Plan Review Details - Permit 21121060
| Plan Review Stops For Permit 21121060 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-02-09 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-09 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-09 |
Time |
09:28 |
Sent To |
|
|
| Notes |
| 2022-02-09 09:34:39 | ELECTRIC REVIEW FAILED | | | 1) RISER DIAGRAM IS INCORRECTLY DRAWN, WITH FPL MAST | | | GOING TO DISCONNECT INSTEAD OF METER, (2) 2' CONDUITS | | | SHOWN GOING FROM METER TO DISCONNECT ARE ALSO | | | INCORRECT. PLEASE SUBMIT A CORRECT RISER DIAGRAM . NEC | | | 215.5 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-27 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-27 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2022-01-27 09:04:31 | ELECTRIC REVIEW FAILED | | | 1)DRAWING DENOTES 3/0 CU SERVICE ENTRANCE CONDUCTORS | | | FOR 400-AMP SERVICE. CORRECT CONDUCTOR SIZE AS PER NEC | | | 310.15.(B) | | | 2) DRAWINGS STATES MDP IS SINGLE PHASE PLEASE CORRECT. | | | NEC 215.5 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-04 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-18 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-09 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-09 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-09 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-27 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-27 |
Time |
09:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-04 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-04 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-02-09 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-09 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-09 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-27 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-27 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2022-01-27 09:06:51 | SIGNATURE REVIEW FAILED | | | IT APPEARS ALL DRAWINGS ARE COPIES/SCANS OF ENGINEERED, | | | DIGITALLY SIGNED AND SEALED DRAWINGS. COPIES OR SCANS | | | OF DOCUMENTS WITH ENGINEERS DIGITAL SIGNATURES CANNOT | | | BE CERTIFIED USING SIGNATURE, CERTIFYING, SOFTWARE. | | | PLANS SUBMITTED ELECTRONICALLY MUST BE DIGITALLY SIGNED | | | AND SEALED BY THE ENGINEER OF RECORD. PLEASE FOLLOW THE | | | DIRECTIONS OUTLINED BELOW TO CORRECT THIS ISSUE. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
|