| Plan Review Stops For Permit 22010155 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-01-10 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-01-10 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-01-10 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2022-01-10 14:32:28 | SOUTH BUILDING ADDRESS OF 315 VALENCIA RD IS | | | APPROPRIATE FOR THE FRONT BUILDING, REAR BUILDING | | | HABITABLE SPACE NEEDS ITS OWN SEPARATE UNIQUE ADDRESS | | | AND TO BE REVIEWED UNDER 22010160 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-06-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-06-18 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-06-18 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-25 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-22 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2022-04-25 09:25:37 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. THE ADDRESS ON THE SOILS REPORT IS 313 VALENCIA RD. | | | THE CORRECT ADDRESS IS 315 VALENCIA RD. PLEASE CORRECT | | | AND RE-SUBMIT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2.PROVIDE AN ENERGY SUBMITTAL | | | | | | FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 | | | STORIES. | | | FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE | | | ALTERNATIVE. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | 3. DESIGNER SHALL STATE R VALUE OF EXTERIOR WALLS ON | | | PLANS. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 4. IDENTIFY WINDOW AND DOOR TYPE ON PLANS. COORDINATE | | | WITH WINDOW AND DOOR SCHEDULE. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 5. PROVIDE A ROOF FRAMING PLAN. PROVIDE DESIGN | | | PRESSURES FOR NEW ROOFING PER FIGURE R301.2(7) | | | COMPONENT AND CLADDING PRESSURE ZONES | | | R301.2.1.1WIND DESIGN REQUIRED. | | | | | | 6.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER | | | CALCULATED DESIGN PRESSURES. | | | TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING | | | SCHEDULE FOR WOOD STRUCTURAL PANELS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-06-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-06-18 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-06-18 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-04-25 |
Time |
20:57 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-04-25 |
Time |
19:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2022-04-15 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-04-15 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-04-15 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2022-04-15 13:06:21 | PLANS ON PERMIT 22010160 |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-02-03 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-02-03 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-02-03 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-06-21 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-06-21 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-05-09 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-04-27 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-04-27 |
Time |
14:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-01-25 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-01-10 |
Time |
06:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-07-12 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-06-21 |
Time |
09:01 |
Sent To |
|
|
| Notes |
| 2022-06-21 09:19:26 | 7/11/22 RECEIPT MU-2022-028934-0000 $12,460.17 PAID AO | | | 6/21/22 EMAILED IMPACT FOR REVIEW-AO |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-01-14 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2022-01-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-15 07:11:52 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT | | | TO [email protected]. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-05-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-13 |
Time |
10:44 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-13 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2022-05-13 10:44:34 | MAIN HOUSE APPROVED ME |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-25 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-25 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2022-04-25 09:50:08 | 1ST REVIEW FMC | | | PERMIT: 22010155 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE ENERGY CALCULATIONS, INCLUDING | | | THE GARAGE AND MAKE SURE THE GARAGE DOOR IS INCLUDED IN | | | THE CALCULATIONS. FEC R402.1 | | | | | | | | | 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
N |
Date |
2022-04-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-23 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-22 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2022-04-23 11:43:03 | PROPERTY IS NOT LOCATED IN A SPECIAL FLOOD HAZARD AREA. | | | NO BASE FLOOD ELEVATION ESTABLISHED. NO ELEVATION | | | CERTIFICATE REQUIRED. CT |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-04-15 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-04-15 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-04-15 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2022-04-15 13:06:01 | PLANS ON PERMIT 22010160 |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2022-07-07 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-07-07 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-07-07 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2022-07-07 13:57:53 | PRIVATE PROVIDER RE-INSTATED FOR INSPECTIONS. |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2022-04-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-04-12 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-04-12 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2022-04-12 16:28:06 | OWNER RESCINDED PRIVATE PROVIDER | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2022-01-05 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2022-01-05 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2022-01-05 14:56:49 | OK-CREDENTIALS | | | REVIEW OF PPLAN REVIEW AFFIDAVITS TO OCCUR AFTER OTHER | | | AGENCY APPROVALS. | | | | | | DYLAN BATTLES | | | 561-805-6718 | | | [email protected] | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-25 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-14 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2022-04-25 09:17:15 | PROVISO ON PLAN PAGE A212: A SEPERATE ROOFING PERMIT IS | | | REQUIRED. CT |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-06-18 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-06-18 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-06-18 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-04-25 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-04-14 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2022-04-25 14:11:14 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 CFM | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | RE: ALL STRUCTURAL PLANS: | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-04-27 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-04-27 |
Time |
14:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-21 |
|
|
Cont ID |
|
| Sent By |
asanglee |
Date |
2022-01-21 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-01-21 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2022-02-03 16:13:26 | SITE PLAN SHOWS SETBACKS. | | | | | | NEED SEPERATE LANDSCAPE PLAN PERMIT SUBMITTAL. | | 2022-01-21 15:47:01 | FAILED: SURVEY LACKS SETBACKS OF THE PROPERTY LINES. | | | | | | ALEXIS SANGELEER | | | ASSOCIATE PLANNER | | | [email protected] |
|
|