Plan Review Details - Permit 21120971
Plan Review Stops For Permit 21120971
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-11 Cont ID  
Sent By jbrooks Date 2022-03-11 Time 14:34 Rev Time 0.00
Received By jbrooks Date 2022-03-11 Time 08:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-22 Cont ID  
Sent By jbrooks Date 2021-12-22 Time 08:52 Rev Time 0.00
Received By jbrooks Date 2021-12-22 Time 07:33 Sent To  
Notes
2021-12-22 08:52:33JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 150. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF SYSTEM TO BE
 USED. INCLUDE COVER PAGE, EVALUATION REPORTS AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 2. FBC B 107.2.1. CITY OF WEST PALM BEACH IS NOT
 LOCATED IN A HVHZ AND HAS NOT ADOPTED RAS 128. SUBMIT
 FASTENER DENSITY CALCULATIONS PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT, OR REGISTERED ROOF CONSULTANT.
 3. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL
 SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH
 NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS.
 PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT
 INDICATE ON ROOF DRAWING/SKETCH).
 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW
 ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF
 SLOPE(S), MEAN ROOF HEIGHT(S).
 5. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR
 THE EXISTING SECOND STORY WALLS.
 6. WPB A 109.3 BUILDING PERMIT VALUATIONS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES. VALUE TO INCLUDE LABOR AND
 MATERIALS, ARCHITECTURAL AND DESIGN FEES, OVERHEAD AND
 PROFIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-01-06 Cont ID  
Sent By amhamilt Date 2022-01-06 Time 13:43 Rev Time 0.00
Received By amhamilt Date 2022-01-06 Time 13:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-11 Cont ID  
Sent By jbrooks Date 2022-03-11 Time 14:34 Rev Time 0.00
Received By jbrooks Date 2022-03-07 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-07 Cont ID  
Sent By lmarchan Date 2022-01-07 Time 08:49 Rev Time 0.00
Received By lmarchan Date 2021-12-21 Time 08:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-03-08 Cont ID  
Sent By rmcphers Date 2022-03-08 Time 07:52 Rev Time 0.00
Received By rmcphers Date 2022-03-08 Time 07:52 Sent To  
Notes
2022-03-08 07:52:47ORIGINAL SIGNED AND SEALED DRAWINGS TO STORAGE