| Plan Review Stops For Permit 21121091 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2022-04-20 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-04-20 |
Time |
20:38 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-04-20 |
Time |
19:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-04-05 |
Time |
19:44 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-04-05 |
Time |
19:09 |
Sent To |
|
|
| Notes |
| 2022-04-05 19:44:33 | PROVIDE ACTUAL LOAD STUDY FROM FPL THE LOCAL POWER | | | UTILTIY. WHAT WAS PROVIDED DOES NOT SHOW THAT IT IS | | | FROM FPL. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-03-19 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-19 |
Time |
15:08 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-03-19 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2022-03-19 15:08:53 | PREVIOUS PLAN REVIEW COMMENTS NOT ADDRESSED | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-02-01 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-01 |
Time |
22:55 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-02-01 |
Time |
22:35 |
Sent To |
|
|
| Notes |
| 2022-02-01 22:55:55 | SEE PREVIOUS PLAN REVIEW COMMENTS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-01-22 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-01-22 |
Time |
20:27 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-01-22 |
Time |
20:08 |
Sent To |
|
|
| Notes |
| 2022-01-22 20:26:58 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. VALUE LOW FOR AMOUNT OF WORK SHOWN. ALL MATERIALS | | | AND LABOR TO BE INCLUDED REGARDLESS IF CUSTOMER | | | PROVIDED. PROVIDE ACCURATE VALUE AND COST BREAK DOWN. | | | FBC 109.3 | | | | | | 2. PROVIDE LOAD STUDY USED IN LOAD CALCULATION FROM | | | POWER UTILITY COMPANY. FBC 107.2.1 NEC 220 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-04-20 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-04-20 |
Time |
20:39 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-04-07 |
Time |
09:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-04-05 |
Time |
19:44 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-03-24 |
Time |
16:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-03-19 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-19 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-03-09 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-01 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-01 |
Time |
22:56 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-01-28 |
Time |
16:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-22 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-01-22 |
Time |
20:27 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-01-03 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-13 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-13 |
Time |
08:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2022-03-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-29 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-29 |
Time |
15:27 |
Sent To |
|
|
| Notes |
| 2022-03-29 15:30:15 | E-1 ELECTRICAL DRAWING STILL HAS A WALK-IN FREEZER | | | COOLER UNIT IN THE SCOPE OF WORK. IF THERE IS TO BE NO | | | WALK-IN FREEZER COOLER UNIT PLEASE REMOVE THIS FROM THE | | | SCOPE OF WORK. IF IT IS TO BE INSTALLED PLEASE SHOW THE | | | LOCATION OF THE UNIT AND THE LOCATION OF THE CONDENSING | | | UNIT. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-03-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-10 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-10 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2022-03-10 09:11:30 | PLEASE RESPOND TO PREVIOUS REVIEW COMMENT BELOW: | | | | | | PLEASE AMEND THE PERMIT APPLICATION TO ALSO INCLUDE THE | | | WALKIN FREEZER. | | | PLEASE ADJUST THE VALUE OF THIS PROJECT TO SHOW THE | | | WALKIN FREEZER. THE VALUE SHOULD REFLECT THE COST OF | | | THE EQUIPMENT AND THE LABOR ASSOCIATED WITH THIS | | | PROJECT. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-01-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-31 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-31 |
Time |
09:41 |
Sent To |
|
|
| Notes |
| 2022-01-31 09:44:32 | PLEASE AMEND THE PERMIT APPLICATION TO ALSO INCLUDE THE | | | WALKIN FREEZER. | | | PLEASE ADJUST THE VALUE OF THIS PROJECT TO SHOW THE | | | WALKIN FREEZER. THE VALUE SHOULD REFLECT THE COST OF | | | THE EQUIPMENT AND THE LABOR ASSOCIATED WITH THIS | | | PROJECT. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-05 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-05 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2022-01-05 09:46:32 | SHEET E1 INDICATES THERE IS ALSO A SELF CONTAINED WALK | | | IN FREEZER/COOLER UNIT. IS THIS GOING TO BE PART OF THE | | | MECHANICAL CONTRACTORS SCOPE OF WORK? IF SO PLEASE | | | INCLUDE THE SPECIFICATIONS FOR THIS UNIT AND SHOW THIS | | | WALKIN FREEZER/COOLER ON THE DRAWING. IF NOT THEN | | | ANOTHER PERMIT APPLICATION AND REVIEW WILL BE REQUIRED. | | | FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-04-20 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-04-20 |
Time |
20:39 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-03-19 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-03-19 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-02-01 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-01 |
Time |
22:56 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-01-22 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-01-22 |
Time |
20:27 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-01-22 |
Time |
20:27 |
Sent To |
|
|
| Notes |
|
|