Plan Review Details - Permit 21120923
Plan Review Stops For Permit 21120923
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-19 Cont ID  
Sent By rmcphers Date 2022-07-19 Time 09:41 Rev Time 0.00
Received By rmcphers Date 2022-07-19 Time 09:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-22 Cont ID  
Sent By rmcphers Date 2022-03-22 Time 11:04 Rev Time 0.00
Received By rmcphers Date 2022-03-22 Time 11:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-02 Cont ID  
Sent By rmcphers Date 2022-03-02 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2022-03-02 Time 14:47 Sent To  
Notes
2022-03-02 15:10:52OUTDOOR COOLER
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THE
 COOLER, THE DISTANCE FROM PROPERTY LINES, THE FLOOD
 ZONE PER THE LATEST FIRM. FBC 107.2.5
  
 2) WIND DESIGN DATA ON THE DRAWINGS AND CALCULATIONS
 SHOWS RISK CATEGORY II WITH WIND SPEED OF 169MPH - THE
 WIND SPEED FOR A RISK CATEGORY II IS 170MPH - PER FBC
 WPB SECTION 120
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2022-01-12 Cont ID  
Sent By fgiaquin Date 2022-01-12 Time 21:15 Rev Time 0.00
Received By fgiaquin Date 2022-01-12 Time 20:42 Sent To  
Notes
2022-01-12 21:14:57NO ELEC WORK REVIEWED OR APPROVED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-07-14 Cont ID  
Sent By   Date 2022-07-14 Time   Rev Time 0.00
Received By bdolan Date 2022-07-14 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-21 Cont ID  
Sent By pleduc Date 2022-03-21 Time   Rev Time 0.00
Received By pleduc Date 2022-03-21 Time 10:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-12-22 Cont ID  
Sent By pleduc Date 2021-12-22 Time   Rev Time 0.00
Received By pleduc Date 2021-12-22 Time 09:57 Sent To  
Notes
2021-12-22 10:09:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF WHERE THIS PROPOSED
 WALK-IN COOLER IS LOCATED WITHIN THE PROPERTY.
  
 PLEASE PROVIDE A SITE PLAN INDICATING THE SPECIFIC
 LOCATION INCLUDING DIMENSIONS TO OTHER
 BUILDINGS/PROPERTY LINES/SIDEWALKS, STEPUPS/STEPDOWNS
 AT GRADE, ETC.
  
  
  
 2) THERE IS NO INDICATION OF LIGHTING/ELECTRIC TO NOR
 WITHIN THE WALK-IN COOLER.
  
 ELECTICAL WORK SHALL COMPLY WITH NFPA 70, NEC 2017 ED.
  
 PLEASE PROVIDE ELECTICAL DETAILS, INCLUDING HOW AND
 WHERE THE POWER COMES FROM.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-19 Cont ID  
Sent By rmcphers Date 2022-07-19 Time 09:41 Rev Time 0.00
Received By rmcphers Date 2022-07-12 Time 07:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-09 Cont ID  
Sent By lmarchan Date 2022-05-09 Time 11:32 Rev Time 0.00
Received By lmarchan Date 2022-03-20 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-02 Cont ID  
Sent By rmcphers Date 2022-03-02 Time 15:23 Rev Time 0.00
Received By rmcphers Date 2021-12-20 Time 16:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-07-13 Cont ID  
Sent By medwards Date 2022-07-13 Time 14:29 Rev Time 0.00
Received By medwards Date 2022-07-13 Time 14:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-03-23 Cont ID  
Sent By medwards Date 2022-03-23 Time 14:58 Rev Time 0.00
Received By medwards Date 2022-03-23 Time 14:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By medwards Date 2021-12-21 Time 08:08 Rev Time 0.00
Received By medwards Date 2021-12-21 Time 08:08 Sent To  
Notes
2021-12-21 08:10:05PLEASE PROVIDE A SURVEY SHOWING THE LOCATION OF THIS
 NEW WALK IN FREEZER.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-13 Cont ID  
Sent By medwards Date 2022-07-13 Time 14:29 Rev Time 0.00
Received By medwards Date 2022-07-13 Time 14:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-03-22 Cont ID  
Sent By rmcphers Date 2022-03-22 Time 11:15 Rev Time 0.00
Received By rmcphers Date 2022-03-22 Time 11:15 Sent To  
Notes
2022-03-22 11:16:16SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL OF THE PROVIDED DRAWINGS DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-02 Cont ID  
Sent By rmcphers Date 2022-03-02 Time 15:22 Rev Time 0.00
Received By rmcphers Date 2022-03-02 Time 15:22 Sent To  
Notes
2022-03-02 15:23:45SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL OF THE PROVIDED DRAWINGS DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-21 Cont ID  
Sent By jroach Date 2022-06-21 Time 07:53 Rev Time 0.00
Received By jroach Date 2022-06-21 Time 07:53 Sent To  
Notes
2022-06-21 07:53:40BEFORE COMMENCING THE IMPROVEMENTS, THE ZOO SHALL
 PROVIDE THE CITY?S RISK MANAGER WITH CERTIFICATES OF
 INSURANCE EVIDENCING THAT ANY CONTRACTOR(S) PERFORMING
 THE IMPROVEMENTS CARRIES COMMERCIAL GENERAL LIABILITY
 INSURANCE (INCLUDING, WITHOUT LIMITATION, CONTRACTOR?S
 LIABILITY COVERAGE), WRITTEN ON AN OCCURRENCE BASIS
 WITH A MINIMUM COMBINED SINGLE LIMIT OF $2,000,000,
 ALONG WITH WORKERS COMPENSATION INSURANCE AS REQUIRED
 BY LAW, AND INCLUDING THE CITY OF WEST PALM BEACH AS AN
 ADDITIONAL INSURED.
 ________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 TTY: 800.955.8771
 E: [email protected]
  
 W: WPB.ORG
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By jroach Date 2022-05-09 Time 10:47 Rev Time 0.00
Received By jroach Date 2022-05-09 Time 10:44 Sent To  
Notes
2022-05-09 10:47:51ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.09.2022
 PERMIT NO.: 21120923
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO THE LEASE AGREEMENT BETWEEN THE PALM
 BEACH ZOO AND THE CITY OF WEST PALM BEACH, INDIVIDUAL
 STRUCTURES OR IMPROVEMENTS IN EXCESS OF $5000 ARE TO BE
 SUBMITTED TO THE CITY COMMISSION FOR PRIOR APPROVAL AS
 SUCH IMPROVEMENTS WOULD OCCUR ON CITY-OWNED PROPERTY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved