Plan Review Details - Permit 21121087
Plan Review Stops For Permit 21121087
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-15 Cont ID  
Sent By jleahy Date 2022-05-15 Time 15:28 Rev Time 0.00
Received By jleahy Date 2022-05-15 Time 15:28 Sent To  
Notes
2022-05-15 15:29:22PAD PLAN DONE UNDER THE ELECTRICAL REVIEW. JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-09 Cont ID  
Sent By rmcdouga Date 2022-03-09 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2022-03-09 Time 16:09 Sent To  
Notes
2022-03-09 16:19:57PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY HOW THE GENERATOR WILL BE ANCHORED TO THE
 CONCRETE PAD FOR WIND LOADS. FBC-R 301
  
 2) FBC-R303.5 OPENING LOCATION. OUTDOOR INTAKE AND
 EXHAUST OPENINGS SHALL BE LOCATED IN ACCORDANCE WITH
 SECTIONS R303.5.1 AND R303.5.2.
 THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. PLEASE SPECIFY
 THIS ON THE SURVEY.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-15 Cont ID  
Sent By jleahy Date 2022-05-15 Time 15:24 Rev Time 0.00
Received By jleahy Date 2022-05-15 Time 15:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-27 Cont ID  
Sent By jleahy Date 2022-01-27 Time 14:41 Rev Time 0.00
Received By jleahy Date 2022-01-27 Time 14:37 Sent To  
Notes
2022-01-27 15:17:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) 1. VALUE FOR WORK STATED ON PERMIT APPLICATION
 APPEARS LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND
 LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED
 CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C.
 109.3
  
 2) PLEASE INDICATE WHICH PANEL OR PANELS THE GENERATOR
 WILL FEED.
  
 3) PLEASE INDICATE THE SIZE AND NUMBER OF CONDUCTORS
 GOING THROUGH THE NIPPLE BETWEEN METER AND TRANSFER
 SWITCH.
  
 4) PLAN DOES NOT REALLY INDICATE THE SIZE OF THE
 GENERATOR, PLEASE INDICATE THE SIZE OF THE GENERATOR.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-31 Cont ID  
Sent By jleahy Date 2022-05-31 Time 12:34 Rev Time 0.00
Received By jleahy Date 2022-05-24 Time 10:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2022-05-15 Cont ID  
Sent By jleahy Date 2022-05-15 Time 15:29 Rev Time 0.00
Received By jleahy Date 2022-05-02 Time 11:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-09 Cont ID  
Sent By rmcdouga Date 2022-03-09 Time 16:20 Rev Time 0.00
Received By rmcdouga Date 2022-01-05 Time 08:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-31 Cont ID  
Sent By jleahy Date 2022-05-31 Time 12:34 Rev Time 0.00
Received By jleahy Date 2022-05-31 Time 12:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-15 Cont ID  
Sent By jleahy Date 2022-05-15 Time 15:28 Rev Time 0.00
Received By jleahy Date 2022-05-15 Time 15:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-09 Cont ID  
Sent By rmcdouga Date 2022-03-09 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2022-03-09 Time 15:56 Sent To  
Notes
2022-03-09 16:01:00THE ENGINEER'S DIGITAL SIGNATURE ON THE GENERATOR PAD
 DRAWING CAN NOT BE VERIFIED. IT DOES NOT APPEAR TO BE
 AN ORIGNAL ELECTRONIC DOCUMENT. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 3 Status P Date 2022-05-27 Cont ID  
Sent By vbroglia Date 2022-05-27 Time 13:24 Rev Time 0.00
Received By vbroglia Date 2022-05-27 Time 13:24 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-05-09 Cont ID  
Sent By vbroglia Date 2022-05-09 Time 16:48 Rev Time 0.00
Received By vbroglia Date 2022-05-09 Time 16:48 Sent To  
Notes
2022-05-09 16:51:4705/09/2022 FAILED
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS
 MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED
 SIDE SETBACK.
  
 GENERATOR NEEDS TO BE 8 FEET OFF THE REAR PROPERTY LINE
 AS THE REQUIRED REAR SETBACK IS 12 FEET (10% OF THE LOT
 DEPTH)
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-19 Cont ID  
Sent By vbroglia Date 2022-01-19 Time 12:50 Rev Time 0.00
Received By vbroglia Date 2022-01-19 Time 12:50 Sent To  
Notes
2022-01-19 12:53:031/19/22 FAILED- PLEASE SHOW THE DISTANCE/SETBACKS FROM
 THE PROPERTY LINE TO THE PROPOSED LOCATION OF THE
 GENERATOR
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  