WIND LOAD SCHEDULE.
 SHOW NEW ROOF AREAS AS REQUIRED BY CURRENT 2020 CODE
 FIGURE R3101.2(7) FBC-RESIDENTIAL.
  
 C)REVISE CORNER DISTANCE "A" SHOWN BELOW THE WIND LOAD
 SCHEDULE. CORNER DISTANCE IS 4'-0" MIN. AS REQUIRED BY
 NOTE "A" OF CURRENT 2020 CODE FIGURE R3101.2(7)
 FBC-RESIDENTIAL.
  
 D)PLYWOOD SHEATHING NAILING SCHEDULE: REVISE ROOF
 SHEATHING NAILING TYPE, SIZE AND SPACING. NEED TO USE
 RING SHANK NAILS AND ROOF SHEATHING NEEDS TO BE NAILED
 WITH AT 4 INCHES O.C. IN THE FIELD AND EDGES AS
 REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1
 FBC-RESIDENTIAL. REVISE NAILING ON ROOF ZONES
 ACCORDINGLY. COORDINATE WITH COMMENT 6(A)ABOVE.
 NOTE: REVISE SPECIFICATIONS OR PROVIDE CALCULATIONS
 SHOWING THAT SPECIFIED NAIL TYPE AND SPACING MATCHES OR
 EXCEEDS TABLE R803.2.3.1 FBC-RESIDENTIAL MINIMUM
 REQUIREMENTS.
  
 E) CLARIFY WHY THE LOADS ON THE DESIGN LOAD SCHEDULE
 ARE HIGHER FOR THE GARAGE THAN THE LOADS SHOWN FOR THE
 MAIN HOUSE. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 7- PROVIDE DOORS AND WINDOWS STRUCTURAL BUCK DETAILS
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR/WINDOW FRAME.
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON
 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)FOLDING DOOR AS SHOWN ON PLANS. NEED COMPLETE PRODUCT
 APPROVAL. NEED TO PROVIDE FLORIDA PRODUCT APPROVAL
 COVER PAGE THAT CORRESPONDS TO DRAWINGS SUBMITTED.
  
 C)SHUTTERS: CLARIFY WHY SUBMITTING "ASTRO GUARD"
 FLEXIBLE WIND ABATEMENT SYSTEM. WHERE IS THIS SYSTEM
 GOING TO BE INSTALLED?. AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 D)ROOF TILE SHOWN IN THE ADDITION.
 NOTE: CLEARLY MARK/SPECIFY TILE FASTENING METHOD. IF
 SPECIFYING SCREWS, THEN SPECIFY THE NUMBER AND SIZE OF
 SCREWS TO BE USED FOR ALL ROOF ZONES. IF USING
 ADHESIVE, THEN CLEARLY MARK/SPECIFY PADDY SIZE.
  
 E)NEED FOAM ADHESIVE PRODUCT APPROVAL IF USING FOAM.
 SEE ROOF TILE NOA FOR LISTED FOAM.
  
 F)SHUTTERS AS SHOWN ON ADDITION/STUDIO (BARN TYPE). AND
 PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ALSO TO PRODUCT APPROVALS ALREADY
 SUBMITTED.
  
 10- THIS HOUSE IS A CONTRIBUTING HISTORIC HOUSE. ENERGY
 CALCULATIONS ARE NOT REQUIRED. BUT IF APPLICANT WANTS
 THEM TO BE PART OF THE CONSTRUCTION DOCUMENTS, THEN
 REVISE THEM AS FOLLOWS (NOTE: COORDINATE WITH
 ARCHITECTURAL PLANS TO AVOID CONFLICTS/DELAYS):
  
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER NAME, PERMIT AND JURISDICTION NUMBER
 (THIS JURISDICTION IS 604700). SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE THE NAME OF THE PERSON DOING THE CALCULATIONS
 AS REQUIRED BY SEC. R405.4.2.1 FBC-ENERGY CONSERVATION.
  
 D) BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-07-11 Cont ID  
Sent By mpeterso Date 2022-07-11 Time 14:24 Rev Time 0.00
Received By mpeterso Date 2022-07-11 Time 14:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-05-23 Cont ID  
Sent By mpeterso Date 2022-05-23 Time 11:33 Rev Time 0.00
Received By mpeterso Date 2022-05-23 Time 11:33 Sent To  
Notes
2022-05-23 11:34:35ELECTRIC REVIEW FAILED
 1) PLEASE LOCATE ALL ELECTRIC EQUIPMENT ATS, PANELS A,
 B, AND C ON ELECTRIC FLOOR PLAN AS REQUESTED IN LAST
 REVIEW. FBC 107.2
 2) PLEASE DETAIL GROUNDING ELECTRODE SYSTEM FOR GUEST
 HOUSE ON ELECTRICAL PANEL ON RISER DIAGRAM AS REQUESTED
 IN LAST REVIEW. NEC 250.32
 3) PLEASE INDICATE SIZE OF OVERCURRENT PROTECTION FOR
 ALL PANELS IN METER MAIN. NEC 215.5
 4) PLEASE INDICATE SIZE OF OVERCURRENT PROTECTION FOR
 PANEL C, AND DETAIL PANEL C ELECTRIC LOAD ON LOAD
 CALCULATION. NEC 215.5
 5) MAIN HOUSE KITCHEN APPEARS TO REQUIRE AN ADDITIONAL
 RECEPTACLE ON COUNTERTOP LOCATED NEXT TO PASSTHROUGH.
 NEC 210.52
 6) MAIN AND GUEST HOUSE APPEAR TO REQUIRE OUTDOOR
 RECEPTACLES ON MANY OF THE OUTDOOR BALCONIES, PATIOS OR
 DECKS NEC 210.52
 7) PLEASE INDICATE LOCATION OF OUTSIDE AIRCONDITIONING
 UNITS ON ELECTRIC FLOOR PLAN AS REQUESTED IN LAST
 REVIEW. ENSURE TO COMPLY WITH NEC 210.63
 8) PLEASE INDICATE A SMOKE/CARBON ALARM IN MAIN HOUSE
 MASTER BEDROOM AND GUEST HOUSE MASTER BEDROOM, GUEST
 BED ROOM AND HALL. FBC 553.883
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-07 Cont ID  
Sent By mpeterso Date 2022-02-07 Time 15:15 Rev Time 0.00
Received By mpeterso Date 2022-02-07 Time 15:15 Sent To  
Notes
2022-02-07 15:17:22ELECTRIC PLANE REVIEW FAILED
 1) PLEASE INDICATE ALL ELECTRIC METER MAINS, ELECTRIC
 PANELS ON ELECTRICAL DRAWINGS. FBC 107.2
 2) PLEASE PROVIDE PANEL SCHEDULES AND LOAD
 CALCULATIONS. FBC 107.2 NEC 215.5
 3) PLEASE INDICATE AIR HANDLING AND CONDENSING UNITS
 LOCATIONS AND THERE ASSOCIATED CONDUCTORS ON ELECTRICAL
 PLANS
 4) IT APPEARS GUEST HOUSE WILL REQUIRE MORE THAN ONE
 MULTI WIRE CIRCUIT. PLEASE INDICATE THAT GUEST HOUSE
 HAS SUBPANEL FOR GUEST HOUSE LOADS. AS PER NEC 225.30.
 .
 IN ADDITION, SINCE THIS GUEST HOUSE APPEARS IT WILL
 REQUIRE AN ELECTRIC SUB PANEL, INDICATE THE NECESSARY
 GROUNDING ELECTRODE SYSTEM AS PER NEC 250.32
 5) REVISE ELECTRICAL RISER DIAGRAM AS NECESSARY TO
 COMPLY WITH THE ABOVE COMMENTS
 6) PLEASE CHANGE NOMENCLATURE FOR SMOKE DETECTORS TO
 INDICATE NECESSARY COMBINATION SMOKE/ CARBON ALARMS AS
 REQUIRED DUE TO GAS APPLIANCES PRESENT.
 7) RECEPTACLE SPACING IN SEVERAL AREAS APPEAR TO BE
 INADEQUATE ACCORDING TO NEC 210.52 (A)-(I)
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2022-10-20 Cont ID  
Sent By rwbrown Date 2022-10-20 Time 09:30 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-10-20 09:31:24GAS SUB ON THIS MASTER PERMIT NOT REQUIRED. GAS PULLED
 AS SEPARATE PERMIT 22100815

