Plan Review Details - Permit 21120962
Plan Review Stops For Permit 21120962
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2023-05-02 Cont ID  
Sent By rwbrown Date 2023-05-02 Time 10:21 Rev Time 0.00
Received By rwbrown Date 2023-05-02 Time 10:21 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 10:53 Rev Time 0.00
Received By lcrespo Date 2021-12-27 Time 09:08 Sent To  
Notes
2021-12-27 10:54:1712/27/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. NOTE: THE CITY OF WEST PALM BEACH HAS NO RECORD OF
 EXISTING GAS PERMITS WITH INSPECTIONS OF THE CURRENT
 SYSTEM OF A TANKLESS. A COMPLETE EVALUATION OF ALL GAS
 SYSTEMS AND EQUIPMENT WILL BE DONE AT THIS STAGE, AND
 IF NOT TO CODE, IT MAY NEED TO BE BOUT UP TO CODE
 COMPLIANCE AT THE OWNER?S EXPENSE. PLEASE INCLUDE THE
 CURRENT AND NEW GAS SYSTEM OF AN ISOMETRIC DRAWING AND
 EQUIPMENT IN THIS PERMIT FOR THIS SCOPE OF WORK PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1. SOME OF THE ITEMS
 BELOW MAY BE NEEDED FOR REVIEW!
  
 2. WOULD YOU PLEASE SHOW THE ISOMETRIC DRAWING THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC RES.
 SECS. G2413.4.1, G2413.4.2.
  
 3. WOULD YOU PLEASE SHOW THE CORRESPONDING EHD NUMBER
 OF THE CORRUGATED STAINLESS STEEL TUBING PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. WOULD YOU PLEASE PROVIDE WHAT TYPE OF GAS (LP OR
 NATURAL) IS BEING USED PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. THE TANKLESS UNIT CALL FOR A 10.5? WATER COLUMN, AND
 THE SERVICE METER DISCHARGES IS A 12? WATER COLUMN
 REQUIRING A REGULATOR FOR THIS UNIT AS PER THE
 MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES.
 SEC. G2421.1.
  
 6. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT
 OF REGULATOR 1? OF EITHER SIDE PER THE 2020 FBC RES.
 SEC G2421.2.
  
 7. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON
 GAS ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC
 RES. SEC. G2420.5.
  
 8. WOULD YOU PLEASE SHOW DRIP LEG ON TANKLESS PER THE
 2020 FBC RES. SEC. G2419.2.
  
 9. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 10. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. WOULD YOU PLEASE NOTE ON PLANS?
  
 11. CONDENSATE FOR TANKLESS NEEDS TO BE 1' AWAY FROM
 THE STRUCTURE PER THE 2020 FBC SEC. R318.5.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 10:54 Rev Time 0.00
Received By lcrespo Date 2021-12-21 Time 13:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 10:54 Rev Time 0.00
Received By lcrespo Date 2021-12-27 Time 10:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By lcrespo Date 2021-12-27 Time 10:54 Rev Time 0.00
Received By lcrespo Date 2021-12-27 Time 10:54 Sent To  
Notes
***NONE***