| Plan Review Stops For Permit 21120861 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-22 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-22 |
Time |
14:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-10 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-10 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2022-02-10 07:52:37 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN | | | THE SUBJECT LINE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-19 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-19 |
Time |
15:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-22 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-22 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2022-03-22 15:50:38 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) PROVIDE A DESCRIPTION OF EXISTING SITE CONDITIONS: | | | THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW | | | (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL). | | | | | | 2) SUBMIT THE TEST REPORTS FOR THE PROPOSED | | | UNDERLAYMENT BASED ON THE EXISTING SITE CONDITIONS. | | | A) SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE | | | SOUND INSULATION INCLUDING FLAME SPREAD AND SMOKE | | | DEVELOPED FOR THE APPLICABLE CONSTRUCTION CONDITIONS. | | | FBC 603.1 FLAME SPREAD AND SMOKE DEVELOPED - ASTM E | | | 84-09, | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 WALLS, | | | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR | | | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 90. | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. PLEASE NOTE | | | THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS | | | MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-10 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-10 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2022-02-10 08:46:50 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SITE PLAN SHOWING THE EXISTING KITCHEN IS NOT | | | LEGIBLE OR CLEAR. SUBMIT CLEAR AND LEGIBLE DIMENSIONED | | | FLOOR PLANS SHOWING THE EXISTING KITCHEN WITH CABINET | | | AND FIXTURE LOCATIONS AND THE PROPOSED KITCHEN FLOOR | | | PLAN. FBC AMENDMENTS 107.2.1 | | | | | | 2) PROVIDE A COMPLETE SCOPE OF WORK ON THE PROPOSED | | | FLOOR PLAN. FBC AMENDMENTS 107.2.1 | | | | | | 3) FBC AMENDMENTS 107.2.1 - INFORMATION ON CONSTRUCTION | | | DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 4) IF THIS PROJECT INVOLVES THE REPLACEMENT OR ADDITION | | | OF ANY FLOORING, PROVIDE ALL OF THE FOLLOWING THAT | | | APPLY: | | | -1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. | | | DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC AMENDMENTS | | | 107.2.1 | | | -2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. | | | -3. TYPE OF PROPOSED HARD FINISH FLOORING (TILE, | | | LAMINATE, WOOD, MARBLE, ETC.). | | | -4. STATED VALUE OF WORK. | | | -5. DESCRIPTION OF EXISTING SITE CONDITIONS: THICKNESS | | | OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW (EXPOSED | | | CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL). | | | -6. PROPOSED ACOUSTICAL INSULATION UNDERLAYMENT. | | | -7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON | | | THE EXISTING SITE CONDITIONS. | | | -8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: | | | E-84, E-90 & E-492. | | | -9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. | | | (UNLESS SUBMITTING ELECTRONICALLY) | | | -SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND | | | INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED | | | FOR THE APPLICABLE CONSTRUCTION CONDITIONS. | | | FBC 603.1 FLAME SPREAD - ASTM E 84-09, | | | FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. PLEASE NOTE | | | THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS | | | MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-03-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-03-13 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-03-13 |
Time |
12:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-01-24 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-01-24 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-01-24 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2022-01-24 15:09:28 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED AND ELECTRICAL LAYOUT PLAN SHOWING ALL OUTLETS AND | | | LIGHTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-03-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-03-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-03-29 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2022-03-29 11:27:30 | FIRE PROVISO: | | | | | | PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND | | | EQUIPMENT. | | | | | | DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM | | | DEVICES/EQUIPMENT. | | | | | | THE PROPOSED WORK MAY AFFECT FIRE SPRINKLER HEAD | | | COVERAGE OR FIRE ALARM DEVICES. | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-02-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-02-23 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2022-02-23 12:43:11 | FIRE PROVISO: | | | | | | THE PROPOSED WORK MAY AFFECT FIRE SPRINKLER HEAD | | | COVERAGE OR FIRE ALARM DEVICES. | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-12-23 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-12-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-12-23 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2021-12-23 13:44:02 | FIRE PROVISO: | | | | | | THE PROPOSED WORK MAY AFFECT FIRE SPRINKLER HEAD | | | COVERAGE OR FIRE ALARM DEVICES. | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-19 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-28 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-22 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-22 |
Time |
09:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-10 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-12-22 |
Time |
06:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-04-01 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-04-01 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-04-01 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-02-23 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-02-23 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2022-02-23 11:52:31 | 02/23/22 2 ND PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. A BAR SINK HAS BEEN ADDED AND A ISOMETRIC RISER | | | DIAGRAM IS REQUIRED PER THE WPB AMENDMENTS TO THE FBC | | | SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. THE ONE | | | PROVIDED DO NOT SHOW THE CONNECTION TO EXISTING | | | SANITARY LINES, NEED TO SHOW THE CONNECTION AND THE | | | VENT BEING USED. IT MUST BE DOWN STREAM OF A BATHROOM | | | GROUP. | | | | | | 2. THE DRAWING 002 KITCHEN SHOW THE 2017 CODE 6TH | | | EDITION AND THE CURRENT IS 2020 FBC 7 THE EDITION. | | | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE | | | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 3. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, | | | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT | | | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO | | | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. PLUMBING CONTRACTOR NEEDS TO SIGN PLANS IF | | | HE IS DESIGNING THEM. | | | | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON | | | REQUEST. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-01-04 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-01-04 |
Time |
07:42 |
Sent To |
|
|
| Notes |
| 2022-01-04 07:55:25 | 01/04/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. A BAR SINK HAS BEEN ADDED AND A ISOMETRIC RISER | | | DIAGRAM IS REQUIRED PER THE WPB AMENDMENTS TO THE FBC | | | SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. | | | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA | | | | | | WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON | | | REQUEST. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-10 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-10 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2022-02-10 07:53:54 | NO PLANS FROM AN ARCHITECT OR ENGINEER WERE SUBMITTED. |
|
|