Plan Review Details - Permit 21121052
Plan Review Stops For Permit 21121052
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-03-07 Cont ID  
Sent By cpuell Date 2022-03-07 Time 17:01 Rev Time 0.00
Received By cpuell Date 2022-03-07 Time 17:01 Sent To  
Notes
2022-03-07 17:01:50UPDATED ADDRESS TO 585 FERN ST

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By cpuell Date 2021-12-27 Time 12:11 Rev Time 0.00
Received By cpuell Date 2021-12-27 Time 12:11 Sent To  
Notes
2021-12-27 12:13:10AREA OF WORK TO BE WORKED ON HAD PREVIOUSLY BEEN ISSUED
 AN ADDRESS OF 585 FERN ST, PLEASE UPDATE ALL THE PLANS
 AND APPLICATION FORMS TO REMOVE AN REFERENCE OF THE
 INCORRECT ADDRESS OF 360 S ROSEMARY AVE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-03-23 Cont ID  
Sent By rmcphers Date 2022-03-23 Time 09:28 Rev Time 0.00
Received By rmcphers Date 2022-03-23 Time 09:28 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-02-09 Cont ID  
Sent By rmcphers Date 2022-02-09 Time 11:50 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 15:34 Sent To  
Notes
2022-02-09 11:52:42PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-27 Cont ID  
Sent By rmcphers Date 2022-04-27 Time 10:04 Rev Time 0.00
Received By rmcphers Date 2022-04-27 Time 10:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-23 Cont ID  
Sent By rmcphers Date 2022-03-23 Time 09:13 Rev Time 0.00
Received By rmcphers Date 2022-03-23 Time 09:13 Sent To  
Notes
2022-03-23 09:28:35RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) DRAWING A9.0.1 DETAIL 5 SHOWS WALL TILE AT AN
 ELEVATION OF 3 FOOT 6 INCHES - PLEASE SHOW THE WALLS AT
 THE URNALS AND TOILETS TO COMPLY WITH FBC 1210.2.2
 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-09 Cont ID  
Sent By rmcphers Date 2022-02-09 Time 12:56 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 15:34 Sent To  
Notes
2022-02-09 12:54:06RESTAURANT BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) RAMP HAND RAIL EXTENSION SHOULD NOT TURN AROUND THE
 CORNER AS SHOWN ON DRAWING A1.1.1 FBC A 505.10.1 TOP
 AND BOTTOM EXTENSION AT RAMPS.
 RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE
 LANDING FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP
 AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A
 WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN.
  
 2) PLEASE SHOW THE REQUIRED HANDRAILS AT ALL OF THE
 RAMPS FBC 405.8
  
 3) PLEASE SHOW THE DOOR MANEUVERING CLEARANCE ON THE
 INTERIOR SIDE OF RESTROOM (DOOR 113) (18" BESIDE THE
 LATCH SIDE) FBC 404.2.4
  
 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR
 DIMENSIONS FROM THE FINISHED FLOOR TO THE BOTTOM OF THE
 "REFLECTIVE SURFACE" FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 5) PLEASE SHOW THE HOURLY FIRE RATING FOR THE DOORS
 LOCATED IN THE FIRE PARTITIONS FBC 716
  
 6) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS - ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD
 FBC WPB 107.3.4
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-05-12 Cont ID  
Sent By jleahy Date 2022-05-12 Time 16:39 Rev Time 0.00
Received By jleahy Date 2022-05-12 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-04-29 Cont ID  
Sent By mpeterso Date 2022-04-29 Time 12:46 Rev Time 0.00
Received By mpeterso Date 2022-04-29 Time 12:46 Sent To  
Notes
2022-04-29 13:05:03ELECTRIC REVIEW FAILED
 1) RISER DIAGRAM DETAILS 3P-400-AMP FEEDING
 TRANSFORMER. PANEL SCEDULE DETAILS PANEL HC-1 FEEDING
 TRANSFORMER. PLEASE DETAIL CORRECT PANEL FEEDING
 TRANSFORMER. NEC 215.5
 2) PANEL SCHEDULE HC 1 DETAILS 125-AMP BREAKER FEEDING
 PANEL AC VIA TRANSFORMER. THIS TRANSFORMER FEEDS PANEL
 LC1. PLEASE CORRECT PANEL SCHEDULE AS APPROPRIATE. NEC
 215.5
 3) PRIMARY OVER CURRENT PROTECTION IS DETAILED AS
 125-AMP FOR 225 KVA TRANSFORMER APPEARS TO BE TOO
 SMALL. PLEASE CORRECT SIZE AS PER NEC 450.3(B)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-02-02 Cont ID  
Sent By jleahy Date 2022-02-02 Time 15:08 Rev Time 0.00
Received By jleahy Date 2022-01-31 Time 14:01 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-03-24 Cont ID  
Sent By mpeterso Date 2023-03-24 Time 14:39 Rev Time 0.00
Received By mpeterso Date 2023-03-24 Time 14:39 Sent To  
Notes
2023-03-24 14:40:21VOICE AND DATA AS PER PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-08 Cont ID  
Sent By cwalker Date 2022-03-08 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-03-08 09:19:15FIRE PROVISO NOTES:
 1. ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A
 CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA
 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
 2. THE LIFE SAFETY SYSTEMS, FIRE SPRINKLER AND/OR FIRE
 ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION
 PERIOD.
 3. ENSURE THAT EMERGENCY AND EXIT LIGHTING IS SUPPLIED
 FOR ALL EXITS AND EXIT PATHS. THIS INCLUDES WALK IN
 UNITS. A COMBINATION EXIT/EMERGENCY UNIT IS ACCEPTABLE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-29 Cont ID  
Sent By cwalker Date 2021-12-29 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2021-12-29 12:52:50FIRE PROVISO NOTES:
 1.ALL FIRE ALARM SYSTEM WORK SHALL BE DONE BY A
 CERTIFIED FIRE ALARM CONTRACTOR AND COMPLY WITH NFPA
 72. A SEPARATE SHOP DRAWING IS REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY WORK ON THE SYSTEM.
 2.THE LIFE SAFETY SYSTEMS, FIRE SPRINKLER AND/OR FIRE
 ALARM, SHALL REMAIN ACTIVE THROUGHOUT THE CONSTRUCTION
 PERIOD.
 3.ENSURE THAT EMERGENCY AND EXIT LIGHTING IS SUPPLIED
 FOR ALL EXITS AND EXIT PATHS. THIS INCLUDES WALK IN
 UNITS. A COMBINATION EXIT/EMERGENCY UNIT IS ACCEPTABLE.
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-05-12 Cont ID  
Sent By ccole Date 2022-05-12 Time 17:04 Rev Time 0.00
Received By ccole Date 2022-05-12 Time 15:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-04-15 Cont ID  
Sent By ccole Date 2022-04-15 Time 08:05 Rev Time 0.00
Received By ccole Date 2022-04-14 Time 10:40 Sent To  
Notes
2022-04-15 08:05:582ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21121052
 4/15/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS RROM THE
 1ST AND 2ND REVIEWS ARE LISTED BELOW WITH ADDITIONAL
 NOTES.
  
 2) FAILED. FG2.1 GAS RISER: B) SHOW THE TOTAL DEVELOPED
 LENGTH OF THE SYSTEM FROM THE METER TO THE MOST REMOTE
 APPLIANCE OUTLET- SEC. 402.4.1 FBC FG. NOT PROVIDED ON
 THE RISER.
  
 10) FAILED. FG0.1 & FG1.1: PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE PIZZA OVEN AND COOKING APPLIANCES
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. 304.1
 FBC FG.THE COMBUSTION AIR CALCULATIONS ON SHEET FG1.1
 ARE FOR FAN-ASSISTED APPLIANCES. BASED ON THE SUBMITTED
 SPECS, THE COOKING APPLIANCES AND PIZZA OVEN ARE NOT
 FAN-ASSISTED. PLEASE SEC. 202 FBC FG FOR DEFINITION OF
 FAN-ASSISTED APPLIANCES- AN APPLIANCE EQUIPPED WITH AN
 INTEGRAL MECHANICAL MEANS TO EITHER DRAW OR FORCE
 PRODUCTS OF COMBUSTION THROUGH THE COMBUSTION CHAMBER
 OR HEAT EXCHANGER. PLEASE NOTE WHERE COMBUSTION AIR IS
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR- SEC. 304.9.3 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-03-15 Cont ID  
Sent By ccole Date 2022-03-15 Time 13:14 Rev Time 0.00
Received By ccole Date 2022-03-14 Time 16:27 Sent To  
Notes
2022-03-15 13:20:182ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21121052
 3/15/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS RROM THE
 1SRT REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 2) FAILED. FG2.1 GAS RISER: B) SHOW THE TOTAL DEVELOPED
 LENGTH OF THE SYSTEM FROM THE METER TO THE MOST REMOTE
 APPLIANCE OUTLET- SEC. 402.4.1 FBC FG. NOT PROVIDED.
  
 4) FAILED. FG1.1 & FG1.2: AN AUTOMATIC GAS SHUTOFF
 VALVE WITH MANUAL RESET IS REQUIRED TO BE CONNECTED TO
 THE HOOD FIRE SUPPRESSION SYSTEM PER SEC. 10.4.1 NFPA
 96. THE VALVE DOES NOT APPEAR TO BE IN AN ACCESSIBLE
 LOCATION AS REQUIRED. PLEASE CORRECT THE PLAN AND
 PROVIDE THE VALVE SPECIFICATIONS. VALVE LOCATION NOT
 SHOWN ON RISER
  
 6) FAILED. FG1.1: INDICATE THE TYPE OF CONCENTRIC DUCT
 ON THE PLAN AND PROVIDE THE TOTAL RUN LENGTH AND SLOPE
 OF THE DUCT. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE WATER HEATERS, THE
 VENT DUCT AND TERMINATION CAP- SECS. 624.1, 503.2.3, &
 503.8 FBC FG. PLEASE SHOW THE TERMINATION CLEARANCE
 DISTANCES AS REQUIRED BY SEC. AND TABLE 503.8. SPECS
 FOR WATER HEATER AND CONCENTRIC VENT NOT PROVIDED.
  
  
 10) FAILED. FG0.1 & FG1.1: PROVIDE COMBUSTION AIR
 CALCULATIONS FOR THE PIZZA OVEN AND COOKING APPLIANCES
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. 304.1
 FBC FG. COMBUSTION AIR CALCULATIONS FOR THE PIZZA OVEN
 AND COOKING APPLIANCES NOT PROVIDED ON PLAN.
  
 11) FAILED. FG1.1: PROVIDE A CONDENSATE DISPOSAL PLAN
 FOR THE GAS-FIRED WATER HEATERS IN THE MEZZANINE- SECS.
 307.2, 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF
 CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN
 LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING
 DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P. SPECS FOR
 THE WATER HEATER NOT PROVIDED TO VERIFY INTEGRAL
 NEUTRALIZING DEVICE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-01-25 Cont ID  
Sent By ccole Date 2022-01-25 Time 09:07 Rev Time 0.00
Received By ccole Date 2022-01-25 Time 09:07 Sent To  
Notes
2022-01-25 09:08:421ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21121052
 1/25/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET FG0.1: THE GAS PIPE SIZING TABLE SHOWS AN
 INCORRECT TABLE FOR THE 2 PSI SYSTEM- SEE TABLE
 402.4(5) FBC FG. SEC. 402.3 FBC FG.
  
 2) FG2.1 GAS RISER:
 A) LABEL THE GAS APPLIANCES AND INDIVIDUAL BTUH LOADS
 AT EACH OUTLET- SEC. 402.4.1 FBC FG.
 B) SHOW THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM
 THE METER TO THE MOST REMOTE APPLIANCE OUTLET- SEC.
 402.4.1 FBC FG.
 C) SHOW THE BRANCH AND CUT PIPE LENGTH MEASUREMENTS-
 SEC. 402.4.2 FBC FG.
  
 3) FG0.1 DETAIL 1: SHOW PIPE UNIONS WITHIN 1 FT. OF
 EITHER SIDE OF THE REGULATOR- SEC. 410.2(7) FBC FG.
  
 4) FG1.1 & FG1.2: AN AUTOMATIC GAS SHUTOFF VALVE WITH
 MANUAL RESET IS REQUIRED TO BE CONNECTED TO THE HOOD
 FIRE SUPPRESSION SYSTEM PER SEC. 10.4.1 NFPA 96. THE
 VALVE DOES NOT APPEAR TO BE IN AN ACCESSIBLE LOCATION
 AS REQUIRED. PLEASE CORRECT THE PLAN AND PROVIDE THE
 VALVE SPECIFICATIONS.
  
 5) FG1.1: THE PLAN APPEARS TO SHOW THE TANKLESS WATER
 HEATER VENT PENETRATING THE EXIT STAIRWAY WHICH IS
 PROHIBITED IN ACCORDANCE WITH SEC. 1023.5 FBC B. PLEASE
 RELOCATE THE VENT.
  
 6) FG1.1: INDICATE THE TYPE OF CONCENTRIC DUCT ON THE
 PLAN AND PROVIDE THE TOTAL RUN LENGTH AND SLOPE OF THE
 DUCT. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE WATER HEATERS, THE
 VENT DUCT AND TERMINATION CAP- SECS. 624.1, 503.2.3, &
 503.8 FBC FG. PLEASE SHOW THE TERMINATION CLEARANCE
 DISTANCES AS REQUIRED BY SEC. AND TABLE 503.8.
  
 7) FG1.1: PROVIDE AN EQUIPMENT TAG FOR THE GAS-FIRE
 APPLIANCE DOWNSTREAM OF THE PIZZA OVEN- ITEM 24- SEC.
 107.2.1 WPB.
  
 8) FG2.1 GAS RISER: LABEL THE GAS APPLIANCES AND
 INDIVIDUAL BTUH LOADS AT EACH OUTLET- SEC. 402.4.1 FBC
 FG.
  
 9) FG0.1 & FG1.1: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE GAS-FIRED PIZZA OVEN AND COOKING APPLIANCES -
 SEC. 623.1 FBC FG.
  
 10) FG0.1 & FG1.1: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE PIZZA OVEN COOKING APPLIANCES AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SEC. 304.1 FBC FG.
  
 11) FG1.1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 GAS-FIRED WATER HEATERS IN THE MEZZANINE- SECS. 307.2,
 307.4, & 307.5 FBC FG. SHOW THE TYPE AND SIZE OF
 CONDENSATE PIPING, PIPING RUN, REQUIRED PAN, PAN DRAIN
 LINE AND DISPOSAL LOCATION. PLEASE NOTE A NEUTRALIZING
 DEVICE WILL BE REQUIRED PER SEC. 803.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2022-05-12 Time   Rev Time 0.00
Received By aoliver Date 2022-05-12 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-29 Cont ID  
Sent By mpeterso Date 2022-04-29 Time 13:05 Rev Time 0.00
Received By mpeterso Date 2022-04-12 Time 15:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-28 Cont ID  
Sent By medwards Date 2022-03-28 Time 08:07 Rev Time 0.00
Received By medwards Date 2022-03-07 Time 06:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-09 Cont ID  
Sent By rmcphers Date 2022-02-09 Time 13:06 Rev Time 0.00
Received By rmcphers Date 2021-12-27 Time 09:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2022-05-17 Cont ID  
Sent By rmcphers Date 2022-05-17 Time 14:37 Rev Time 0.00
Received By rmcphers Date 2022-05-17 Time 14:37 Sent To  
Notes
2022-05-17 14:38:28SHELL BUILDING - 360 ROSEMARY
2022-05-16 15:19:265/16/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-02-09 Cont ID  
Sent By rmcphers Date 2022-02-09 Time 12:57 Rev Time 0.00
Received By rmcphers Date 2022-02-09 Time 12:57 Sent To  
Notes
2022-02-09 12:57:53PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-05-12 Cont ID  
Sent By medwards Date 2022-05-12 Time 16:04 Rev Time 0.00
Received By medwards Date 2022-05-12 Time 16:04 Sent To  
Notes
2022-05-12 16:06:53THE KITCHEN HOOD AND GREASE DUCT DRAWINGS HAVE BEEN
 LOCKED AND WILL NOT BE A PART OF THIS REVIEW. WHEN THE
 KITCHEN HOOD GREASE DUCT PERMIT IS APPLIED FOR PLEASE
 SUBMIT THOSE DRAWINGS WITH THAT PERMIT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-04-29 Cont ID  
Sent By medwards Date 2022-04-29 Time 09:01 Rev Time 0.00
Received By medwards Date 2022-04-29 Time 09:01 Sent To  
Notes
2022-04-29 09:01:541ST REVIEW FMC
 PERMIT: 21121052
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REMOVE THE HOODS AND GREASE DUCT AND THE
 PIZZA OVENS SHEET M-503FROM THIS SUBMITTAL AS THEY WILL
 NOT BE REVIEWED UNDER THIS PERMIT AND REQUIRE A
 SEPARATE PERMIT AND REVIEW. THE HOODS AND GREASE DUCT
 ON THIS SHEET ARE MAKING IT DIFFICULT TO FOLLOW ALL THE
 CHANGES TO THE MECHANICAL SYSTEM OF THIS PROJECT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-03-28 Cont ID  
Sent By medwards Date 2022-03-28 Time 08:06 Rev Time 0.00
Received By medwards Date 2022-03-28 Time 08:06 Sent To  
Notes
2022-03-28 08:07:14THE KITCHEN HOOD EXHAUST FANS WILL BE ADDRESSED WHEN
 THE HOOD REVIEW IS COMPLETED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-18 Cont ID  
Sent By medwards Date 2022-01-18 Time 15:14 Rev Time 0.00
Received By medwards Date 2022-01-18 Time 15:14 Sent To  
Notes
2022-01-18 15:14:191ST REVIEW FBC-2020 MECHANICAL
 PERMIT- 21121052
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE TO THE MECHANICAL DRAWINGS STATING
 THAT THE KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT
 APPLICATION AND REVIEW AS THEY WILL NOT BE REVIEWED
 UNDER THIS PERMIT.
  
 2) PLEASE ADDA NOTE TO THE MECHANICAL DRAWINGS STATING
 THAT THE REFRIGERATION EQUIPMENT WILL REQUIRE A
 SEPARATE PERMIT APPLICATION AND REVIEW AS THEY WILL NOT
 BE REVIEWED UNDER THIS PERMIT.
  
 3) PLEASE SHOW THAT THE IN LINE GREASE DUCT EXHAUST
 FANS WILL MEET THE RATING REQUIREMENTS OF FBC M
 506.5.1.2
  
 4) PLEASE SHOW HOW THE PENETRATIONS IN THE RATED
 SEPARATION WALLS WILL BE PROTECTED WHERE ALL DUCTS
 PENETRATE THE RATED WALLS. FBC M 607
  
 5) SHEET P4.1: I DO NOT SEE ANY PIZZA OVENS ON THE
 EQUIPMENT SCHEDULE. PLEASE EXPLAIN WHAT WILL BE USED.
 FBC 107.2.1
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-05-12 Cont ID  
Sent By ccole Date 2022-05-12 Time 17:04 Rev Time 0.00
Received By ccole Date 2022-05-12 Time 15:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-04-14 Cont ID  
Sent By ccole Date 2022-04-14 Time 12:07 Rev Time 0.00
Received By ccole Date 2022-04-14 Time 10:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-15 Cont ID  
Sent By ccole Date 2022-03-15 Time 13:07 Rev Time 0.00
Received By ccole Date 2022-03-14 Time 16:27 Sent To  
Notes
2022-03-15 13:14:002ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21121052
 3/15/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE COMMENTS BELOW ARE
 BASED ON THE RE-SUBMITTED PLANS AND RESPONSE NARRATIVE
  
 1) SHEETS P1.1 & P1.2: AS DISCUSSED IN PHONE CALL WITH
 RGD ENGINEERS, THE DRAINAGE FROM THE GLASS WASHERS IN
 THE BAR AREAS SHALL DISCHARGE INTO THE GREASE WASTE
 LINE. FOR CLARIFICATION: FOOD AND BEVERAGE SERVICE
 SINKS INCLUDING 1, 2, OR 3-COMPARTMENT SINKS,
 DISHWASHERS AND GLASS WASHERS SHALL DRAIN INTO THE
 GREASE WASTE LINE- SEE SEC. 1003.3.1 FBC P. DRAINAGE
 FROM ICE MAKERS, ICE BINS, AND HAND SINKS SHALL DRAIN
 INTO THE SANITARY SYSTEM- SEC. 1003.3.1 FBC P.
  
 2) P1.1 & P1.2: THE REVISED PLAN SHOWS A GREASE WASTE
 DRAIN LINE FROM FLOOR SINKS BELOW ICE CHEST 134 AND
 DRIP PAN 205 CONNECTING TO THE SANITARY. DOES THE
 DRAINAGE FROM THE DRIP PAN CONTAIN FATS, OIL, OR GREASE
 OR IS THE LINE MISLABLED- SEC. 1003.3.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-24 Cont ID  
Sent By ccole Date 2022-01-24 Time 17:37 Rev Time 0.00
Received By ccole Date 2022-01-24 Time 10:48 Sent To  
Notes
2022-01-24 17:38:351ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21121052
 1/24/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A9.01 DETAILS 6 & 10: LABEL THE 3'4"
 MEASUREMENT FROM THE FINISHED FLOOR TO THE REFLECTIVE
 SURFACE OF THE MIRROR- SEC. 603.3 WPB.
  
 2) A9.01 DETAILS 1, 3, 7, & 8: SHOW THE KNEE AND TOE
 CLEARANCE MEASUREMENTS FOR THE LAVATORIES IN THE
 DETAILS- SEC. 606.2 & FIGURES 306.2 & 306.3 FBC ACC.
  
 3) P1.1: REMOVE THE BAR PLAN OVERLAY BLOCKING OUT THE
 UNDER-SLAB PIPING RUNS- SEC. 107.2.1 WPB.
  
 4) P1.1, P1.2, & P4.1: THERE ARE NUMEROUS HANDSINKS AND
 FLOOR SINKS BELOW ICE MAKERS, BINS, GLASS WASHERS ETC.
 SHOWN DRAINING INTO THE GREASE WASTE LINE. REFER TO
 SEC. 1003.3.1 FBC P AND ROUT THE DRAINAGE FROM THOSE
 FIXTURES TO THE SANITARY SYSTEM- SEC. 1003.3.1 FBC P.
 THE LIST INCLUDES, BUT IS NOT LIMITED TO ITEMS 44, 45,
 49, 66, 67, 68, 69, 103, 107, 108, 109, 134, & 135.
 PLEASE NOTE THAT ONLY FIXTURES DISCHARGING FATS, OILS,
 OR GREASE SHALL DRAIN INTO THE GREASE WASTE DISPOSAL
 SYSTEM.
  
 5) ) P1.1, P1.2: SHOW THE GREASE WASTE LINE
 CONTINUATIONS TO THE GREASE INTERCEPTOR LOCATIONS AND
 INDICATE NEW OR EXISTING INTERCEPTORS- SECS. 107.2.1
 WPB. REFER TO SECS. 1003.3- 1003.3.8 FBC P AND PROVIDE:
 A) GREASE WASTE CALCULATIONS. B) EQUIPMENT SCHEDULES
 INDICATING MAKES, MODELS AND CAPACITIES. C) GREASE
 WASTE PIPING LAYOUT SHOWING PIPING RUNS AND SIZES,
 LOCATIONS OF CLEANOUTS, VENTS, AND SAMPLING PORTS.
 PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE GREASE INTERCEPTOR(S) AND THIS IS A
 PRELIMINARY REVIEW FOR COMPLIANCE. A COMPLETE SET OF
 PLANS, DETAILS, AND SPECIFICATIONS ARE REQUIRED FOR
 REVIEW UNDER THE SEPARATE PERMIT.
  
 6) P1.1 & P1.3: PLACE TARGET NOTES AT THE GREASE WASTE
 PIPE CONTINUATIONS TO INDICATE WHERE THE PIPING IS
 RUNNING TO- SEC. 107.2.1 WPB.
  
 7) P1.1 & P1.3: THE PLAN APPEARS TO SHOW THE FOLLOWING
 LIST OF FLOOR DRAINS AND FLOOR SINKS THAT ARE MISSING
 VENTS OR HAVE TRAPS THAT EXCEED THE MAXIMUM DISTANCE
 FROM TRAP TO VENT- SEE TABLE 909.1 & SEC. 915.1 FBC P-
 EFD-1 IN FEATURE BAR, FS-1 AT ITEM 103, EFD-1 IN PIZZA
 KITCHEN, FS-1 IN MAIN KITCHEN BY ITEM 92, EFD-1 IN MAIN
 KITCHEN, FS-1 BY ITEM 116.
  
 8) P1.1 & P1.3: PROVIDE TRAP SEAL PROTECTION FOR THE
 EFD'S- SEC.1002.4.1 FBC P. PLEASE NOTE THAT
 BARRIER-TYPE SEAL PROTECTION DEVICES ARE NOT APPROVED
 BY THE WPB BUILDING DEPT. FOR USE IN COMMERCIAL
 KITCHENS.
  
 9) P2.1, P2.2, P2.3: SHOW THE MAIN COLD WATER SUPPLY
 LINE INTO THE SPACE AND LOCATION SOF MAIN SHUTOFF VALVE
 AND WATER METER- SECS. 604.3 & 606.1 FBC P.
  
 10) P2.1, P2.2, P2.3, & P4.2: SHOW THE WHA-A & WHA-B
 LOCATIONS- SEC. 604.9 FBC P.
  
 11) P2.3: SHOW THE PIPE RISER CONTINUATIONS INTO THE
 MEZZANINE AND LOCATIONS OF SHUTOFF VALVES FOR DOWN
 FEEDING PIPES- SEC. 606.1 FBC P.
  
 12) P4.2: PLEASE ADD THE FLOOR DRAINS, FLOOR SINKS, AND
 TROUGH DRAINS TO THE PLUMBING FIXTURE SCHEDULE- SECS.
 412 & 413 FBC P.
  
 13) P4.2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 BACKFLOW PREVENTERS- SEC. 608.3 FBC P.
  
 14) P4.3: THE WATER HEATER PIPING DIAGRAM DOES NOT SHOW
 THE HWR LINE CONNECTING TO THE COLD COLD WATER INLET
 PIPE OF THE WATER HEATER AND THE COLD WATER INLET PIPE
 OR THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC
 MIXING VALVE- SEC.607.2.2 WPB.
  
 15) P2.2 & P4.3: SHOW THE WATER HEATER PAN DRAIN LINE
 RUNS AND DISCHARGE LOCATIONS- SEC. 504.7.2 FBC P.
  
 16) P4.2: PROVIDE A SLAB REPAIR DETAIL- SEC. 107.2.1
 WPB.
  
 17) P4.3: REFER TO TABLE C403.2.10 FBC EC. AND PROVIDE
 HOT WATER PIPE INSULATION SPECIFICATIONS.
  
 18) P4.2: DEFERRED SUBMITTALS- PROVIDE A LIST OF
 DEFERRED SUBMITTALS ON THE PLAN- SEC. 107.4.1 WPB. THE
 LIST SHALL INCLUDE ALL FIXTURES, DEVICES, APPLIANCES
 AND EQUIPMENT THAT DO NOT HAVE MAKES AND MODELS
 SPECIFIED ON THE PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-04-01 Cont ID  
Sent By rgathrig Date 2022-04-01 Time 10:13 Rev Time 0.00
Received By rgathrig Date 2022-04-01 Time 10:12 Sent To  
Notes
2022-04-01 10:14:08PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
 TEW & TAYLOR
  
 RICHARD GATHRIGHT
 561-805-6679

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-05-12 Cont ID  
Sent By ccole Date 2022-05-12 Time 17:11 Rev Time 0.00
Received By ccole Date 2022-05-12 Time 17:04 Sent To  
Notes
2022-05-12 16:07:38MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-27 Cont ID  
Sent By rmcphers Date 2022-04-27 Time 10:13 Rev Time 0.00
Received By rmcphers Date 2022-04-27 Time 10:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-23 Cont ID  
Sent By rmcphers Date 2022-03-23 Time 09:41 Rev Time 0.00
Received By rmcphers Date 2022-03-23 Time 09:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-02-09 Cont ID  
Sent By rmcphers Date 2022-02-09 Time 13:06 Rev Time 0.00
Received By rmcphers Date 2022-02-09 Time 13:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-03-11 Cont ID  
Sent By ckimmerl Date 2022-03-11 Time 11:41 Rev Time 0.00
Received By ckimmerl Date 2022-03-11 Time 11:41 Sent To  
Notes
2022-03-11 11:41:44PROVISO: OUTDOOR PERGOLA NOT INCLUDED.

Review Stop Z ZONING
Rev No 1 Status P Date 2022-01-20 Cont ID  
Sent By aaponte Date 2022-01-20 Time 16:47 Rev Time 0.00
Received By aaponte Date 2022-01-20 Time 16:47 Sent To  
Notes
2022-01-20 16:47:39PROVISO: OUTDOOR PERGOLA NOT INCLUDED.