Plan Review Details - Permit 21121135
| Plan Review Stops For Permit 21121135 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-01-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-01-06 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-01-06 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2022-01-06 07:29:43 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-01-04 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-01-04 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2022-01-04 07:23:02 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | SITE PLAN | | | A. SHOW TO SCALE THE SIZE AND LOCATION OF NEW | | | CONSTRUCTION AND EXISTING | | | STRUCTURES ON THE SITE? | | | B. SHOW DISTANCE TO LOT LINES AND OTHER STRUCTURES PER | | | FBC CHPT. 6, SEC. 602 | | | C. PROVIDE SQUARE FOOTAGE | | | D. PROVIDE ESTIMATED OCCUPANCY CONTENT OF EACH TENT | | | E. PROVIDE ACCESSIBLE ROUTE FROM PARKING TO TENT | | | ENTRANCE | | | F. IDENTIFY MEANS OF EGRESS PER CHPT. 10 | | | G. PROVIDE ACCESSIBLE ROUTE FROM TENT TO ACCESSIBLE | | | RESTROOMS | | | H. ACCESSIBLE RESTROOMS SHALL BE LOCATED WITHIN 500 | | | FEET OF TENT |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-01-18 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-01-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2022-01-18 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2022-01-18 13:56:01 | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. | | | | | | TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-03 |
|
|
Cont ID |
|
| Sent By |
amcgrego |
Date |
2022-01-03 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
amcgrego |
Date |
2022-01-03 |
Time |
17:33 |
Sent To |
|
|
| Notes |
|
|
|