| 2022-02-14 09:44:48 | 02/14/22 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE ISOMETRIC SHOWS A METER, AND THIS IS AN LP |
| | TANK; PLEASE CLARIFY IF THE LP TANK IS NOT BEING USED |
| | OR A GAS METER WILL BE ADDED PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 2. WOULD YOU PLEASE SHOW WHAT IS NEW AND EXISTING PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. THE CITY OF WEST PALM BEACH HAS A PERMIT (07030314) |
| | ON FILE FOR THE GENERATOR, AND IT IS NOT SHOWN ON THE |
| | SYSTEM OR NOTE. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 4. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | |
| | 5. THE TOTAL BTU LOAD FOR THE SYSTEM IS INCORRECT. THE |
| | EXISTING GAS SYSTEM MUST BE ADDED TO THE TOTAL BTU LOAD |
| | TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. THE |
| | EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM IF UNDERSIZED. SUBMIT A GAS PIPING |
| | RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| | APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| | SIZE, AND THE TYPE OF PIPE TO EACH APPLIANCE. |
| | |
| | 6. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| | AND THE PRESSURE MAY REQUIRE A REGULATOR FOR THIS UNIT |
| | AS PER THE MANUFACTURER'S SPECIFICATION. SUBMIT |
| | MANUFACTURER?S SPECIFICATIONS FOR THE PRESSURE |
| | REGULATORS. REGULATORS INSTALLED ON THE EXTERIOR OF THE |
| | BUILDING SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER |
| | THE 2020 FBC RES. SEC. G2421.1. |
| | |
| | 7. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 8. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF |
| | REGULATOR 1' OF EITHER SIDE FOR THE TANKLESS PER THE |
| | 2020 FBC RES. SEC G2421.2. |
| | |
| | 9. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON |
| | GAS ISOMERIC FOR THE TANKLESS PER THE 2020 FBC RES. |
| | SEC. G2420.5. |
| | |
| | 10. WOULD YOU PLEASE LABEL AND SHOW DRIP LEG ON |
| | TANKLESS 2020 FBC RES. SEC. G2419.2. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |