| 2022-02-09 10:30:43 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 21121205 |
| | ADD: 651 OKEECHOBEE BLVD # 601 |
| | CONT: GULINO CONSTRUCTION LLC |
| | TEL: 561-815-4160 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 09TH/2022 |
| | ACTION: DENIED |
| | |
| | 1) CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. |
| | 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE |
| | EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H) |
| | ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C) |
| | REQUIRES THE CONTRACTOR FOR THAT TRADE THAT WILL BE |
| | LICENSED IN THAT TRADE, WILL ALSO BE THE CONTRACTOR |
| | THAT DESIGNS THE SYSTEM UNDER THAT TRADE. THE |
| | CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET OF |
| | PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF |
| | THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND |
| | LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN AND |
| | PLANS DRAWN. |
| | |
| | 2) DEMO OF RESTROOM DOES THIS INCLUDE THE TILE FLOOR? |
| | IF SO PLEASE SHOW COMPLIANCE WITH FLOOR INSULATION/ |
| | UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE, |
| | VINYL (LYT/ LYP), LAMINATE FLOORING AND WOOD FLOORING |
| | ALL NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED |
| | FLOOR ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET |
| | THE QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS |
| | FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED |
| | CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3A) REMOVAL OF TUB REPLACE WITH SHOWER. 2020 FBC-B |
| | SHOWERS & TUBS 1210.3. SHOWER COMPARTMENTS AND BATHTUBS |
| | WITH INSTALLED SHOWER HEADS SHALL BE FINISHED WITH A |
| | NONABSORBENT SURFACE TO A HEIGHT NOT LESS THAN 72 |
| | INCHES ABOVE THE DRAIN INLET. |
| | |
| | 3B) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS |
| | IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO |
| | BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR |
| | SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION |
| | CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3C) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| | FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| | WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| | THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| | A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| | ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| | HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| | NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| | PENETRATED. |
| | |
| | 3D) TUB ENCLOSURE WALLS AND OR SHOWER WALLS. TUB |
| | ENCLOSURE WALLS AND OR SHOWER WALLS WHICH ARE ALSO |
| | TENANT SEPARATION WALL WHICH WILL ALSO NEED TO SHOW |
| | COMPLIANCE WITH SECTION 420.2 SEPARATION WALLS AND FIRE |
| | PARTITIONS IN ACCORDANCE WITH SECTION 708 OF THE 2020 |
| | FBC-BUILDING CODE. |
| | |
| | 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING |
| | FROM CITY HALL. |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |