Plan Review Details - Permit 21120917
Plan Review Stops For Permit 21120917
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 16:26 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 16:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 15:14 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 15:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By rmcphers Date 2022-01-13 Time 16:03 Rev Time 0.00
Received By rmcphers Date 2022-01-13 Time 16:03 Sent To  
Notes
2022-01-13 16:08:28ANTENNA
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE ROOF TOP CABINET ATTACHMENT TO THE
 EXISTING ROOF TOP PLATFORM.
  
 2) THERE IS A GENERATOR DOCUMENT ADDED TO PROJECTDOX -
 THE DRAWINGS SHOW NO CHANGES TO THE EXISTING GENERATOR
 - PLEASE CLARIFY.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-08-05 Cont ID  
Sent By mpeterso Date 2022-08-05 Time 15:17 Rev Time 0.00
Received By mpeterso Date 2022-08-05 Time 15:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-06-13 Cont ID  
Sent By mpeterso Date 2022-06-13 Time 14:56 Rev Time 0.00
Received By mpeterso Date 2022-06-13 Time 14:56 Sent To  
Notes
2022-06-13 14:57:481) COMMENT #1 FROM PREVIOUS REVIEW NOT COMPLETELY
 ADDRESSED. THE PRIMARY 100 AMP DISCONNECT FEEDING THE
 50KVA TRANSFORMER IS BEING FED FROM A 150- AMP SOURCE.
 THE RATING OF THIS DISCONNECT REQUIRES A RATING EQUAL
 TO THE SOURCE CURRENT AND VOLTAGE RATING. NEC 110.9
 2) PLEASE PROVIDE CLARITY ON WHICH REQUIREMENTS OF NEC
 240.21 THE SECONDARY CONDUCTORS OF THE 50 KVA
 TRANSFORMER MEET. IT APPEARS THESE CONDUCTORS DETAILED
 DO NOT TERMINATE IN A SINGLE CIRCUIT BREAKER OR THEY
 EXTEND BEYOND THE FIRST DISCONNECTING MEANS.
 3) COMMENT #5 HAS NOT BEEN ADDRESSED. PLEASE PROVIDE
 AVAILABLE SHORT CIRCUIT CALCULATION STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS AT EQUIPMENT TO
 CONFIRM THE STATED AIC RATING OF THE EQUIPMENT AND
 SPD'S IS ADEQUATE. NEC 110.9, 110.10 AND 265.7
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-05-06 Cont ID  
Sent By mpeterso Date 2022-05-06 Time 14:20 Rev Time 0.00
Received By mpeterso Date 2022-05-06 Time 14:20 Sent To  
Notes
2022-05-06 14:55:14ELECTRIC REVIEW FAILED
 1) PLEASE LOCATE ALL EQUIPMENT ON A SITE PLAN. FBC
 107.2
 2) IT APPEARS THE PRIMARY SIDE DISCONNECT FEEDING THE
 50 KVA TRANSFORMER IS UNFUSED AND THE INCORRECT RATING.
 NEC 110.9, 215.3(A) AND 450.3(B)(1)
 3) IT APPEARS THE SECONDARY OF THE 50 KVA TRANSFORMER
 IS FEEDING AN ATS WITH NO OVERCURRENT PROTECTION AND IS
 THE INCORRECT RATING. NEC 110.9, 215.3 (A) AND
 408.36(B)
 4) PLEASE DETAIL PANELBOARD (A) RATINGS AND OVERCURRENT
 PROTECTION FOR BRANCH CIRCUITS.NEC 215.5 AND 240
 5) PLEASE PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS AT
 EQUIPMENT TO CONFIRM THE STATED AIC RATING OF THE
 EQUIPMENT AND SPD'S IS ADEQUATE. NEC 110.9, 110.10 AND
 265.7
 6) PLEASE PROVIDE RATINGS FOR ALL EQUIPMENT NEC 110 ,
 285 AND 408
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-21 Cont ID  
Sent By jleahy Date 2022-01-21 Time 10:48 Rev Time 0.00
Received By jleahy Date 2022-01-21 Time 10:45 Sent To  
Notes
2022-01-21 10:52:56ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLAN SHOWS GENERATOR IS THIS NEW OR EXISTING?
  
