Plan Review Details - Permit 21121090
| Plan Review Stops For Permit 21121090 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-08 |
Time |
22:21 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-02-08 |
Time |
22:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-01-25 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-01-25 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-01-25 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2022-01-25 15:22:39 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. FIRE ALARM DESIGNS OVER $5000 MUST BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL. | | | FBC 105.3.1.2 #4 | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-02-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-12-30 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2021-12-30 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-12-30 13:27:26 | FIRE PROVISO NOTE: | | | ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A CERTIFIED | | | FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA 72. THIS MAY | | | REQUIRE SEPARATE SHOP DRAWINGS TO BE SUBMITTED, | | | REVIEWED, AND APPROVED PRIOR TO ANY WORK ON THE SYSTEM, | | | INCLUDING CONNECTING TO THE EXISTING FIRE ALARM SYSTEM. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-17 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-17 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-02-08 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-01-25 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-12-29 |
Time |
14:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2022-01-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-06 |
Time |
06:37 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-06 |
Time |
06:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-02-08 |
Time |
22:21 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-02-08 |
Time |
22:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-01-25 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-01-25 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-01-25 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2022-01-25 15:23:15 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. FIRE ALARM DESIGNS OVER $5000 MUST BE DESIGNED AND | | | SIGNED/SEALED BY A DESIGN PROFESSIONAL. | | | FBC 105.3.1.2 #4 | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
|