Plan Review Details - Permit 22010462
Plan Review Stops For Permit 22010462
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 08:03 Rev Time 0.00
Received By rmcphers Date 2022-02-15 Time 16:30 Sent To  
Notes
2022-02-16 08:04:24PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 08:26 Rev Time 0.00
Received By rmcphers Date 2022-02-15 Time 16:30 Sent To  
Notes
2022-02-16 08:26:23OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS - ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE DESIGNER OF RECORD FBC WPB 107.3.4
  
 2) PLEASE SHOW THE WIND DESIGN CRITERIA USED FOR THE
 WIND DESIGN FBC 1603.1.4
  
 3) PLEASE SHOW THE REQUIRED EXTERIOR COMPONET (DOOR
 OPENING) WIND DESIGN PRESSURES FBC 1609.1
  
 4) PLEASE SHOW THE RESTROOM WALL AND MOP SINK WALL
 FINISH PER FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 5) PLEASE SHOW RESTROOM FLOOR AND BASE BOARD PER FBC
 1210.2.1FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM).
  
 6) ACCESSIBLE RESTROOM - YOU SHOW 44" TO THE BOTTOM OF
 THE MIRROR - SHOULD BE 40" TO THE BOTTOM OF THE
 "REFLECTIVE SURFACE" - PLEASE SHOW MIRROR HEIGHT FROM
 THE FINISHED FLOOR TO THE BOTTOM OF THE "REFLECTIVE
 SURFACE" PER FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-02-08 Cont ID  
Sent By jleahy Date 2022-02-08 Time 16:33 Rev Time 0.00
Received By jleahy Date 2022-02-08 Time 16:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-01-25 Cont ID  
Sent By cwalker Date 2022-01-25 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-01-25 11:47:16FIRE PROVISO NOTES:
 1. LOCKS AND HARDWARE ON EXIT DOORS SHALL COMPLY WITH
 NFPA 101, CHAPTER 7, MEANS OF EGRESS. PROVIDE DETAILS
 OF EXIT DOOR HARDWARE.
 2. ACCESS CONTROL ON EXIT DOOR SHALL REQUIRE A SEPARATE
 PERMIT AND COMPLY WITH NFPA 101 7.2.1.6.2
 3. PROVIDE DETAILS ON INTERIOR FINISHES TO COMPLY WITH
 NFPA 101 CHAPTER 10, INTERIOR FINISH, CONTENTS, AND
 FURNISHINGS.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-02-02 Cont ID  
Sent By lcrespo Date 2022-02-02 Time 10:01 Rev Time 0.00
Received By lcrespo Date 2022-02-01 Time 14:42 Sent To  
Notes
2022-02-02 10:05:2502/02/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON RE-REVIEWING SUBMITTED CORRECTIONS.
  
 1. ON P04;
  
 A. THE BTU LOAD FOR THE WATER HEATER IS FOR A
 TANK-LESS, BUT THE PLAN SAYS AND SHOWS A TANK TYPE AND
 199 BTU'S ARE MOST TANK-LESS AND TANK TYPE ARE ABOUT 50
 BYU'S. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 B. WOULD YOU PLEASE SUBMIT MANUFACTURES SPECIFICATIONS
 FOR THE DRYER AND TANK-LESS TO VERIFY COMPLIANCE WITH
 2020 FBC FG SEC. 305.1.
  
 C. WOULD YOU PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC FG
 410.1.
  
 D. WOULD YOU PLEASE SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE 2020 FBC FG SEC. 304.1, 614.5 (CLOTHES
 DRYERS AND TANK-LESS). IF A MECHANICAL COMBUSTION AIR
 SUPPLY SYSTEM AIR IS BEING SUPPLIED, PLEASE PROVIDE
 INFORMATION OR IF METAL LOUVERS ARE BEING INSTALLED FOR
 THE COMBUSTION AIR. THE LOUVERS CANNOT BE LOCATED ON AN
 EXTERIOR WALL THAT IS FIRE RATED AS THE FIRE RATING OF
 THE WALL MUST BE MAINTAINED.
  
 E. WOULD YOU PLEASE SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF, AND ANCHORING ELEMENTS OF THE GAS VENT(S) PER THE
 2020 FBC FG SECS. 502 THRU 505.
  
 F. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC FG SEC
 410.2.
  
 G. IT SHOWS TWO WASHING MACHINES, BUT THERE ARE TWO
 DRYERS, AND IF THEY ARE STACKED, THE VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING THE EQUIPMENT PER THE 2020
 FBC SEC. G2403 (202) GD, ACCESS.
  
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT.
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE CORRECTION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY
 PAGES. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 08:27 Rev Time 0.00
Received By rmcphers Date 2022-01-24 Time 10:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-07 Cont ID  
Sent By medwards Date 2022-02-07 Time 09:51 Rev Time 0.00
Received By medwards Date 2022-02-07 Time 09:50 Sent To  
Notes
2022-02-07 09:51:221ST REVIEW FBC-2020 MECHANICAL
 PERMIT-22010462
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FROM THE DRAWINGS SUBMITTED IT APPEARS THAT THE 2
 MASSAGE SPA AREAS ARE NOT ACCESSIBLE FROM THE MIZNER
 HAIR AND NAILS TENANT SPACE. THEY APPEAR TO BE SEPARATE
 TENANT SPACES AND WOULD NEED THEIR OWN MECHANICAL
 SYSTEMS. PLEASE SHOW HOW THESE 2 TENANT SPACES WILL
 HAVE ACCESS TO THE MECHANICAL SYSTEMS AND CONTROLS. FBC
 M 405.1
  
 2) THE BEAUTY SALON WILL REQUIRE 1969 CFM OF OUTDOOR
 AIR AND 1905 CFM?S OF EXHAUST AIR. PLEASE SHOW HOW THE
 EXHAUST AIR WILL BE REMOVED AS I DO NOT SEE ANYTHING ON
 THE EXHAUST FANS FOR THIS AMOUNT OF EXHAUST. FBC M
 TABLE 403.3.1.1
  
 3) PLEASE ADD DETAIL DRAWINGS OF THE PEDICURE AND
 MANICURE EXHAUST ALONG WITH THE TOTAL AMOUNT OF EXHAUST
 REQUIRED FOR EACH AND A DRAWING DETAIL OF THE EXHAUST
 SYSTEM FOR THESE. FBC M 502.20
  
 4) PLEASE REMOVE THE REFLECTIVE CEILING LAYER ON THE
 MECHANICAL DRAWINGS SO THE REVIEW IS MORE CLEAR TO THE
 REVIEWER. FBC 107.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-02 Cont ID  
Sent By lcrespo Date 2022-02-02 Time 10:18 Rev Time 0.00
Received By lcrespo Date 2022-02-01 Time 10:41 Sent To  
Notes
2022-02-02 10:19:1602/02/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW,
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON RE-REVIEWING SUBMITTED CORRECTIONS.
  
 1. ON SHEET A03;
  
 A. THE BREAK ROOM SINK, WOULD YOU PLEASE SHOW THE CLEAR
 FLOOR SPACE AND DIMENSIONS PER THE 2020 FBC ACC SEC.
 606.2. 2 CLEAR FLOOR SPACE.
  
 B. IN THE SPA ROOM, THERE IS A SINK. WOULD YOU PLEASE
 SHOW THE CLEAR FLOOR SPACE AND DIMENSIONS PER THE 2020
 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 C. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. PLEASE MAKE A NOTE ON THIS SHEET.
  
 D. WOULD YOU PLEASE SHOW 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD APPROACH TO THE WHEELCHAIR-ACCESSIBLE
 DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2 CLEAR FLOOR
 SPACE.
  
 E. ICEMAKER AND COFFEE MAKER SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2020 FBC SEC. 608.13.10.
  
 F. FOR THE HAIR AND SPA ROOMS, WOULD YOU PLEASE SHOW
 WHICH ONE WILL COMPLY WITH THE 2020 FBC ACC PER THE
 SEC. 212.3 SINKS.
  
 2. ON SHEET A04;
  
 A. TOP RIGHT HAND, THERE IS A DRAWING SHOWING THE
 MIRROR AT 44 INCHES, AND IT SHOULD BE AT 40 INCHES PER
 THE 2020 FBC ACC SEC. 603.3.
  
 B. THE SECOND DRAWING DOWN FROM THE TOP RIGHT SHOWS
 GRAB BARS AND MIRRORS ON THE WRONG DIMENSION, WHICH
 LOOKS LIKE A DUPLICATE. THE SECOND DRAWING ON THE
 BOTTOM LEFT IS CORRECT. WOULD YOU REMOVE OR CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS. THE TOILET GRAB BAR SAYS 6
 INCHES FROM THE WALL, WHICH IS NOT AN ACTUAL NUMBER AS
 THE TOILET IS 16 INCHES TO 18 INCHES TO THE CENTER,
 WHICH MAY CONFUSE THE INSTALLER. WOULD YOU PLEASE
 CORRECT PER THE 2020 FBC ACC SEC. 604.2 LOCATION AND
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 C. THE DRAWING THAT SAYS BATHROOM CLEARANCES HAS THE
 LEFT ONE DETAIL INCORRECT FOR THE TOILET PAPER, LAV
 DISTANCE THAT DOES NOT COMPLY WITH THE 2020 FBC ACC.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 D. WOULD YOU PLEASE SHOW 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD APPROACH TO THE WHEELCHAIR-ACCESSIBLE
 DRINKING FOUNTAIN 2020 FBC ACC SEC. 602.2 CLEAR FLOOR
 SPACE.
  