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-05-04 Cont ID  
Sent By rwbrown Date 2022-05-04 Time 08:31 Rev Time 0.00
Received By rwbrown Date 2022-05-04 Time 08:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-01-28 Cont ID  
Sent By abelisle Date 2022-01-28 Time 21:56 Rev Time 0.00
Received By abelisle Date 2022-01-28 Time 21:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2022-07-22 Cont ID  
Sent By amhamilt Date 2022-07-22 Time 09:40 Rev Time 0.00
Received By amhamilt Date 2022-07-22 Time 09:40 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-05-25 Cont ID  
Sent By amhamilt Date 2022-05-25 Time 11:57 Rev Time 0.00
Received By amhamilt Date 2022-05-25 Time 11:57 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-03-07 Cont ID  
Sent By amhamilt Date 2022-03-07 Time 16:47 Rev Time 0.00
Received By amhamilt Date 2022-03-07 Time 16:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-26 Cont ID  
Sent By shill Date 2022-07-26 Time 10:19 Rev Time 0.00
Received By shill Date 2022-07-01 Time 14:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-27 Cont ID  
Sent By jgomez Date 2022-06-27 Time 14:41 Rev Time 0.00
Received By jgomez Date 2022-04-29 Time 08:57 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-23 Cont ID  
Sent By cpuell Date 2022-03-23 Time 11:28 Rev Time 0.00
Received By cpuell Date 2022-01-21 Time 11:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2022-08-17 Cont ID  
Sent By lmarchan Date 2022-08-17 Time 12:59 Rev Time 0.00
Received By lmarchan Date 2022-07-21 Time 13:50 Sent To  
Notes
2022-08-01 13:06:48MU-2022-034206-0000 - $2,491.56 PAID AO
2022-07-21 13:50:537/21/22 EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-07-19 Cont ID  
Sent By jgomez Date 2022-07-19 Time 16:17 Rev Time 0.00
Received By jgomez Date 2022-07-19 Time 16:17 Sent To  
Notes
2022-07-19 16:17:35IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By jgomez Date 2022-03-22 Time 14:28 Rev Time 0.00
Received By jgomez Date 2022-03-22 Time 14:27 Sent To  
Notes
2022-03-22 14:28:45IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By medwards Date 2022-05-10 Time 10:41 Rev Time 0.00
Received By medwards Date 2022-05-10 Time 10:41 Sent To  
Notes
2022-05-10 10:43:55A SEPARATE PERMIT IS REQUIRED FOR THE STUDIO GUEST
 HOUSE. ME
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-02 Cont ID  
Sent By medwards Date 2022-02-02 Time 13:15 Rev Time 0.00
Received By medwards Date 2022-02-02 Time 13:15 Sent To  
Notes
2022-02-02 13:15:521ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010542
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FIELD STUDIO HOUSE WILL NEED SEPARATE PERMITS.
 PLEASE REFERENCE THE MASTER PERMIT NUMBER ON THE FIELD
 STUDIO HOUSE.
  
 2) THE ENERGY CALCULATIONS SUBMITTED IS FOR THE FIELD
 STUDIO HOUSE. PLEASE SUBMIT THE ENERGY CALCULATIONS FOR
 THE MAIN HOUSE. FBC EC 101.5.1.1.2
  
 3) THE DRAWING SUBMITTED DOES NOT SHOW ANY DOORS.
 PLEASE SUBMIT A DRAWING THAT CLEARLY SHOWS DOOR,
 LOUVERED DOORS IF INSTALLED IN FRONT OF THE AHU?S AND
 THE RETURN AIR PATH BACK TO THE AHU?S. FBC 107.2.1
  
 4) PLEASE SHOW THE ANCHORAGE OF THE CONDENSING UNITS.
 FBC RES M1307.2
  
 5) PLEASE SHOW THE CONDENSATE DRAIN PIPING MATERIAL,
 SIZE AND TERMINATION LOCATION. FBC RES M1411.3
  
 6) PLEASE SHOW THE HOOD LOCATION EXHAUST DUCT, CFM?S OF
 THE HOOD EXHAUST AND THE TERMINATION LOCATION OF THE
 HOOD EXHAUST FOR BOTH STRUCTURES. FBC RES M1503.4
  
 7) PLEASE SHOW THE DRYER LOCATION AND THE EXHAUST DUCT
 TERMINATION LOCATION FOR BOTH STRUCTURES. FBC RES M1502
  
 8) MAIN HOUSE: PLEASE SHOW THE BATH EXHAUST FANS AND
 THE EXHAUST TERMINATION LOCATION. FBC RES M1507.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-04 Cont ID  
Sent By rwbrown Date 2022-05-04 Time 08:31 Rev Time 0.00
Received By rwbrown Date 2022-05-04 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-01-28 Cont ID  
Sent By abelisle Date 2022-01-28 Time 21:55 Rev Time 0.00
Received By abelisle Date 2022-01-28 Time 21:31 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2022-07-19 Cont ID  
Sent By jgomez Date 2022-07-19 Time 16:18 Rev Time 0.00
Received By jgomez Date 2022-07-19 Time 15:56 Sent To  
Notes
2022-07-19 16:21:181- DEFERRED SUBMITTALS: PROVIDE PRODUCT APPROVAL FOR
 (NOTE: PROVIDE FOR REVIEW PRIOR TO INSTALLATION TO
 AVOID CONFLICTS/DELAYS).
 A)FLAT ROOF AND MARK ASSEMBLY TO BE INSTALLED.
 2- ALL PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING
 BY DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 NOTE:
 ROOF TILE NOA 18-0119.03 IS OK.
 ROOF TILE ADHESIVE FL6332-R9 IS OK.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-06-27 Cont ID  
Sent By jgomez Date 2022-06-27 Time 14:38 Rev Time 0.00
Received By jgomez Date 2022-06-27 Time 14:38 Sent To  
Notes
2022-06-27 14:38:50ROOFING REVIEW:
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 ORIGINAL COMMENT:
 A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON
 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 PARTIALLY ADDRESSED. NEW NOA 20-0518.02 WAS SUBMITTED
 BUT APPROVED ASSEMBLY TO BE INSTALLED WAS NOT
 IDENTIFIED. CLEARLY MARK APPROVED ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED RAS 117 CALCULATIONS IF
 THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 FOR ALL ROOF ZONES.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By jgomez Date 2022-03-22 Time 14:29 Rev Time 0.00
Received By jgomez Date 2022-03-22 Time 14:29 Sent To  
Notes
2022-03-22 14:31:17ROOFING REVIEW:
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)FLAT ROOF. NOA 15-0729.18 SUBMITTED EXPIRED ON
 09/22/20. NEED CURRENT PRODUCT APPROVAL AND CLEARLY
 MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 B)ROOF TILE SHOWN IN THE ADDITION.
 NOTE: CLEARLY MARK/SPECIFY TILE FASTENING METHOD. IF
 SPECIFYING SCREWS, THEN SPECIFY THE NUMBER AND SIZE OF
 SCREWS TO BE USED FOR ALL ROOF ZONES. IF USING
 ADHESIVE, THEN CLEARLY MARK/SPECIFY PADDY SIZE.
  
 C)NEED FOAM ADHESIVE PRODUCT APPROVAL IF USING FOAM.
 SEE ROOF TILE NOA FOR LISTED FOAM.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ALSO TO PRODUCT APPROVALS ALREADY
 SUBMITTED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-19 Cont ID  
Sent By jgomez Date 2022-07-19 Time 15:52 Rev Time 0.00
Received By jgomez Date 2022-07-19 Time 15:52 Sent To  
Notes
2022-07-11 14:38:49ALL DRAWING PAGES PASSED SIGNATURE REVIEW THROUGH ADOBE
 OR BLUEBEAM. MP
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-23 Cont ID  
Sent By mpeterso Date 2022-05-23 Time 11:45 Rev Time 0.00
Received By mpeterso Date 2022-05-23 Time 11:45 Sent To  
Notes
2022-05-23 11:47:01ALL DRAWING PAGES PASSED SIGNATURE REVIEW THROUGH ADOBE
 OR BLUEBEAM. MP
2022-05-10 10:43:00DIGITAL SIGNATURE FOR MECHANICAL SHEETS APPROVED ME
  
2022-05-04 08:32:23PLMG PAGES SIGNED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-22 Cont ID  
Sent By jgomez Date 2022-03-22 Time 14:37 Rev Time 0.00
Received By jgomez Date 2022-03-22 Time 14:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-05-25 Cont ID  
Sent By amhamilt Date 2022-05-25 Time 11:57 Rev Time 0.00
Received By amhamilt Date 2022-05-25 Time 11:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-03-07 Cont ID  
Sent By amhamilt Date 2022-03-07 Time 16:47 Rev Time 0.00
Received By amhamilt Date 2022-03-07 Time 16:47 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy