| Plan Review Stops For Permit 21121009 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-07-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-07-01 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-07-01 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2023-07-01 08:56:17 | APPROVAL OF BUILDING REVIEW IS PENDING APPROVAL OF | | | ELEVATION CERTIFICATE.PLEASE SEE COMMENTS UNDER THE 3RD | | | NFIP REVIEW. CT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-02 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-01 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2023-05-02 14:24:15 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | | | | 1. CORRECTED. | | | | | | 2. THE PREVIOUSLY APPROVED ELEVATION CERTIFICATE SHOWS | | | THE GARAGE IS 693 SF. PLAN PAGE A-0.1 SHOWS THE GARAGE | | | IS 693 SF. PLAN PAGE A-1.1 SHOWS THE GARAGE IS 685 SF. | | | PLEASE CORRECT PG A-1.1. (NOT CORRECTED) | | | | | | 3. CORRECTED. | | | | | | NEW COMMENTS: | | | | | | 4. FLOOD OPENINGS ON FLOOR PLAN A-1.1 ARE IDENTIFIED BY | | | A LEGEND KEY OF "O" . NO SCHEDULE OF OPENINGS IS | | | PROVIDED. THIS IS NOT AN ACCEPTABLE WAY TO IDENTIFY THE | | | FLOOD VENTS. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | 5. IDENTIFY THE FLOOD OPENINGS (SMART VENTS) ON FLOOR | | | PLAN A-1.1 WITH THE PRODUCT APPROVAL NUMBER, MODEL | | | NUMBER AND COVERAGE AREA NEXT TO EACH | | | OPENING.FL5822-R8, MODEL 1540-520, COVERAGE 200SF. | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-04 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-04 |
Time |
05:57 |
Sent To |
|
|
| Notes |
| 2022-03-04 12:43:51 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. REFERENCE PLAN PAGES C-1 AND A.01 FOR THE FOLLWING | | | COMMENT: | | | THE GARAGE FLOOR ELEVATION IS AT 6.0' NAVD (CENTER OF | | | ROOM). THERE IS A REQUIRED 1/4" SLOPE. ADDING THE | | | STANDARD 1 1/2" RECESS FOR THE OHD, THE GARAGE FLOOR | | | WILL BE AT APPROX. 3 1/2" TO 4' BELOW THE DRIVEWAY | | | GRADE OF 6.0'NAVD. | | | | | | 2. THE PREVIOUSLY APPROVED ELEVATION CERTIFICATE SHOWS | | | THE GARAGE IS 693 SF. PLAN PAGE A-0.1 SHOWS THE GARAGE | | | IS 693 SF. PLAN PAGE A-1.1 SHOWS THE GARAGE IS 685 SF. | | | PLEASE CORRECT PG A-1.1. | | | | | | 3. PROVIDE THE FLORIDA PRODUCT APPROVALS AND THE ICC-ES | | | REPORT FOR THE PROPOSED SMART VENTS (MODEL 1540-51). | | | APPROVED UNDER THE 2020 FBC, | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-07-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-07-01 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-06-01 |
Time |
08:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-02 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-04-07 |
Time |
15:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-04 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-03 |
Time |
12:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2023-07-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-07-01 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-07-01 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2023-07-01 09:41:39 | NFIP PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 | | | | | | 3RD REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTICE: THIS SUBMITTAL IS A REVISION TO THE | | | CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC) UNDER | | | MASTER PERMIT 21061605. | | | | | | 1. LINE C1 STATES THIS IS A FINISHED CONSTRUCTION EC. | | | PLEASE CLARIFY? | | | 2. LINE C2B) STATES N/A. ENTER ELEVATION OF NEXT | | | HIGHEST FLOOR. | | | 3. LINE C2C) STATES 20.0'. THIS PROPERTY IS NOT LOCATED | | | IN A V ZONE. ENTER N/A. | | | 4. LINE A9A) STATES GARAGE IS 685 SQUARE FEET (SF). THE | | | APPROVED CONSTRUCTION DRAWING EC, PLAN PAGES A-1.0 AND | | | A-1.1 STATE GARAGE IS 693 SF. PLEASE CLARIFY? | | | | | | 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE | | | WITH SECTIONS107.2.1 THROUGH 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-02 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-01 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2023-05-02 14:26:06 | NFIP PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. LINE A8 A), B) & C) CHANGE ENTRIES TO N/A PER EC | | | INSTRUCTIONS. | | | 2. LINE A9A) ENTER THE SF OF THE GARAGE. | | | 3. LINE A9B) ENTER NUMBER OF FLOOD OPENINGS. | | | 4.LINE A9C) ENTER TOTAL NET AREA OF ALL VENTS COMBINED. | | | THIS SHALL BE PREPARED BY A DESIGN PROFESSIONAL PER | | | FEMA TECHNICAL BULLITEN # 1 SECTION 9.3.5 (PG. 39). | | | 5.LINE A9D) CHANGE ENGINEERED FLOOD OPENINS TO YES. | | | 6. LINE B8 FLOOD ZONE IS AE | | | 7. LINE C2B) ENTER ELEVATION OF 2ND FLOOR. | | | 8. SECTION D COMMENTS CHANGE MACHINERY TO :EQUIPMENT | | | AND LOCATION PER C2E): ,,, | | | 9. NO PHOTOS ARE REQUIRED AT CONSTRUCTION DRAWING EC. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-04 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-04 |
Time |
05:57 |
Sent To |
|
|
| Notes |
| 2022-03-04 12:15:59 | NFIP PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | CITY ORDINANCE NO. 4658-16 AND NO. 4729-17 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A CORRECTEED CONSTRUCTION DRAWING ELEVATION | | | CERTIFICATE. | | | FEMA NFIP | | | | | | 2. PROVIDE A CORRECTED SURVEY. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 3. PROVIDE THE FLORIDA PRODUCT APPROVALS AND THE ICC-ES | | | REPORT FOR THE PROPOSED SMART VENTS (MODEL 1540-51). | | | APPROVED UNDER THE 2020 FBC, | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-07-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-07-01 |
Time |
08:56 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-07-01 |
Time |
07:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2023-05-02 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2023-05-02 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2023-05-01 |
Time |
07:44 |
Sent To |
|
|
| Notes |
| 2023-05-02 14:15:31 | 2ND SIGNATURE REVIEW | | | RESULTS: CORRECTIONS NEEDED | | | | | | CHRISTOPHER S. THROOP, CBO, BN, PX, CFM | | | PLANS EXAMINER II | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: | | | | | | NOTICE: PLAN PAGE A-5.2 | | | | | | 1.DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED ELECTRONICALLY FOR PUBLIC RECORD SHALL HAVE A | | | VALID DIGITAL SIGNATURE. | | | A SCAN OF A WET SEAL AND SIGNATURE OR DIGITAL SIGNATURE | | | IS NOT CONSIDERED A VALID DIGITAL SIGNATURE. | | | | | | 2.SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE PER F.S. | | | 668.003 (3); | | | FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | | SECTION 107.3.5). | | | F.S. 471; F.A.C. 61G15-23.005 (ENGINEERS) | | | F.S. 481; F.A.C. 61G1-16.005 (ARCHITECTS) | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-03-04 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-03-04 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-03-04 |
Time |
05:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-06-12 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-06-12 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-06-12 |
Time |
11:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2023-04-17 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2023-04-17 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2023-04-17 |
Time |
14:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-21 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-01-21 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-01-21 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2022-01-21 15:32:17 | FAILED: MEAUREMENT OF HEIGHT STARTS FROM THE FINISHED | | | FLOOR GRADE. |
|
|