| 2022-01-31 06:51:17 | 01/31/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS PERMITS WITH INSPECTIONS OF THE CURRENT |
| | SYSTEM. A SEARCH ON CITY RECORDS BACK TO 1998 HAS BEEN |
| | DONE AND THERE IS NO RECORD OF A PERMIT FOR INSTALLING |
| | AN LP TANK. A COMPLETE EVALUATION OF ALL GAS SYSTEMS |
| | AND EQUIPMENT WILL BE DONE ON A SEPARATE PERMIT, AND IF |
| | NOT TO CODE, IT MAY NEED TO BE BOUT UP TO CODE |
| | COMPLIANCE AT THE OWNER?S EXPENSE. WHAT OTHER |
| | APPLIANCES/EQUIPMENT IS SUPPLIED BY THIS "EXISTING" |
| | TANK? PROVIDE ALL BTU LOADS AND THE TOTAL LOAD ON THE |
| | SYSTEM. SINCE THERE IS NO RECORD OF A PERMIT FOR THE LP |
| | TANK, THE TANK MUST BE INCLUDED IN A SEPARATE PERMIT |
| | FOR THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 105.1. |
| | |
| | 2. WOULD YOU PLEASE SUBMIT THE MANUFACTURER?S |
| | SPECIFICATION SHEETS/INSTALLATION MANUAL FOR ALL LP GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH 2020 FBC FG SEC. |
| | 305.1. |
| | |
| | 3. A LICENSED LP CONTRACTOR REQUIRES A SEPARATE PERMIT |
| | FOR THE LP TANK PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 105.1. CFC LICENSE CON NOT TAKE RESPONSIBILITY OR |
| | INSTALL AN LP TANK. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| | REQUEST. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |
| | |