Plan Review Details - Permit 21121105
Plan Review Stops For Permit 21121105
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-03-15 Cont ID  
Sent By jwitmer Date 2022-03-15 Time 10:43 Rev Time 0.00
Received By jwitmer Date 2022-03-15 Time 10:43 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-02-08 Cont ID  
Sent By jwitmer Date 2022-02-08 Time 13:32 Rev Time 0.00
Received By jwitmer Date 2022-02-08 Time 13:27 Sent To  
Notes
2022-02-08 13:32:35COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-27 Cont ID  
Sent By jwitmer Date 2022-04-27 Time 10:31 Rev Time 0.00
Received By jwitmer Date 2022-04-27 Time 09:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-04-06 Cont ID  
Sent By jwitmer Date 2022-04-06 Time 11:22 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-04-06 11:22:34WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21121105
 ADD: 1501 PRESIDENTIAL WAY # 19
 CONT: PETRA BUILDERS GROUP
 TEL: 561-654-9987
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. APRIL 06TH/2022
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) SHEET A.5 CABINETRY ELEVATIONS:
  
 3A) 3RD REVIEW. THE DESIGNER OF RECORD DISPUTES WORK
 AREAS NEEDING TO COMPLY WITH COUNTER HEIGHTS, CLAIMING
 SECTION 203.9 IN THE 2020 FBC-ACCESSIBILITY CODE.
 WITHIN THIS SECTION 206.2.8 IS AN ACCESSIBLE ROUTE,
 207.1 ACCESSIBLE MEANS OF EGRESS AND 215.3 FIRE ALARMS
 WORK AREAS ARE TO HAVE AUDIBLE ALARMS.
 WHEN REVIEWING WHAT CAN BE CONSIDERED EXAMPLES OF WORK
 SURFACES ADVISORY 902.1 BUT NOT LIMITED TO WRITING
 SURFACES, STUDENT LABORATORY STATIONS THESE ARE
 EXAMPLES OF WHAT NEEDS TO COMPLY WITH 902.3 COUNTER
 HEIGHTS WHAT IS THE DIFFERENCE IF IT IS A STUDENT WORK
 STATION IN A LAB OR LAB IN A WORK ENVIRONMENT.
 2ND REQUEST. DETAILS 3 WORK AREA, 4 WORK AREA WITH SINK
 , WORK AREA 6, LAB WORK AREA 10, WORK AREA WITH SINK 11
 ALL SHOW THE CABINETRY COUNTER TOPS AT 36 INCHES IN
 HEIGHT. ACCESS. CODE SECTION 902.3 HEIGHT. THE TOPS OF
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3B)3RD REQUEST. THE DESIGN PROFESSIONAL HAS STATED IF
 THE NEED ARISES A 2ND MICROWAVE WILL BE PUT ON THE
 COUNTER. THAT DOE NOT MEET CODE COMPLIANCE FOR PLAN
 REVIEW AND INSPECTIONS. WE HAVE SEEN IN THE PAST
 DESIGNERS EITHER PUTTING A 2ND MICROWAVE ON THE COUNTER
 OR PLACING THE MICROWAVE IN THE BASE CABINET.
 DETAIL 11 ALSO SHOWS A MICROWAVE THE BOTTOM OF THE
 SHELF AT 4 FEET 10 INCHES ABOVE THE FLOOR. PLEASE SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
  
 3B)(1). 2ND REQUEST. 308 REACH RANGES. 308.2 FORWARD
 REACH / 308.2.1 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH
 REACH. 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/
 308.3.2 OBSTRUCTED HIGH REACH.
  
 3B)(2) 2ND REQUEST. 309 OPERABLE PARTS. 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308. 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-15 Cont ID  
Sent By jwitmer Date 2022-03-15 Time 11:03 Rev Time 0.00
Received By jwitmer Date 2022-03-15 Time 10:43 Sent To  
Notes
2022-03-15 11:03:15WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21121105
 ADD: 1501 PRESIDENTIAL WAY # 19
 CONT: PETRA BUILDERS GROUP
 TEL: 561-654-9987
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 15TH/2022
 ACTION: DENIED
  
 1)2ND REQUEST. RESPONSE INDICATES SEE SHEET A.3 FOR
 RESTROOMS AND A.1 FOR THE MOP SINK WITH FRP AROUND MOP
 SINK. BOTH SHEETS A.1 AND A.3 SHOW THE UPLOAD DATE OF
 1/5/2022 NO UPDATE NOR REVISION MARKER ON EITHER SHEET.
 SHEET A.3 SHOWS BOTH RESTROOMS 104 & 108 WITH ALL WALLS
 TO BE PAINTED AND WOOD BASE.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 1A) 2ND REQUEST. 1210.2.2 WALLS & PARTITIONS WITHIN 2
 FEET OF SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT
 OF NOT LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIAL USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 1B) 2ND REQUEST. 2509.1. WET AREAS. SHOWERS AND PUBLIC
 TOILET WALLS SHALL COMPLY WITH 1210.2.
  
 1C) 2ND REQUEST. 1210.2. FINISH MATERIALS. WALLS, BASE,
 FLOORS AND PARTITIONS IN TOILET AND BATHROOMS SHALL
 COMPLY WITH SECTIONS 1210.1 THROUGH 1210.4.
  
 2) 2ND REQUEST. SHEET A.3 SHOW THE UPLOAD DATE OF
 1/5/2022 NO UPDATE NOR REVISION MARKER ON SHEET A.3.
 SHEET A-3 SCHEDULES THE TELEPHONE OUTLET AND INTERCOM/
 PHONE ARE BOTH AT A HEIGHT OF 4 FEET 6 INCHES C/L ABOVE
 THE FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY WITH THE
 REACH RANGES UNOBSTRUCTED FOR EITHER A FRONT APPROACH
 OR SIDE APPROACH. 2020 FBC-ACCESSIBILITY CODE:
 2A) 2ND REQUEST. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 2B) 2ND REQUEST. 309 OPERABLE PARTS. 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308. 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 3) SHEET A.5 CABINETRY ELEVATIONS:
 3A) 2ND REQUEST. DETAILS 3 WORK AREA, 4 WORK AREA WITH
 SINK , WORK AREA 6, LAB WORK AREA 10, WORK AREA WITH
 SINK 11 ALL SHOW THE CABINETRY COUNTER TOPS AT 36
 INCHES IN HEIGHT. ACCESS. CODE SECTION 902.3 HEIGHT.
 THE TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
 SINKS SHALL ALSO BE NO MORE THAN 34 INCHES ABOVE FINISH
 FLOOR. 2020 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3B)2ND REQUEST. DETAIL 11 ALSO SHOWS A MICROWAVE THE
 BOTTOM OF THE SHELF AT 4 FEET 10 INCHES ABOVE THE
 FLOOR. PLEASE SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTIONS:
 3B)(1). 2ND REQUEST. 308 REACH RANGES. 308.2 FORWARD
 REACH / 308.2.1 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH
 REACH. 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/
 308.3.2 OBSTRUCTED HIGH REACH.
  
 3B)(2) 2ND REQUEST. 309 OPERABLE PARTS. 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308. 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS MAXIMUM.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-08 Cont ID  
Sent By jwitmer Date 2022-02-08 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2022-02-08 Time 13:27 Sent To  
Notes
2022-02-08 14:10:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21121105
 ADD: 1501 PRESIDENTIAL WAY # 19
 CONT: PETRA BUILDERS GROUP
 TEL: 561-654-9987
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 08TH/2022
 ACTION: DENIED
  
 1) SHEET A.3 SHOWS BOTH RESTROOMS 104 & 108 WITH ALL
 WALLS TO BE PAINTED AND WOOD BASE.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 1A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 1B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 1C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 2) SHEET A-3 SCHEDULES THE TELEPHONE OUTLET AND
 INTERCOM/ PHONE ARE BOTH AT A HEIGHT OF 4 FEET 6 INCHES
 C/L ABOVE THE FINISH FLOOR. THIS HEIGHT DOES NOT COMPLY
 WITH THE REACH RANGES UNOBSTRUCTED FOR EITHER A FRONT
 APPROACH OR SIDE APPROACH. 2020 FBC-ACCESSIBILITY CODE:
 2A) 308.2 FORWARD REACH./ 308.2.1 UNOBSTRUCTED/ 308.2.2
 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 2B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 3) SHEET A.5 CABINETRY ELEVATIONS:
 3A) DETAILS 3, 4, 6, 10, 11 ALL SHOW THE CABINETRY
 COUNTER TOPS AT 36 INCHES IN HEIGHT. ACCESS. CODE
 SECTION 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL
 BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. SINKS SHALL ALSO BE NO MORE
 THAN 34 INCHES ABOVE FINISH FLOOR. 2020
 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3B) DETAIL 11 ALSO SHOWS A MICROWAVE THE BOTTOM OF THE
 SHELF AT 4 FEET 10 INCHES ABOVE THE FLOOR. PLEASE SHOW
 COMPLIANCE WITH THE 2020 FBC-ACCESSIBILITY CODE
 SECTIONS:
 3B)(1). 308 REACH RANGES. 308.2 FORWARD REACH / 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. 308.3 SIDE
 REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 OBSTRUCTED HIGH
 REACH.
  
 3B)(2) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-05-09 Cont ID  
Sent By fgiaquin Date 2022-05-09 Time 23:07 Rev Time 0.00
Received By fgiaquin Date 2022-05-09 Time 20:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-03-25 Cont ID  
Sent By fgiaquin Date 2022-03-25 Time 22:42 Rev Time 0.00
Received By fgiaquin Date 2022-03-25 Time 20:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-27 Cont ID  
Sent By fgiaquin Date 2022-01-27 Time 20:31 Rev Time 0.00
Received By fgiaquin Date 2022-01-27 Time 19:04 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-06-08 Cont ID  
Sent By mpeterso Date 2022-06-08 Time 10:51 Rev Time 0.00
Received By mpeterso Date 2022-06-08 Time 10:51 Sent To  
Notes
2022-06-08 10:52:16LOW VOLTAGE WIRING APPROVED FOR DATA AND TV PER PLAN

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-04-05 Cont ID  
Sent By cwalker Date 2022-04-05 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-10 Cont ID  
Sent By cwalker Date 2022-03-10 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-01-07 Cont ID  
Sent By cwalker Date 2022-01-07 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-01-07 10:41:17THE FLOOR PLAN DOOR 3 IS INDICATED AS AN EXIT. THE
 TREATMENT BAY CHAIR IN FRONT OF THIS DOOR APPEARS TO BE
 AN OBSTRUCTION TO EGRESS. NFPA 101 4.5.3.2
 FIRS SPRINKLER AND/OR FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMOLITION AND CONSTRUCTION. ANY
 WORK ON THE FIRE SPRINKLER AND/OR FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMITS AND SHOP DRAWINGS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-05-09 Cont ID  
Sent By fgiaquin Date 2022-05-09 Time 23:08 Rev Time 0.00
Received By fgiaquin Date 2022-04-20 Time 16:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-15 Cont ID  
Sent By medwards Date 2022-04-15 Time 07:43 Rev Time 0.00
Received By medwards Date 2022-04-04 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-25 Cont ID  
Sent By fgiaquin Date 2022-03-25 Time 22:42 Rev Time 0.00
Received By fgiaquin Date 2022-03-09 Time 08:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-08 Cont ID  
Sent By jwitmer Date 2022-02-08 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2022-01-06 Time 09:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-04-15 Cont ID  
Sent By medwards Date 2022-04-15 Time 07:40 Rev Time 0.00
Received By medwards Date 2022-04-15 Time 07:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-03-16 Cont ID  
Sent By medwards Date 2022-03-16 Time 11:20 Rev Time 0.00
Received By medwards Date 2022-03-16 Time 11:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-11 Cont ID  
Sent By medwards Date 2022-01-11 Time 15:56 Rev Time 0.00
Received By medwards Date 2022-01-11 Time 15:56 Sent To  
Notes
2022-01-11 15:57:101ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21121105
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) EF-1 BATH EXHAUST FANS MUST MEET MINIMUM VENTILATION
 CFM?S ACCORDING TO FBC M TABLE 403.3.1.1 FOOTNOTE F OF
 50 CFM CONTINUOUS OR 70 CFM?S INTERMITTENT
  
 2) PLEASE PROVIDE MORE INFORMATION AS TO WHAT IS BEING
 STORED IN THE MECHANICAL ROOM 115 AND STORAGE ROOM 116.
 EXPLAIN WHY THE EF-2 IS THERMOSTATICALLY CONTROLLED.
 FBC 107.2.1
  
 3) EXPLAIN WHY EF-1 IS TIED INTO THE SAME EXHAUST DUCT
 AS EF-2 FROM THE MECHANICAL ROOM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date 2022-03-10 Cont ID  
Sent By jesmith Date 2022-03-10 Time 16:20 Rev Time 0.00
Received By jesmith Date 2022-03-10 Time 14:31 Sent To  
Notes
2022-03-10 16:20:1621121105 1501 PRESIDENTIAL WAY # 19
  
 MEDICAL GAS COMMENTS: APPROVED
  
 THE NFPA 99-18 APPLIES
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 AS NOTED ON PLAN SHEET T-1 AND IN ACCORDANCE WITH WPB
 FBC 107.2.1 AND WPB FBC 107.3.4.1, MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE DENTAL
 EQUIPMENT AS INDICATED ON PLAN SHEET T.1 ARE TO BE
 PROVIDED AS DEFERRED SUBMITTALS. SUBMITTAL SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. PROCEED AT YOUR OWN RISK.
  
 PROVISO: CLEAN SAND OR GRAVEL FOR TRENCH BACKFILL OF
 UNDERGROUND VACUUM AND AIR PIPING SHALL BE PROVIDED IN
 ACCORDANCE WITH NFPA-18, SECTION 15.5.6.6.2.
  

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2022-01-18 Cont ID  
Sent By jesmith Date 2022-01-18 Time 15:37 Rev Time 0.00
Received By jesmith Date 2022-01-13 Time 15:46 Sent To  
Notes
2022-01-18 15:35:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121105 1501 PRESIDENTIAL WAY # 19
  
 1ST REVIEW
 MED GAS COMMENTS: DENIED
  
 1. P-4/COMPRESSOR DETAIL NOTE REFERENCING COPPER
 CATEGORY 3. PER WPB FBC 107.2.1, CLARIFY THE RISK
 CATEGORY AS DETERMINED BY NFPA 99-18; 15.1.1 THROUGH
 15.1.3 AND CONFIRM ON THE PLANS THE APPLICABLE "RISK
 CATEGORY". THE COMMENTS BELOW APPLY TO RISK CATEGORY 3.
 IF THE RISK CATEGORY IS OTHER THAN 3, ADDITIONAL
 COMMENTS WILL BE FORTHCOMING.
  
 2. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR DENTAL
 EQUIPMENT AND COMPONENTS.
  
 3. PER WPB FBC 107.2.1, PROVIDE NOTE STATING
 MANUFACTURER'S SPECIFICATION SHEETS/INSTALLATION FOR
 BACKFLOW PREVENTER(S) SHALL BE ON SITE PRIOR TO
 INSPECTION.
  
 4. PER WPB FBC 107.2.1, PROVIDE A TRENCH BACKFILL
 DETAIL FOR UNDERGOUND PIPING SHOWING CLEAN SAND OR
 GRAVEL AS REQUIRED BY NFPA 99-18, SECTION 15.5.6.6.2.
  
 5. P-4/VACUUM NOTE 4 STATES NO DRAINAGE FITTINGS;
 DETAIL 4 AND 5 INDICATE DRAINAGE FITTINGS. PER WPB FBC
 107.2.1, CLARIFY.
  
 6. PER WPB FBC 107.2.1, PROVIDE COMPLETE MATERIAL
 SPECIFICATIONS FOR DENTAL AIR PIPING TO INCLUDE PIPE,
 FITTINGS AND JOINTS. SHOW COMPLIANCE WITH NFPA 99-18,
 SECTION 15.5.5.2.2 THROUGH 15.5.5.3.2.3.
  
