| 2021-12-22 15:52:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF FIRE LINE UNDERGROUND |
| | WORK. |
| | |
| | FIRE LINE UNDERGROUND WORK, INCLUDING THE DDCV, SHALL |
| | BE SUBMITTED UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| | |
| | THIS PERMIT WILL NOT BE APPROVED FOR UNDERGROUND WORK. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGMENT THAT A SPEARATE FIRE LINE UNDEGROUND |
| | PERMIT WILL BE SUBMITTED. |
| | |
| | |
| | 1A) A SEPARATE WATER METER & TAP IS REQUIRED BY THE |
| | CITY'S UTILITY DEPARTMENT FOR FIRE SPRINKLER SYSTEMS, |
| | INCLUDING 13R. |
| | |
| | PLEASE CONTACT THAT DEPARTMENT FOR THEIR REQUIREMENTS |
| | FOR THE SEPARATE PERMIT(S). |
| | |
| | |
| | 2) IT APPEARS THAT THIS OCCUPANCY MAY BE A NEW |
| | RESIDENTIAL BOARD & CARE FACILITY AS SUCH SHALL COMPLY |
| | WITH NFPA 101, CH 32. |
| | |
| | PER THAT CHAPTER : |
| | |
| | 32.2.3.5.3.1 IN BUILDINGS FOUR OR FEWER STORIES IN |
| | HEIGHT AND NOT EXCEEDING |
| | 60 FT (18.3 M) IN HEIGHT ABOVE GRADE PLANE, SYSTEMS IN |
| | ACCORDANCE |
| | WITH NFPA 13R SHALL BE PERMITTED. ALL HABITABLE AREAS, |
| | CLOSETS, ROOFED |
| | PORCHES, ROOFED DECKS, AND ROOFED BALCONIES SHALL BE |
| | SPRINKLERED |
| | |
| | THERE APPEARS TO BE CLOSETS WITHOUT FS PROTECTION AS |
| | WELL AS ROOFED BALCONIES. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC A |
| | DETAILED NARRATIVE AND FIRE CODE REFERENCES. |
| | |
| | |
| | |
| | 3) IT APPEARS THAT THIS BUILDING MAY HAVE AN ATTIC OR A |
| | ROOM ON THE ROOF. |
| | |
| | |
| | PER THAT CHAPTER : |
| | |
| | 32.2.3.5.7 ATTICS SHALL BE PROTECTED IN ACCORDANCE WITH |
| | 32.2.3.5.7.1 OR |
| | 32.2.3.5.7.2. |
| | 32.2.3.5.7.1 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | REQUIRED BY |
| | 32.2.3.5, ATTICS USED FOR LIVING PURPOSES, STORAGE, OR |
| | FUEL-FIRED EQUIPMENT |
| | SHALL BE PROTECTED WITH AUTOMATIC SPRINKLERS THAT ARE |
| | PART OF THE REQUIRED, |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | 9.7.1.1. |
| | 32.2.3.5.7.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | REQUIRED BY |
| | 32.2.3.5, ATTICS NOT USED FOR LIVING PURPOSES, STORAGE, |
| | OR FUEL-FIRED EQUIPMENT |
| | SHALL MEET ONE OF THE FOLLOWING CRITERIA: |
| | (1) ATTICS SHALL BE PROTECTED THROUGHOUT BY A HEAT |
| | DETECTION SYSTEM |
| | ARRANGED TO ACTIVATE THE BUILDING FIRE ALARM SYSTEM IN |
| | ACCORDANCE |
| | WITH SECTION 9.6. |
| | (2) ATTICS SHALL BE PROTECTED WITH AUTOMATIC SPRINKLERS |
| | THAT ARE PART OF |
| | THE REQUIRED, APPROVED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE |
| | WITH 9.7.1.1. |
| | (3) ATTICS SHALL BE OF NONCOMBUSTIBLE OR |
| | LIMITED-COMBUSTIBLE |
| | CONSTRUCTION. |
| | (4) ATTICS SHALL BE CONSTRUCTED OF |
| | FIRE-RETARDANT-TREATED WOOD IN ACCORDANCE |
| | WITH NFPA 703. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC A |
| | DETAILED NARRATIVE AND FIRE CODE REFERENCES. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |