| 2022-01-25 15:43:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 22010437 205 DATURA ST # 405 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. PER WPB FBC 107.2.1, CLARIFY MATERIAL |
| | SPECIFICATIONS. P0.1/NOTE 14 CALLS FOR TYPE L COPPER OR |
| | SDR 11 CPVC PIPING FOR WATER DISTRIBUTION. IF CPVC IS |
| | TO BE USED, PROVIDE SPECIFICATION FOR HANGERS AND OTHER |
| | COMPONENTS THAT ARE APPROVED BY THE MANUFACTURER FOR |
| | PHYSICAL CONTACT WITH THE SYSTEM. P0.1/NOTE 15 DOES NOT |
| | CLEARLY CALL FOR PVC BUT ALLUDES TO THE USE. PER WPB |
| | FBC 107.2.1, CLARIFY. |
| | |
| | 2. P1.1/GENERAL NOTE 1; CONTRACTOR TO VERIFY IF TENANT |
| | CEILING SPACE BELOW IS A PLENUM AND PROVIDE CAST IRON |
| | INSTEAD OF PVC. PLEASE NOTE THAT THERE IS NO FIRE RATED |
| | FLOOR PENETRATION FOR METALLIC PIPE SHOWN ON P4.3. PER |
| | WPB FBC 107.2.1, PLEASE PROVIDE. |
| | |
| | 3. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE |
| | LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1. |
| | PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE |
| | SAME. |
| | |
| | 4. P0.1/PLUMBING SCOPE NOTE 3 STATES ROUTE CONDENSATE |
| | DRAIN TO MECHANICAL ROOM DRAIN. P0.1/PLUMBING SCOPE |
| | NOTE 3 STATES CONDENSATE DRAIN TO ROUTE TO EXISTING |
| | CONDENSATE DRAIN IN MECHANICAL ROOM P1.1/KEYNOTE 3. PER |
| | WPB FBC 107.2.1, PLEASE MAKE P0.1/PLUMBING SCOPE NOTE 3 |
| | AS CLEAR AS P0.1/PLUMBING SCOPE NOTE 3. |
| | |
| | 5. P2.1/NOTE 4: PER FBC PL 606.1 (2), WATER SERVICE |
| | (FULL OPEN) VALVE SHALL BE INSTALLED AT THE ENTRANCE TO |
| | STRUCTURE. PROVIDE IN COMMON AREA WITH ACCESS PANEL |
| | RATED SAME AS THE CEILING. |
| | |
| | 6. P4.1/WATER HEATER SCHEDULE: PROVIDE NOTE STATING |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL SHALL |
| | BE ON SITE PRIOR TO INSPECTION |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |