| 2022-02-10 17:26:53 | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22010382 |
| | 2/10/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A-7: THE RELOCATION OF THE GAS-FIRED TANKLESS WATER |
| | HEATER INTO THE BATHROOM IS PROHIBITED UNLESS THE UNIT |
| | IS A DIRECT-VENT APPLIANCE- SEC. G2406.2 FBC RES. |
| | PLEASE PROVIDE MORE INFORMATION INCLUDING THE MAKE AND |
| | MODEL OF THE WATER HEATER. |
| | |
| | 2) A-7: PROVIDE A GAS PIPING PLAN AND RISER DRAWING- |
| | SEC. 107.3.5.3 WPB. THE RISER SHALL INCLUDE THE |
| | FOLLOWING DETAILS AND INFORMATION: |
| | A) TYPE OF GAS- NATURAL OR LP. |
| | B) DELIVERY PRESSURE AT THE METER. |
| | C) BTU LOAD OF THE WATER HEATER. |
| | D) TYPES AND SIZE OF GAS PIPING. |
| | E) LOCATIONS OF REGULATOR, SHUTOFF VALVE, AND PIPE |
| | UNIONS. |
| | F) OUTLET PRESSURE AT REGULATOR. |
| | G) PIPE SIZING TABLE. |
| | |
| | 3) A-7: COMBUSTION AIR AND VENTING PLANS ARE REQUIRED. |
| | FOR A DIRECT VENT UNIT SHOW THE TYPE AND SIZE OF INTAKE |
| | AND EXHAUST DUCTS, THE DUCT RUNS, AND TERMINATION |
| | LOCATIONS. ADDITIONAL COMMENTS MAY OCCUR DEPENDING ON |
| | THE TYPE OF UNIT BEING RELOCATED- SECS. G2407.1 & |
| | G2427.1 FBC RES. |
| | |
| | 3) SUBMIT A GAS SUB-PERMIT APPLICATION- SECTION 105.1 |
| | WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |