Plan Review Details - Permit 22010317
Plan Review Stops For Permit 22010317
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-22 Cont ID  
Sent By rmcphers Date 2022-03-22 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2022-03-22 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-15 Cont ID  
Sent By rmcphers Date 2022-02-15 Time 15:19 Rev Time 0.00
Received By rmcphers Date 2022-02-15 Time 15:18 Sent To  
Notes
2022-02-15 15:19:52RAILING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) DRAWINGS AND CALCULATIONS SHOW THE DESIGN WIND SPEED
 AT 160MPH FOR RISK CATEGORY II - RISK GATEGORY II
 MINIMUM WIND DESIGN SPEED NEEDS TO BE 170 MPH PER FBC
 WPB SECTION 120.
  
 2) DRAWING 1 OF 3 NOTE NUMBER 4 IS FOR FABRIC - PLEASE
 CLARIFY.
  
 3) PLEASE SHOW STAIR HANDRAIL EXTENSIONS AT TOP AND
 BOTTOM OF THE STAIRS PER FBC 1014.6 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS
 WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS
 AND THE RAMP RUNS AT RAMPS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 12:34 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 11:53 Sent To  
Notes
2022-02-04 12:34:14RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) DRAWINGS AND CALCULATIONS SHOW THE DESIGN WIND SPEED
 AT 160MPH FOR RISK CATEGORY II - RISK GATEGORY II
 MINIMUM WIND DESIGN SPEED NEEDS TO BE 170 MPH PER FBC
 WPB SECTION 120.
  
 2) DRAWING 1 OF 3 NOTE NUMBER 4 IS FOR FABRIC - PLEASE
 CLARIFY.
  
 3) PLEASE SHOW STAIR HANDRAIL EXTENSIONS AT TOP AND
 BOTTOM OF THE STAIRS PER FBC 1014.6 HANDRAIL
 EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS
 ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM)
 BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE
 DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS
 WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS
 AND THE RAMP RUNS AT RAMPS.
  
 4) PLEASE PROVIDE A DRAWING TO SHOW THE LOCATION OF THE
 RAILING TO BE REPLACED. FLOOR PLAN OR ELEVATION PLAN.
  
 5) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 FENCE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-03-18 Cont ID  
Sent By pleduc Date 2022-03-18 Time   Rev Time 0.00
Received By pleduc Date 2022-03-18 Time 11:37 Sent To  
Notes
2022-03-18 11:44:56FIRE PROVISO:
  
 GATES SHALL HAVE FREE EGRESS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-08 Cont ID  
Sent By pleduc Date 2022-02-08 Time   Rev Time 0.00
Received By pleduc Date 2022-02-08 Time 10:53 Sent To  
Notes
2022-02-08 10:59:09FIRE PROVISO:
  
 GATES SHALL HAVE FREE EGRESS AS
 REQUIRED PER NFPA 101
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-01-11 Cont ID  
Sent By pleduc Date 2022-01-11 Time   Rev Time 0.00
Received By pleduc Date 2022-01-11 Time 14:13 Sent To  
Notes
2022-01-11 14:17:38THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A FRONT AND REAR FENCE
 WITH A SWING GATE.
  
 HOWEVER, THERE IS NO SITE PLAN INDICATING THE LOCATION
 OF THE FENCE.
  
 PLEASE REVIEW AND PROVIDE A SITE PLAN SHOWING THE
 LOCATION OF THE FENCE AND GATES.
  
 1A) THERE IS A INDICATION OF GATES WITHIN THE FENCE,
 HOWEVER, THERE IS NO INDICATION OF THE HARDWARE TO
 OPEN/CLOSE/SECURE THE GATE.
  
 ADDITIONALLY, THERE IS NO INDICATION OF IF THESE GATES
 ARE IN THE PATH OF EXIT TRAVEL TO A PUBLIC WAY AND
 WOULD REQUIRE CODE COMPLIANT EXIT HARDWARE.
  
 PLEASE REVIEW AND PROVIDE A LIFE SAFETY REVIEW WITH
 APPLICABLE DETAILS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-25 Cont ID  
Sent By asangele Date 2022-03-25 Time 10:19 Rev Time 0.00
Received By asangele Date 2022-03-25 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-15 Cont ID  
Sent By rmcphers Date 2022-02-15 Time 15:20 Rev Time 0.00
Received By rmcphers Date 2022-02-07 Time 13:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 12:35 Rev Time 0.00
Received By rmcphers Date 2022-01-11 Time 05:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-17 Cont ID  
Sent By mpeterso Date 2022-03-17 Time 14:29 Rev Time 0.00
Received By mpeterso Date 2022-03-17 Time 14:28 Sent To  
Notes
2022-03-17 14:29:583/17/22 REVIEW OF SIGNATURE ON PAPER PLANS PASSED AND
 ROUTED TO STORAGE.M.P.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-07 Cont ID  
Sent By medwards Date 2022-02-07 Time 14:35 Rev Time 0.00
Received By medwards Date 2022-02-07 Time 14:35 Sent To  
Notes
2022-02-07 14:36:20SITE PLAN HAS THE ORIGINAL SEAL AND SIGNATURE. ROUTED
 TO STORAGE. ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-11 Cont ID  
Sent By rmcdouga Date 2022-01-11 Time 11:01 Rev Time 0.00
Received By rmcdouga Date 2022-01-11 Time 11:01 Sent To  
Notes
2022-01-11 11:06:48THE (3) PLAN SHEETS, (7) PAGES OF FENCE AND GATE
 CALCULATIONS AND (13) PAGES OF RAILING CALCULATIONS
 HAVE THE ENGINEER'S ORIGINAL SIGNATURE AND SEAL ON THE.
 ALL HAVE BEEN SENT TO STORAGE.

Review Stop Z ZONING
Rev No 3 Status P Date 2022-03-25 Cont ID  
Sent By asangele Date 2022-03-25 Time 10:19 Rev Time 0.00
Received By asangele Date 2022-03-25 Time 10:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-11 Cont ID  
Sent By asangele Date 2022-02-11 Time   Rev Time 0.00
Received By asangele Date 2022-02-11 Time 09:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-24 Cont ID  
Sent By asanglee Date 2022-01-24 Time 08:47 Rev Time 0.00
Received By asangele Date 2022-01-24 Time 08:45 Sent To  
Notes
2022-01-24 08:47:24FAILED: PLEASE PROVIDE A SURVEY ON WHERE YOU ARE
 PLANNING ON LOCATING OF THE FENCE.
  
 ALEXIS SANGELEER
 ASSOCIATE PLANNER
 [email protected]