| 2021-12-30 08:53:14 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected] AND REQUEST |
| | THAT IT BE CONVERTED TO PROJECTDOX. |
| | |
| | 1. PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT |
| | APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT TO |
| | BE USED FOR TILE INSTALLATION. INCLUDE COVER PAGE, |
| | EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR |
| | SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| | COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| | ENGINEERING |
| | 2. FBC R 301 FAC9N-3. PROVIDE A COMPLETE SET OF 2020 |
| | CODE VERSION PRODUCT APPROVALS/NOA'S FOR THE PROPOSED |
| | ROOFING TILE ADHESIVE TO BE USED. |
| | 3. FBC EB 706.6 PROVIDE A FLASHING DETAIL DRAWING FOR |
| | THE EXISTING PARAPET WALLS TO INCLUDE PARAPET WALL |
| | HEIGHT(S). |
| | 4. FBC B 107.2.1 PROVIDE A ROOF DRAINAGE PLAN THAT |
| | COMPLIES WITH SECTION 903.4 OF THE 2020 FBC-RESIDENTIAL |
| | AND CHAPTER 11 OF THE 2020 FBC-PLUMBING |
| | 5. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL |
| | SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH |
| | NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS. |
| | PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT |
| | INDICATE ON ROOF DRAWING/SKETCH). |
| | 6. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF |
| | DIAGRAM/SKETCH AND SHOW THE AREAS TO RECEIVE NEW |
| | ROOFING CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF |
| | SLOPE(S), MEAN ROOF HEIGHT(S). |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |