Plan Review Details - Permit 21121091
Plan Review Stops For Permit 21121091
Review Stop E ELECTRICAL
Rev No 5 Status P Date 2022-04-20 Cont ID  
Sent By fgiaquin Date 2022-04-20 Time 20:38 Rev Time 0.00
Received By fgiaquin Date 2022-04-20 Time 19:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2022-04-05 Cont ID  
Sent By fgiaquin Date 2022-04-05 Time 19:44 Rev Time 0.00
Received By fgiaquin Date 2022-04-05 Time 19:09 Sent To  
Notes
2022-04-05 19:44:33PROVIDE ACTUAL LOAD STUDY FROM FPL THE LOCAL POWER
 UTILTIY. WHAT WAS PROVIDED DOES NOT SHOW THAT IT IS
 FROM FPL.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-03-19 Cont ID  
Sent By fgiaquin Date 2022-03-19 Time 15:08 Rev Time 0.00
Received By fgiaquin Date 2022-03-19 Time 14:15 Sent To  
Notes
2022-03-19 15:08:53PREVIOUS PLAN REVIEW COMMENTS NOT ADDRESSED
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-02-01 Cont ID  
Sent By fgiaquin Date 2022-02-01 Time 22:55 Rev Time 0.00
Received By fgiaquin Date 2022-02-01 Time 22:35 Sent To  
Notes
2022-02-01 22:55:55SEE PREVIOUS PLAN REVIEW COMMENTS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-22 Cont ID  
Sent By fgiaquin Date 2022-01-22 Time 20:27 Rev Time 0.00
Received By fgiaquin Date 2022-01-22 Time 20:08 Sent To  
Notes
2022-01-22 20:26:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE LOW FOR AMOUNT OF WORK SHOWN. ALL MATERIALS
 AND LABOR TO BE INCLUDED REGARDLESS IF CUSTOMER
 PROVIDED. PROVIDE ACCURATE VALUE AND COST BREAK DOWN.
 FBC 109.3
  
 2. PROVIDE LOAD STUDY USED IN LOAD CALCULATION FROM
 POWER UTILITY COMPANY. FBC 107.2.1 NEC 220
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-04-20 Cont ID  
Sent By fgiaquin Date 2022-04-20 Time 20:39 Rev Time 0.00
Received By fgiaquin Date 2022-04-07 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-05 Cont ID  
Sent By fgiaquin Date 2022-04-05 Time 19:44 Rev Time 0.00
Received By fgiaquin Date 2022-03-24 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-19 Cont ID  
Sent By fgiaquin Date 2022-03-19 Time 15:09 Rev Time 0.00
Received By fgiaquin Date 2022-03-09 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-01 Cont ID  
Sent By fgiaquin Date 2022-02-01 Time 22:56 Rev Time 0.00
Received By fgiaquin Date 2022-01-28 Time 16:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-22 Cont ID  
Sent By fgiaquin Date 2022-01-22 Time 20:27 Rev Time 0.00
Received By fgiaquin Date 2022-01-03 Time 08:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2022-04-25 Cont ID  
Sent By medwards Date 2022-04-13 Time 08:38 Rev Time 0.00
Received By medwards Date 2022-04-13 Time 08:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2022-03-29 Cont ID  
Sent By medwards Date 2022-03-29 Time 15:27 Rev Time 0.00
Received By medwards Date 2022-03-29 Time 15:27 Sent To  
Notes
2022-03-29 15:30:15E-1 ELECTRICAL DRAWING STILL HAS A WALK-IN FREEZER
 COOLER UNIT IN THE SCOPE OF WORK. IF THERE IS TO BE NO
 WALK-IN FREEZER COOLER UNIT PLEASE REMOVE THIS FROM THE
 SCOPE OF WORK. IF IT IS TO BE INSTALLED PLEASE SHOW THE
 LOCATION OF THE UNIT AND THE LOCATION OF THE CONDENSING
 UNIT. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 09:10 Rev Time 0.00
Received By medwards Date 2022-03-10 Time 09:10 Sent To  
Notes
2022-03-10 09:11:30PLEASE RESPOND TO PREVIOUS REVIEW COMMENT BELOW:
  
 PLEASE AMEND THE PERMIT APPLICATION TO ALSO INCLUDE THE
 WALKIN FREEZER.
 PLEASE ADJUST THE VALUE OF THIS PROJECT TO SHOW THE
 WALKIN FREEZER. THE VALUE SHOULD REFLECT THE COST OF
 THE EQUIPMENT AND THE LABOR ASSOCIATED WITH THIS
 PROJECT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-01-31 Cont ID  
Sent By medwards Date 2022-01-31 Time 09:41 Rev Time 0.00
Received By medwards Date 2022-01-31 Time 09:41 Sent To  
Notes
2022-01-31 09:44:32PLEASE AMEND THE PERMIT APPLICATION TO ALSO INCLUDE THE
 WALKIN FREEZER.
 PLEASE ADJUST THE VALUE OF THIS PROJECT TO SHOW THE
 WALKIN FREEZER. THE VALUE SHOULD REFLECT THE COST OF
 THE EQUIPMENT AND THE LABOR ASSOCIATED WITH THIS
 PROJECT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By medwards Date 2022-01-05 Time 09:43 Rev Time 0.00
Received By medwards Date 2022-01-05 Time 09:43 Sent To  
Notes
2022-01-05 09:46:32SHEET E1 INDICATES THERE IS ALSO A SELF CONTAINED WALK
 IN FREEZER/COOLER UNIT. IS THIS GOING TO BE PART OF THE
 MECHANICAL CONTRACTORS SCOPE OF WORK? IF SO PLEASE
 INCLUDE THE SPECIFICATIONS FOR THIS UNIT AND SHOW THIS
 WALKIN FREEZER/COOLER ON THE DRAWING. IF NOT THEN
 ANOTHER PERMIT APPLICATION AND REVIEW WILL BE REQUIRED.
 FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-04-20 Cont ID  
Sent By fgiaquin Date 2022-04-20 Time 20:39 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-19 Cont ID  
Sent By fgiaquin Date 2022-03-19 Time 15:09 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-01 Cont ID  
Sent By fgiaquin Date 2022-02-01 Time 22:56 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-22 Cont ID  
Sent By fgiaquin Date 2022-01-22 Time 20:27 Rev Time 0.00
Received By fgiaquin Date 2022-01-22 Time 20:27 Sent To  
Notes
***NONE***