 7. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION SHEETS/INSTALLATION MANUAL FOR DENTAL
 EQUIPMENT AND COMPONENTS INCLUDING BUT NOT LIMITED TO
 OUTLETS, VALVES, GAUGES, CONTROLS.
  
 8. PER WPB FBC 107.2.1, PROVIDE RISER DIAGRAM OF PIPING
 SYSTEMS FROM SOURCE TO OUTLETS, INCLUDE ALL IN-LINE
 COMPONENTS
  
 9. PER WPB FBC 107.2.1, PROVIDE LOCATION AND DETAIL
 TERMINATION OF VACUUM PUMP EXHAUST VENT INCLUDING
 ELEVATION AND ANCHORING DETAILS. COMPLY WITH ALL
 REQUIREMENTS OF NFPA 99-15, SECTIONS 5.1.3.7.6.2
 THROUGH 5.1.3.7.6.5.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-04-12 Cont ID  
Sent By jesmith Date 2022-04-12 Time 16:09 Rev Time 0.00
Received By jesmith Date 2022-04-05 Time 14:58 Sent To  
Notes
2022-04-05 14:58:5921121105 1501 PRESIDENTIAL WAY # 19
  
  
 PLUMBING COMMENTS: APPROVED
  
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO: SEE P-3/EWH & RECIRC PUMP DIAGRAM. DISCHARGE
 FROM EXPANSION VALVE RELIEF OUTLET SHALL BE PIPED TO
 THE PAN DRAIN OR MOP SINK THROUGH AN AIR GAP
  
 PROVISO: MANUFACTURER'S SPECIFICATION/INSTALLATION
 MANUAL FOR THE BACKFLOW PREVENTER AT THE WATER
 CONNECTION TO THE VACUUM PUMP SHALL BE ON SITE FOR
 INSPECTION.
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-10 Cont ID  
Sent By jesmith Date 2022-03-10 Time 15:02 Rev Time 0.00
Received By jesmith Date 2022-03-10 Time 14:31 Sent To  
Notes
2022-03-10 14:59:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121105 1501 PRESIDENTIAL WAY # 19
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 1.SECOND REQUEST: ARCHITECT RESPONSE NOTED A.3/WALL
 FINISH SCHEDULE REVISED TO SPECIFY TILE FOR RESTROOM
 WALLS TO COMPLY WITH FBC 1210.2.2, FBC PL 310.3.
 SCHEDULE STILL INDICATES PAINT.
  
 2.NEW COMMENT: P.3/EWH & RECIRC PUMP DIAGRAM; REFER TO
 WATTS MANUFACTURER'S INSTALLATION GUIDE. COLD-WATER
 SUPPLY PIPE TO RISE TO A LEVEL EVEN WITH THE TOP OR
 ABOVE THE WATER HEATER WHERE THE DEVICE WILL BE
 INSTALLED IN A VERTICAL POSITION, THEN THEN PIPE DOWN
 AND INTO THE COLD-WATER INLET. INSTALLATION SHALL
 COMPLY WITH MANUFACTURER'S RECOMMENDATIONS PER FBC PL
 310.7 AND 303.2.
  
 3.SECOND REQUEST: P.3/EWH & RECIRC PUMP DIAGRAM;
 PROVIDE, SPECIFY (MANUFACTURER AND SIZE) AND POSITION
 THERMAL EXPANSION CONTROL DEVICE. FBC PL 607.3.
  
 4.P-4/WATER FILTER DETAIL
 ***A) SECOND REQUEST A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE SUPPLY TO THE WATER FILTER PER FBC PL
 604.9. PER WPB FBC 107.2.1, INDICATE ON DETAIL. TO BE
 CLEAR, THE WATER FILTER DETAIL SHOWS A SOLENOID VALVE.
 IF THIS IS A BALL VALVE THEN REMOVE REFERENCE TO A
 SOLENOID VALVE ON THE DETAIL
 ***B) NEW COMMENT/SECOND REQUEST: REGARDING THE CHECK
 VALVE/VACUUM BREAKER ON THE WATER INLET. ENGINEER'S
 RESPONSE IS THAT A WATTS 007 SERIES DOUBLE CHECK VALVE
 IS TO BE USED. PER WPB FBC 107.2.1, INDICATE THE SAME
 ON THE DETAIL.
  
 5.P-4/VACUUM PUMP DETAIL: ENGINEER'S RESPONSE NOTED
 BACKFLOW PREVENTION DEVICE IS FURNISHED BY THE
 EQUIPMENT SUPPLIER. A REVIEW OF THE SUBMITTAL SHEETS
 DOES NOT IN ANY WAY REFERENCE A BACKFLOW PREVENTER.
 REGARDLESS OF WHO PROVIDES THE DEVICE, IT STILL NEEDS
 TO BE SPECIFIED AND REVIEWED FOR APPROVAL.
 SECOND REQUEST: PER WPB FBC 107.2.1, SPECIFY TYPE OF
 BACKFLOW PREVENTER TO BE INSTALLED ON THE COLD-WATER
 CONNECTION. SHALL COMPLY WITH FBC PL 608.14.1,
 608.14.2, 608.14.5, 608.14.6 OR 608.14.8. PROVIDE
 APPLICABLE STANDARD (I.E. ASSE, ASME)
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-18 Cont ID  
Sent By jesmith Date 2022-01-18 Time 15:33 Rev Time 0.00
Received By jesmith Date 2022-01-11 Time 17:07 Sent To  
Notes
2022-01-18 15:33:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 NFPA 99-18 = HEALTH CARE FACILITIES CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21121105 1501 PRESIDENTIAL WAY # 19
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE ON THE PLANS, THE FOLLOWING
 CLARIFICATIONS:
 ?.A)MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 "REFLECTING SURFACE" 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 ?.B)PROVIDE NOTE: PER FBC ACC602.7, SPOUT OUTLETS OF
 DRINKING FOUNTAINS FOR STANDING PERSONS SHALL BE 38
 INCHES (965 MM) MINIMUM AND 43 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 2.SEE FBC 1210.2.2, FBC PL 310.3. WALLS AND PARTITIONS
 WITHIN 2 FEET OF SERVICE SINKS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NON-ABSORBENT SURFACE PER
 FBC-BUILDING SEC. 1210.2.2. SECTION 1210.2.2 STIPULATES
 THAT THE MATERIAL BE "HARD." THE INTENT OF THIS SECTION
 IS THAT THE SURROUNDING MATERIAL SHOULD NOT BE OF A
 TYPE THAT IS EASILY DAMAGED SUCH THAT THE MATERIAL
 COULD BECOME ABSORBENT AND THUS, NOT READILY CLEANABLE
 AND SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
 THE FINISH SCHEDULE CALLS OUT TWO PART EPOXY PAINT.
 THIS DOES NOT COMPLY.
  
 3.ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 4.PER WPB FBC 107.2.1, PROVIDE AT THE PIPE HANGER
 DETAIL A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 5.RE: WATER HEATER DETAIL.: PER WPB FBC 107.2.1,
 PROVIDE A MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL. INDICATE ON DETAIL BOTTOM FED OR TOP FED COLD
 WATER SUPPLY, NOTING VACUUM RELIEF VALVE OR COLD DIP
 TUBE AS IS APPLICABLE (SEE FBC PL 504.1, 504.2);
 PROVIDE, SPECIFY (MANUFACTURER AND SIZE) AND POSITION
 THERMAL EXPANSION CONTROL DEVICE. FBC PL 607.3.
 PROVIDE AIR GAP FOR T&P DISCHARGE TO PAN; SHALL
 TERMINATE NOT MORE THAN 6 INCHES) ABOVE AND NOT LESS
 THAN TWO TIMES THE DISCHARGE PIPE DIAMETER ABOVE THE
 FLOOR OR FLOOD LEVEL RIM OF THE PAN PER FBC PL
 504.6(10).
  
