| 2022-01-24 10:12:25 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1 FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| | APPROVAL FL16709-R9 SELECTED OPTION FOR SYSTEM NO W-5; |
| | EXPOSURE (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); |
| | ULTIMATE WIND SPEED (170), IS NOT CORRECT. THE CORRECT |
| | EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE D; VERIFY |
| | AND CORRECT ROOF HEIGHT; ROOF SKETCH INDICATES |
| | TWO-STORY BUILDING.. PLEASE SELECT THE CORRECT OPTIONS. |
| | 2. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT |
| | COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL |
| | AND CHAPTER 11 OF THE 2020 FBC-PLUMBING. |
| | 3. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR |
| | THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL |
| | HEIGHT(S). |
| | 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF |
| | HEIGHT(S). LOW SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |