Plan Review Details - Permit 21121037
Plan Review Stops For Permit 21121037
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-01-10 Cont ID  
Sent By cpuell Date 2022-01-10 Time 08:35 Rev Time 0.00
Received By cpuell Date 2022-01-10 Time 08:35 Sent To  
Notes
2022-01-10 08:37:03PRIMARY CHANGED TO 237 WALTON BLVD FROM 239 WALTON BLVD
 WHICH IS THE DOWNSTAIRS UNITS, UPSTAIRS UNIT CHANGED
 FROM 239 1/2 WALTON BLVD TO 239 WALTON BLVD

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-01-07 Cont ID  
Sent By cpuell Date 2022-01-07 Time 14:13 Rev Time 0.00
Received By cpuell Date 2022-01-07 Time 14:12 Sent To  
Notes
2022-01-07 14:14:08IS THE BACKFLOW FOR THE NORTH EAST OR NORTH WEST
 BUILDING? THE NORTH WEST BUILDING HAS A HALF ADDRESS
 WHICH WILL NEED TO BE READDRESSED. PLEASE HAVE THE
 OWNER CONTACT [email protected] OR CALL 561-805-6659 TO
 READDRESS THE HALF ADDRESS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-19 Cont ID  
Sent By lmarchan Date 2022-01-19 Time 11:34 Rev Time 0.00
Received By lmarchan Date 2022-01-10 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-07 Cont ID  
Sent By cpuell Date 2022-01-07 Time 14:14 Rev Time 0.00
Received By cpuell Date 2022-01-06 Time 08:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-11 Cont ID  
Sent By lcrespo Date 2022-01-11 Time 06:44 Rev Time 0.00
Received By lcrespo Date 2022-01-11 Time 06:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-07 Cont ID  
Sent By ccole Date 2022-01-07 Time 07:47 Rev Time 0.00
Received By ccole Date 2022-01-07 Time 07:35 Sent To  
Notes
2022-01-07 07:48:081ST REVIEW FBC-2020 PLUMBING
 PERMIT-21121037
 1/7/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 BACKFLOW PREVENTER INDICATING THE MAKE, MODEL, AND SIZE
 OF THE DEVICE. THE DOCUMENTATION SHALL INDICATE THE
 DEVICE IS LEAD FREE AND IS ON THE APPROVED DEVICE LIST
 PUBLISHED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA
 (USC). PLEASE CONTACT DEPARTMENT OF PUBLIC UTILITY
 FIELD CUSTOMER SERVICE AT 561-822-2240 FOR DOCUMENTED
 CONFIRMATION THAT THE PROPOSED BACKFLOW PREVENTION
 DEVICE COMPLIES WITH CITY REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PU PUBLIC UTILITIES
Rev No 2 Status P Date 2022-01-19 Cont ID  
Sent By lmarchan Date 2022-01-19 Time 11:33 Rev Time 0.00
Received By lmarchan Date 2022-01-19 Time 11:33 Sent To  
Notes
2022-01-19 11:34:13NOTE FROM DGRIFFITHS - THE LOCATION FOR THE BACKFLOW
 INSTALLATION, IS MARKED IN BLUE PAINT IN LINE WITH THE
 METER, 2 FEET AFTER THE SIDE WALK ON THE CUSTOMER
 PROPERTY.

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date 2022-01-07 Cont ID  
Sent By ccole Date 2022-01-07 Time 08:57 Rev Time 0.00
Received By ccole Date 2022-01-07 Time 08:57 Sent To  
Notes
2022-01-07 08:57:53SEE PLUMBING COMMENTS.