 6.SLAB REPAIR DETAIL SUBMIT A SLAB REPAIR DETAIL SHOW
 THE WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE SIZE AND LENGTH OF THE DOWELS, THE MINIMUM
 EMBEDMENT DEPTH INTO THE EXISTING SLAB, THE ANCHORING
 MATERIAL FOR THE DOWELS AND THE SPACING OF THE DOWELS
 ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE
 TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER
 OVER WELL-COMPACTED SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 7.WATER RISER: PER WPB FBC 107.2.1, SIZE ALL PIPING.
  
 8.P-2/NOTE 21: PER WPB FBC 107.2.1, SELECT TRAP SEAL
 METHOD AND PROVIDE A DETAIL FOR THE TRAP PRIMER.
  
 9.P-4/WATER FILTER DETAIL
 ?.A) A WATER HAMMER ARRESTOR IS REQUIRED ON THE SUPPLY
 TO THE WATER FILTER PER FBC PL 604.9. PER WPB FBC
 107.2.1, INDICATE ON DETAIL.
 ?.B)DETAIL SHOWS A CHECK VALVE AND INDICATES A VACUUM
 BREAKER ON WATER INLET. PER WPB FBC 107.2.1, SPECIFY
 TYPE OF BACKFLOW PREVENTER (SEE FBC PL 608.1, TABLE
 608.1) TO BE INSTALLED AT THE WATER FILTER INLET.
 PROVIDE ASSE OR CSA STANDARD. REVISE DETAIL TO REFLECT.
  
 10.P-4/VACUUM PUMP DETAIL:
 PER WPB FBC 107.2.1, SPECIFY TYPE OF BACKFLOW PREVENTER
 TO BE INSTALLED ON THE COLD WATER CONNECTION. SHALL
 COMPLY WITH FBC PL 608.14.1, 608.14.2, 608.14.5,
 608.14.6 OR 608.14.8. PROVIDE APPLICABLE STANDARD (I.E.
 ASSE, ASME)
  
 11.PROVIDE MANUFACTURER SPECIFICATION/INSTALLATION
 MANUAL FOR DENTAL EQUIPMENT
  
 12.M-2/ NOTE 29 STATES SEE PLUMBING DRAWINGS FOR AC
 CONDENSATE. P-2/NOTE 13 PROVIDES AC CONDENSATE MATERIAL
 SPECIFICATION BUT NO PIPING IS SHOWN ON PLANS. THERE IS
 A NOTE 9 ON M-1 CALLING OUT 2 INCH DEEP TRAP WITH 3/4
 INCH PVC TO EXISTING CONDENSATE RISERS. PER WPB FBC
 107.2.1, PROVIDE ROUTING OF CONDENSATE DRAINS.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK TUESDAYS AND
 THURSDAYS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-05-09 Cont ID  
Sent By fgiaquin Date 2022-05-09 Time 23:08 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-04-15 Cont ID  
Sent By medwards Date 2022-04-15 Time 07:41 Rev Time 0.00
Received By medwards Date 2022-04-15 Time 07:41 Sent To  
Notes
2022-04-15 07:42:22ELECTRICAL SHEET E.2 HAS A COPY OF A DIGITAL SIGNATURE.
 PLEASE PROVIDE THE ORIGINAL DIGITALLY SIGNED DRAWING.
 FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2022-04-05 15:55:06SIGNATURES FOR PLUMBING ARE VALID. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-03-16 Cont ID  
Sent By medwards Date 2022-03-16 Time 11:23 Rev Time 0.00
Received By medwards Date 2022-03-16 Time 11:23 Sent To  
Notes
2022-03-16 11:25:24VERSION 2 DOCUMENTS HAVE A COPY OF THE ORIGINAL DIGITAL
 SIGNATURE. PLEASE SUBMIT THE ORIGINAL DIGITALLY SIGNED
 DRAWINGS.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2022-03-15 09:50:03SIGNATURES FOR PLUMBING; NOT APPARENT IN PDFS.
 CORRECTIONS NEEDED. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-08 Cont ID  
Sent By jwitmer Date 2022-02-08 Time 14:12 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***