 2) PLAN SHOWS 5000 GALLON TANK IS THIS NEW OR EXITING?
  
 3) PLEASE CLARIFY 1 AND 2
  
 4) SUBMIT A SIGNED RISER DIAGRAM FOR SERVICE TO
 EQUIPMENT. 215.5
  
 5) SUBMIT A FAULT CURRENT CALCULATION FOR THE SERVICE
 PER 110.9, 110.10

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-07-27 Cont ID  
Sent By cwalker Date 2022-07-27 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-05-31 Cont ID  
Sent By cwalker Date 2022-05-31 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-18 Cont ID  
Sent By cwalker Date 2022-04-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-22 Cont ID  
Sent By cwalker Date 2021-12-22 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-05 Cont ID  
Sent By mpeterso Date 2022-08-05 Time 15:17 Rev Time 0.00
Received By mpeterso Date 2022-07-26 Time 16:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-13 Cont ID  
Sent By mpeterso Date 2022-06-13 Time 14:57 Rev Time 0.00
Received By mpeterso Date 2022-05-27 Time 11:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-06 Cont ID  
Sent By mpeterso Date 2022-05-06 Time 14:55 Rev Time 0.00
Received By mpeterso Date 2022-05-06 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-23 Cont ID  
Sent By lmarchan Date 2022-01-23 Time 07:54 Rev Time 0.00
Received By lmarchan Date 2021-12-21 Time 06:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 16:26 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 16:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-06 Cont ID  
Sent By rmcphers Date 2022-06-06 Time 15:15 Rev Time 0.00
Received By rmcphers Date 2022-06-06 Time 15:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 14:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-13 Cont ID  
Sent By rmcphers Date 2022-01-13 Time 16:11 Rev Time 0.00
Received By rmcphers Date 2022-01-13 Time 16:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2022-08-03 Cont ID  
Sent By ckimmerl Date 2022-08-03 Time 11:49 Rev Time 0.00
Received By ckimmerl Date 2022-08-03 Time 11:49 Sent To  
Notes
2022-08-03 11:49:50PROVISO: PROPOSED CABINET AND WIRELESS ANTENNA
 COMPONENTS SHALL BE PAINTED TO MATCH THE BUILDING.

Review Stop Z ZONING
Rev No 3 Status P Date 2022-06-09 Cont ID  
Sent By ckimmerl Date 2022-06-09 Time 11:42 Rev Time 0.00
Received By ckimmerl Date 2022-06-09 Time 11:42 Sent To  
Notes
2022-06-09 11:42:44PROVISO: PROPOSED CABINET AND WIRELESS ANTENNA
 COMPONENTS SHALL BE PAINTED TO MATCH THE BUILDING.

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-22 Cont ID  
Sent By ckimmerl Date 2022-04-22 Time 10:40 Rev Time 0.00
Received By ckimmerl Date 2022-04-22 Time 10:39 Sent To  
Notes
2022-04-22 10:40:10PROVISO: PROPOSED CABINET AND WIRELESS ANTENNA
 COMPONENTS SHALL BE PAINTED TO MATCH THE BUILDING.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By ckimmerl Date 2022-01-13 Time 12:26 Rev Time 0.00
Received By ckimmerl Date 2022-01-13 Time 12:25 Sent To  
Notes
2022-01-13 12:26:461. NEED TO SUBMIT FOR A CITY OF WEST PALM BEACH
 WIRELESS COMMUNICATIONS FACILITY APPLICATION TO THE
 PLANNING DIVISION.
  
 ZONING REVIEW IS DEPENDENT ON COMPLETION OF APPLICATION
 AND REVIEW FROM CITYSCAPE.