Plan Review Details - Permit 22010362
Plan Review Stops For Permit 22010362
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2023-02-27 Cont ID  
Sent By rmcdouga Date 2023-02-27 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2023-02-27 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-01-31 Cont ID  
Sent By rmcdouga Date 2022-01-31 Time 17:04 Rev Time 0.00
Received By rmcdouga Date 2022-01-31 Time 17:04 Sent To  
Notes
2022-01-31 17:14:06BUILDING PROVISO
  
 1) IN ORDER TO DETERMINE IF THE ROOF STANDS ARE CAPABLE
 OF WITHSTANDING THE REQUIRED WIND LOADS, THE SIZES OF
 THE UNITS, THE CLEAR HEIGHT OF THE STANDS AND THE ROOF
 ZONE IN WHICH THEY ARE LOCATED WILL HAVE TO BE
 SPECIFIED. SUBMIT THIS INFORMATION ALONG WITH THE
 APPROPRIATE ITEMS CIRCLED OR HI-LITED ON THE TABLES IN
 THE PRODUCT APPROVALS AND THE GENERIC ENGINEERING.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-02-27 Cont ID  
Sent By rmcdouga Date 2023-02-27 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2023-02-02 Time 13:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-01 Cont ID  
Sent By medwards Date 2022-02-01 Time 13:16 Rev Time 0.00
Received By medwards Date 2022-01-12 Time 05:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-02-01 Cont ID  
Sent By medwards Date 2022-02-01 Time 13:15 Rev Time 0.00
Received By medwards Date 2022-02-01 Time 13:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-02-27 Cont ID  
Sent By rmcdouga Date 2023-02-27 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2023-02-27 Time 14:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By rmcdouga Date 2022-01-31 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2022-01-31 Time 16:41 Sent To  
Notes
2022-01-31 16:50:39THE DOCUMENTS FOR THE ADJUSTABLE HEIGHT PIPE STANDS AND
 THE FIXED HEIGHT PIPE STANDS ARE NOT A PRODUCT APPROVAL
 AND DO NOT HAVE THE ENGINEER'S DIGITAL SIGNATURE AND
 SEAL. ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO
 HAVE THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON
 THEM. YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & 61G1 OR FS 471 &
 61G15