| 2022-01-18 07:33:05 | 01/18/22 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS |
| | FOR GAS TANKLESS AND STOVE EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1. GAS |
| | APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 2. WOULD YOU PLEASE SUBMIT THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON ISOMETRIC |
| | LISTING THE SIZING TABLES FROM GAS CODES OR ANOTHER |
| | STANDARD THAT WAS USED IN THE DESIGN OF THIS SYSTEM PER |
| | THE 2020 FBC RES. SEC. G2413.3. |
| | |
| | 3. WOULD YOU PLEASE SHOW THE ISOMETRIC DRAWING THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC RES. |
| | SECS. G2413.4.1, G2413.4.2. |
| | |
| | 4. WOULD YOU PLEASE SHOW THE TOTAL BTU LOAD ON THE |
| | SYSTEM PER THE WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 5. WOULD YOU PLEASE SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | THE 2 2020 FBC RES. SEC. G2413.4.1. |
| | |
| | 6. WOULD YOU PLEASE INDICATE THE SYSTEM'S DELIVERY |
| | PRESSURE (PSI) ON THE PLAN PER THE 2020 FBC FG SEC. |
| | 402.2 OR 2020 FBC RES. SEC. G2413.2. |
| | |
| | 7. PROVIDE INFORMATION FOR THE TERMINATION LOCATION OF |
| | THE EXHAUST VENT. THE EXIT TERMINAL OF A MECHANICAL |
| | DRAFT SYSTEM (IF INSTALLED) SHALL COMPLY WITH 2020 FBC |
| | FG SECS. 503.3.3, (1-6), 503.8 (1) (2). |
| | |
| | 8. WOULD YOU PLEASE SHOW THE CORRESPONDING EHD NUMBER |
| | OF THE CORRUGATED STAINLESS STEEL TUBING PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. IF APPLICABLE. |
| | |
| | 9. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR |
| | NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 10. THE TANKLESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1. |
| | |
| | 11. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT |
| | OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. |
| | SEC G2421.2. |
| | |
| | 12. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE |
| | ON GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5. THE |
| | SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT MOVING THE |
| | EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) GD, ACCESS. |
| | |
| | 13. DRIP LEG IS MISSING ON TANKLESS PER THE 2020 FBC |
| | RES. SEC. G2419.2. |
| | |
| | 14. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 15. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE |
| | INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE |
| | 403.5.3. WOULD YOU PLEASE NOTE ON PLANS. IF APPLICABLE. |
| | |
| | 16. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM |
| | THE STRUCTURE PER THE 2020 FBC SEC. R318.5. IF |
| | APPLICABLE. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |