Plan Review Details - Permit 21120861
Plan Review Stops For Permit 21120861
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-03-22 Cont ID  
Sent By rmcdouga Date 2022-03-22 Time 14:28 Rev Time 0.00
Received By rmcdouga Date 2022-03-22 Time 14:28 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-02-10 Cont ID  
Sent By rmcdouga Date 2022-02-10 Time 07:43 Rev Time 0.00
Received By rmcdouga Date 2022-02-10 Time 07:43 Sent To  
Notes
2022-02-10 07:52:37PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN
 THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-19 Cont ID  
Sent By rmcdouga Date 2022-04-19 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2022-04-19 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-22 Cont ID  
Sent By rmcdouga Date 2022-03-22 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2022-03-22 Time 15:50 Sent To  
Notes
2022-03-22 15:50:38PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE A DESCRIPTION OF EXISTING SITE CONDITIONS:
 THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL).
  
 2) SUBMIT THE TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT BASED ON THE EXISTING SITE CONDITIONS.
 A) SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE
 SOUND INSULATION INCLUDING FLAME SPREAD AND SMOKE
 DEVELOPED FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
 FBC 603.1 FLAME SPREAD AND SMOKE DEVELOPED - ASTM E
 84-09,
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. PLEASE NOTE
 THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS
 MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-02-10 Cont ID  
Sent By rmcdouga Date 2022-02-10 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2022-02-10 Time 07:53 Sent To  
Notes
2022-02-10 08:46:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SITE PLAN SHOWING THE EXISTING KITCHEN IS NOT
 LEGIBLE OR CLEAR. SUBMIT CLEAR AND LEGIBLE DIMENSIONED
 FLOOR PLANS SHOWING THE EXISTING KITCHEN WITH CABINET
 AND FIXTURE LOCATIONS AND THE PROPOSED KITCHEN FLOOR
 PLAN. FBC AMENDMENTS 107.2.1
  
 2) PROVIDE A COMPLETE SCOPE OF WORK ON THE PROPOSED
 FLOOR PLAN. FBC AMENDMENTS 107.2.1
  
 3) FBC AMENDMENTS 107.2.1 - INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) IF THIS PROJECT INVOLVES THE REPLACEMENT OR ADDITION
 OF ANY FLOORING, PROVIDE ALL OF THE FOLLOWING THAT
 APPLY:
 -1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC AMENDMENTS
 107.2.1
 -2. TOTAL SQUARE FOOTAGE OF NEW FLOORING.
 -3. TYPE OF PROPOSED HARD FINISH FLOORING (TILE,
 LAMINATE, WOOD, MARBLE, ETC.).
 -4. STATED VALUE OF WORK.
 -5. DESCRIPTION OF EXISTING SITE CONDITIONS: THICKNESS
 OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW (EXPOSED
 CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL).
 -6. PROPOSED ACOUSTICAL INSULATION UNDERLAYMENT.
 -7. TEST REPORTS FOR THE PROPOSED UNDERLAYMENT BASED ON
 THE EXISTING SITE CONDITIONS.
 -8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 -9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 (UNLESS SUBMITTING ELECTRONICALLY)
 -SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
 FBC 603.1 FLAME SPREAD - ASTM E 84-09,
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. PLEASE NOTE
 THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS
 MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-03-13 Cont ID  
Sent By jleahy Date 2022-03-13 Time 12:15 Rev Time 0.00
Received By jleahy Date 2022-03-13 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-24 Cont ID  
Sent By jleahy Date 2022-01-24 Time 15:07 Rev Time 0.00
Received By jleahy Date 2022-01-24 Time 15:00 Sent To  
Notes
2022-01-24 15:09:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED AND ELECTRICAL LAYOUT PLAN SHOWING ALL OUTLETS AND
 LIGHTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-03-29 Cont ID  
Sent By pleduc Date 2022-03-29 Time   Rev Time 0.00
Received By pleduc Date 2022-03-29 Time 11:27 Sent To  
Notes
2022-03-29 11:27:30FIRE PROVISO:
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE PROPOSED WORK MAY AFFECT FIRE SPRINKLER HEAD
 COVERAGE OR FIRE ALARM DEVICES.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-23 Cont ID  
Sent By pleduc Date 2022-02-23 Time   Rev Time 0.00
Received By pleduc Date 2022-02-23 Time 12:39 Sent To  
Notes
2022-02-23 12:43:11FIRE PROVISO:
  
 THE PROPOSED WORK MAY AFFECT FIRE SPRINKLER HEAD
 COVERAGE OR FIRE ALARM DEVICES.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-23 Cont ID  
Sent By pleduc Date 2021-12-23 Time   Rev Time 0.00
Received By pleduc Date 2021-12-23 Time 13:39 Sent To  
Notes
2021-12-23 13:44:02FIRE PROVISO:
  
 THE PROPOSED WORK MAY AFFECT FIRE SPRINKLER HEAD
 COVERAGE OR FIRE ALARM DEVICES.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-19 Cont ID  
Sent By rmcdouga Date 2022-04-19 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2022-03-28 Time 07:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-22 Cont ID  
Sent By rmcdouga Date 2022-03-22 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2022-02-22 Time 09:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-10 Cont ID  
Sent By rmcdouga Date 2022-02-10 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2021-12-22 Time 06:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-04-01 Cont ID  
Sent By lcrespo Date 2022-04-01 Time 15:11 Rev Time 0.00
Received By lcrespo Date 2022-04-01 Time 15:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-02-23 Cont ID  
Sent By lcrespo Date 2022-02-23 Time 11:52 Rev Time 0.00
Received By lcrespo Date 2022-02-23 Time 11:52 Sent To  
Notes
2022-02-23 11:52:3102/23/22 2 ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A BAR SINK HAS BEEN ADDED AND A ISOMETRIC RISER
 DIAGRAM IS REQUIRED PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. THE ONE
 PROVIDED DO NOT SHOW THE CONNECTION TO EXISTING
 SANITARY LINES, NEED TO SHOW THE CONNECTION AND THE
 VENT BEING USED. IT MUST BE DOWN STREAM OF A BATHROOM
 GROUP.
  
 2. THE DRAWING 002 KITCHEN SHOW THE 2017 CODE 6TH
 EDITION AND THE CURRENT IS 2020 FBC 7 THE EDITION.
 WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. PLUMBING CONTRACTOR NEEDS TO SIGN PLANS IF
 HE IS DESIGNING THEM.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-01-04 Cont ID  
Sent By lcrespo Date 2022-01-04 Time 07:54 Rev Time 0.00
Received By lcrespo Date 2022-01-04 Time 07:42 Sent To  
Notes
2022-01-04 07:55:2501/04/22 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A BAR SINK HAS BEEN ADDED AND A ISOMETRIC RISER
 DIAGRAM IS REQUIRED PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-02-10 Cont ID  
Sent By rmcdouga Date 2022-02-10 Time 07:53 Rev Time 0.00
Received By rmcdouga Date 2022-02-10 Time 07:53 Sent To  
Notes
2022-02-10 07:53:54NO PLANS FROM AN ARCHITECT OR ENGINEER WERE SUBMITTED.