 E. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 3. ON SHEET A05, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE FOR LAV, DRINKING FOUNTAIN, AND SINKS FOR
 PREVIOUS COMMENTS PER THE SEATS OF WATER CLOSETS SHALL
 BE OPEN-FRONT TYPE PER 2020 FBC P 425.3 WATER CLOSET
 SEATS.
  
 4. ON SHEET P-1;
  
 A. THERE IS A GAS WATER HEATER, AND IT DOES NOT SHOW A
 DRAIN PAN, BUT A DRAIN PAN ON P04 DRAINING TO THE MOP
 SINK IS THE DRAIN BY GRAVITY TO THE MOP SINK. WOULD YOU
 PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 B. WOULD YOU PLEASE SHOW THE MAIN SHUT-OFF ON THIS AND
 P03 PER THE 2020 FBC SEC. P 606.1 (2) LOCATION OF
 FULL-OPEN VALVES.
  
 C. NEXT TO THE WATER HEATER, IT SHOWS A HOSE BIBB.
 WOULD YOU PLEASE LABEL IT, SHOW IT IN P03, AND SHOW A
 SHUT-OFF PER THE 2020 FBC SEC P 606.2 LOCATION OF
 SHUTOFF VALVES.
  
 D. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNIT AND WITHIN REACH PER
 THE 2020 FBC SEC. P 606.3 ACCESS TO VALVES.
  
 5. ON SHEET P-2;
  
 A. IT CALLS OUT A WASHING MACHINE THAT WILL REQUIRE A
 LINT TRAP. WOULD YOU PLEASE SUPPLY DETAILS OR NOTES PER
 THE 2020 FBC SEC. 1003.6.
  
 B. WOULD YOU PLEASE SHOW THE CLEANOUT PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. THE PC IS VENTED INCORRECTLY PER THE 2020 FBC SEC. P
 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
  
 D. THE SPA LAV 101, 102, 109, 110 111, 112, 114, 115,
 117, 118, 126, 127, 128, 129, 130 AND 131 ARE NOT
 PEOPERLY VENTED PER THE 2020 FBC SEC. P 1002.1 FIXTURE
 TRAPS.
  
 6. ON SHEET P03, HOT WATER LINES LOOPED FOR THE
 RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP.
 THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE SEC.
 C404.6.1. THERE IS A TABLE THAT LIMITS THE BETWEEN THE
 SOURCE AND THE OUTLET; PLEASE REFER TO TABLE 404.5.1
 FOR THE MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY.
  
 7. ON SHEEP P04;
  
 A. ON THE GAS HEATER DETAIL, THE BOTTOM-FED WATER
 HEATERS AND BOTTOM-FED TANKS CONNECTED TO WATER HEATERS
 SHALL HAVE A VACUUM RELIEF VALVE INSTALLED PER THE 2020
 FBC SEC. P 504.2VACUUM RELIEF VALVE.
  
 B. THE UNIT LOOKS LIKE IT IS ELEVATED. WILL IT BE ON A
 STAND OR IN BRACKETS ON THE WALL? WOULD YOU PLEASE
 CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS? IF NOT ON STAN
 YOU, PLEASE PROVIDE A DETAIL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 C. WOULD YOU PLEASE SUBMIT LISTED FIRE-STOPPING DETAILS
 FOR THE PIPPING THROUGH RATED WALLS OR THE FLOORS.
 PLEASE SUBMIT THE COMPLETE ASSEMBLY DETAILS FOR THE
 SYSTEMS PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 D. UNDER GENERAL NOTES, IT SAYS #3 (D) INSULATION ON
 THE FIRST 8 FT, BUT THE RECIRCULATING SYSTEM THE PIPING
 SHALL BE INSULATED IN ITS ENTIRETY, INCLUDING THE
 SUPPLY AND RETURN PIPING OF A CIRCULATING PER C404.4
 (A) INSULATION OF PIPING.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT.
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE CORRECTION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY
 PAGES. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 08:27 Rev Time 0.00
Received By rmcphers Date 2022-02-16 Time 08:27 Sent To  
Notes
***NONE***