| 2022-02-10 08:54:19 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL5259-R33 |
| | HAS BEEN REVISED TO FL5259-R34. PLEASE PROVIDE A |
| | COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF |
| | COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| | COMBINATIONS & ALLOWABLE SUBSTRATES. SELECT OPTIONS TO |
| | BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 2. SUBMITTED PRODUCT APPROVAL FL1654-R27 HAS BEEN |
| | REVISED TO FL1654-R28. PROVIDE THE FOLLOWING: COVER |
| | PAGE, EVALUATION REPORTS PAGES 1-5 TO INCLUDE |
| | LIMITATIONS PAGE(S) AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. SELECTED SYSTEM W-209 DO NOT MEET OR |
| | EXCEEDS EXPOSURE CATEGORY C MINIMUM DESIGN PRESSURE |
| | ZONE 3 REQUIREMENTS OF -108.17. PLEASE SELECT SYSTEM |
| | NO. THAT MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE |
| | SIGNED AND SEALED ENGINEERED NAILING CALCULATION FOR |
| | ZONE 3. |
| | 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL11602-R11 |
| | HAS BEEN REVISED TO FL11602-R13. PLEASE PROVIDE A |
| | COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF |
| | COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE |
| | COMBINATIONS & ALLOWABLE SUBSTRATES. SELECT OPTIONS TO |
| | BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| | CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| | DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| | PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| | 4. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL4595.19-R6 COVERS MULTIPLE FASTENER SPACING |
| | TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT CORRECT |
| | FASTENER PATTERN & SPACING FROM TABLE ?A? PAGE #2 OF |
| | THE EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM |
| | DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE |
| | CATEGORY C AREAS. (-108.17). ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |