| 2022-11-29 13:28:59 | 1. PLEASE CLARIFY THE FINAL HEIGHT OF THE PROPOSED |
| | WIRELESS FACILITIES POLE AND IDENTIFY THE REFERENCED |
| | POLE FOR COMPATIBLE HEIGHT WITHIN THE SAME ROW. |
| | |
| | SPECIFIC PURPOSE SURVEY SIGNED BY THOMAS CLANCY ON |
| | 11/10/19 STATES A NEW STANDALONE 30??? HEIGHT POLE, |
| | WITH TOP ELEVATION AT 33???. THE REFERENCED POLE FOR |
| | COMPATIBLE HEIGHT IS 26???. THE PROPOSED WIRELESS |
| | FACILITIES POLE MUST BE LESS THAN OR EQUAL TO THE |
| | HEIGHT OF THE REFERENCED POLE ALONG THE SAME PORTION OF |
| | ROW. PLEASE ADJUST TOTAL WCF POLE HEIGHT TO BE AT OR |
| | LESS THAN 26???. |
| | |
| | |
| | SPECIFIC PURPOSE SURVEY SIGNED BY THOMAS CLANCY ON |
| | 1/28/22 STATES THE NEW STANDALONE POLE IS AT 25??? IN |
| | HEIGHT, WITH A TOP ELEVATION AT 28???. THE REFERENCED |
| | POLE FOR COMPATIBLE HEIGHT IS 26???. THE PROPOSED |
| | WIRELESS FACILITIES POLE MUST BE LESS THAN OR EQUAL TO |
| | THE HEIGHT OF THE REFERENCED POLE ALONG THE SAME |
| | PORTION OF ROW. PLEASE ADJUST TOTAL WCF POLE HEIGHT TO |
| | BE AT OR LESS THAN 26???. |
| | |
| | THE PLAN VIEW SHEET FROM DRAFTPROS SUGGESTS 30??? |
| | HEIGHT POLES WITHIN THE ROW AS REFERENCE, AND A 30??? |
| | PROPOSED WCF POLE. |
| | |
| | NEW POLE ELEVATIONS AND PHOTO SIM SHEETS ALSO SUGGEST A |
| | 30??? PROPOSED POLE. |
| | |
| | |
| | 2. PLEASE PROVIDE PROPOSED UNDERGROUND POWER ROUTE FOR |
| | THE ELECTRICAL CONNECTION, WHERE IS POWER BEING DRAWN |
| | TO AND FROM? |
| | |
| | STAFF MUST CONFIRM THAT THE POWER SOURCE IS LOCATED |
| | WITHIN THE ROW OR WITHIN A GENERAL UTILITIES EASEMENT. |
| | |
| | PLEASE INCLUDE BORING/HANDHOLE LOCATIONS, UNDERGROUND |
| | BORING PROFILE, DEPTH OF LINES AND DIMENSIONAL RELATION |
| | TO ANY UNDERGROUND UTILITIES OR STREET TREES. ANY |
| | EXCAVATION WORK MUST MAINTAIN A MINIMUM OF 8??? |
| | CLEARANCE FROM STREET TREES. |
| | |
| | |
| | 3. PROPOSED POLE DESIGN SHALL MEET CITY STANDARDS FOR |
| | STEALTH DESIGN AND COLOR. RAYCAP INTEGRATED POLE - RAL |
| | 7044 (SILK GREY) OR EQUIVALENT. |
| | |
| | PHOTO SIM SHEETS REFERENCE LIGHT GREY, PLEASE MATCH RAL |
| | 7044 (SILK GREY). |
| | |
| | 4. OVERALL SITE PLAN AND SURVEY SHOULD PROVIDE FULL |
| | SCOPE OF PROJECT/WORK AREA. INCLUDING THE POWER RUN AND |
| | CONNECTIONS TO/FROM WCF POLE. |
| | |
| | |
| | CHRIS KIMMERLY, AICP |
| | URBAN DESIGN PLANNER |
| | 822-1426 [email protected] |