| Plan Review Stops For Permit 21120898 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-03-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-07 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-07 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-30 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-30 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2021-12-30 11:35:54 | REVISION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE APEARANCE OF WALL TILE HAS BEEN REMOVED FROM | | | DRAWING - A9.1.6 DETAIL 9 - PLEASE PROVIDE WALL FINISH | | | DETAIL FBC 1210.2.2 | | | | | | 2) THE APEARANCE OF WALL TILE HAS BEEN REMOVED FROM | | | DRAWING - A9.1.3 DETAIL 3 - PLEASE PROVIDE WALL FINISH | | | DETAIL FBC 1210.2.2 | | | | | | 3) THE APEARANCE OF WALL TILE HAS BEEN REMOVED FROM | | | DRAWING - A9.1.9 DETAIL 7 - PLEASE PROVIDE WALL FINISH | | | DETAIL FBC 1210.2.2 | | | | | | 4) DRAWING A1.1.1B - COOLER DOORS ENCROACH ON THE MEANS | | | OF EGRESS - PLEASE SHOW DIMENSIONS THAT COOLER DOORS | | | WILL COMPLY WITH FBC 1005.7.1 DOORS. | | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | | THAN ONE-HALF. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-01-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-01-24 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-24 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-12-27 |
|
|
Cont ID |
|
| Sent By |
bdolan |
Date |
2021-12-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
jcclark |
Date |
2021-12-27 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2021-12-27 12:04:33 | ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE | | | ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND | | | SHOP DRAWINGS BY CERTIFIED CONTRACTORS. | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | JOSEPH CLARK | | | OFFICE OF THE FIRE MARSHAL | | | 561-804-4748 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-03-02 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-03-02 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-01-05 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-01-05 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2022-01-05 09:35:25 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 21120898 | | | 1/5/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P7.05: PLEASE PROVIDE A REVISED CIVIL PLAN | | | DRAWING SHOWING THE NEW GAS METER LOCATION AND POINT OF | | | CONNECTION OF THE NEW SERVICE LINE AND EXISTING LINE | | | ONSITE- SEC. 401.1 FBC FG. | | | | | | 2) P7.05: PROVIDE VEHICLE IMPACT PROTECTION FOR THE GAS | | | METER- SEC. 303.4 FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-07 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-24 |
Time |
09:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-02-17 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-02-17 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-12-22 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2021-12-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-29 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-29 |
Time |
13:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-03-02 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-03-02 |
Time |
12:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-01-05 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-01-04 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2022-01-05 09:09:46 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21120898 | | | 1/5/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P1.1.1: PLEASE REVISE CIVIL PLANS C3.0 & C3.1 | | | TO SHOW THE CONNECTION POINT OF THE GOLF SHOP SANITARY | | | AND THE MAIN SEWER LINE- SEC. 701.2 FBC P. PLEASE NOTE | | | THAT A BACKWATER VALVE MAY BE REQUIRED- SEC. 714.1 FBC | | | P. | | | | | | 2) P1.1.0 & P7.0.1: VERIFY THAT THE AUTOMATIC WASHING | | | MACHINES WILL DISCHARGE BY GRAVITY INTO THE NEW DRAIN | | | TROUGH- SEC. 406.2 FBC P. | | | | | | 3) P7.03: PROVIDE SHUTOFF VALVES FOR THE WASHING | | | MACHINE SUPPLY LINES- SEC. 606.2 FBC P. | | | | | | 4) P7: PLACE A NOTE TO INDICATE THE ROOF DOWNSPOUTS | | | WILL DISCHARGE AT LEAST 1 FOOT AWAY FROM THE STRUCTURE | | | SIDEWALL, WHETHER BY UNDERGROUND PIPING, TAIL | | | EXTENSIONS, OR SPLASH BLOCKS- SEC. 1503.7 FBC B. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
REV |
REVISIONS |
| Rev No |
1 |
Status |
P |
Date |
2021-12-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-12-22 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-12-22 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2022-03-09 10:18:39 | 3/9/22 FEES PAID. OK TO PASS. LEM | | 2021-12-22 13:34:03 | PER RBROWN, OK TO ROUTE REVISION WITHOUT FEES - THIS | | | STOP WILL NOT BE APPROVED UNTIL FEES ARE PAID. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-03-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-07 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-07 |
Time |
11:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-12-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-30 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-30 |
Time |
12:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2022-02-17 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2022-02-17 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2022-02-17 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2022-02-17 09:13:32 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 02.17.2022 | | | PERMIT NO.: 21070675 - REVISION NO.: 21120898 | | | ________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ________________________________________ | | | | | | THIS REVIEW IS LIMITED TO THE SFPGA OFFICE BUILDING | | | ONLY AND HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. SEPARATE PERMITS REQUIRED FOR: | | | | | | 1.1. LANDSCAPING | | | 1.2. FENCING/GATES | | | 1.3. SITE/PRIVACY WALLS | | | 1.4. SITE LIGHTING | | | 1.5. IRRIGATION | | | 1.6. GENERATOR | | | 1.7. SIGNAGE | | | 1.8. PARING LOT / STRIPING / HARDSCAPE | | | 1.9. SITE FIXTURES (I.E. BIKE RACKS, ETC.) | | | | | | 2. THE WPB GOLF PARK DEVELOPMENT SHALL BE SUBJECT TO | | | ALL DEVELOPMENT ORDER CONDITIONS, AS OUTLINED IN FORMAL | | | SITE PLAN REVIEW (FSPR) CASE NO. 21-02, AND AS MAY BE | | | AMENDED. ALL CONDITIONS OF APPROVAL IMPOSED BY FSPR | | | CASE NO. 21-02, AS AMENDED, SHALL BE ADDRESSED WITHIN | | | THE APPROPRIATE SPECIFIED TIMEFRAMES. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|