Plan Review Details - Permit 21120733
Plan Review Stops For Permit 21120733
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-01-19 Cont ID  
Sent By cpuell Date 2022-01-19 Time 16:17 Rev Time 0.00
Received By cpuell Date 2022-01-19 Time 16:17 Sent To  
Notes
2022-01-19 16:18:26PER THE ROOF DIAGRAM THE SUITES EFFECTED WILL BE A B
 AND C

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-01-11 Cont ID  
Sent By cpuell Date 2022-01-11 Time 14:11 Rev Time 0.00
Received By cpuell Date 2022-01-11 Time 14:11 Sent To  
Notes
2022-01-11 14:12:43MULTILEVEL ROOF, WILL THE SUITE AFFECTED BE A, B AND OR
 C, PLEASE RESPOND TO [email protected] OR CALL
 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-02-04 Cont ID  
Sent By jbrooks Date 2022-02-04 Time 13:21 Rev Time 0.00
Received By jbrooks Date 2022-02-04 Time 08:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-21 Cont ID  
Sent By jbrooks Date 2022-01-21 Time 12:16 Rev Time 0.00
Received By jbrooks Date 2022-01-21 Time 07:48 Sent To  
Notes
2022-01-21 12:17:05JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. PLEASE PROVIDE ENGINEER'S SIGNED AND
 SEALED FASTENER SPACING DETAIL WITH CALCULATIONS FOR
 PERIMETERS AND CORNERS AS PER PRODUCT APPROVAL
 LIMITATIONS #7. PLEASE NOTE THIS PROJECT IS LOCATED IN
 AN EXPOSURE C CATEGORY AREA.
 2. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE NOA NO.:
 20-0204.01 COVERS MULTIPLE DESIGN PRESSURE OPTIONS.
 PLEASE SELECT CORRECT OPTIONS FROM TABLE ?A? PAGE #4
 THAT MEET OR EXCEED THE MINIMUM DESIGN PRESSURE
 REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C AREAS. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. SECOND
 REQUEST.
 3. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE FLAT/LOW ROOF SLOPE(S).
 FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-12 Cont ID  
Sent By jbrooks Date 2022-01-12 Time 08:47 Rev Time 0.00
Received By jbrooks Date 2022-01-12 Time 07:39 Sent To  
Notes
2022-01-12 08:48:18JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. SUBMITTED MIAMI-DADE COUNTY NOA 18-0919.07 COVERS
 MULTIPLE ROOFING SYSTEMS TYPES A(1) THROUGH E(4).
 SELECT SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING. ENGINEERED SIGNED AND SEALED
 CALCULATIONS MAY BE REQUIRED. PLEASE NOTE THIS IS A
 CATEGORY C AREA.
 2. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE NOA NO.:
 20-0204.01 COVERS MULTIPLE DESIGN PRESSURE OPTIONS.
 PLEASE SELECT CORRECT OPTIONS FROM TABLE ?A? PAGE #4
 THAT MEET OR EXCEED THE MINIMUM DESIGN PRESSURE
 REQUIREMENT FOR ZONE 3 EXPOSURE CATEGORY C AREAS. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING
 3. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL
 SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH
 NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS.
 PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT
 INDICATE ON ROOF DRAWING/SKETCH).
 4. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-02-15 Cont ID  
Sent By cthroop Date 2022-02-15 Time 10:52 Rev Time 0.00
Received By cthroop Date 2022-02-14 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-10 Cont ID  
Sent By cthroop Date 2022-02-10 Time 14:11 Rev Time 0.00
Received By cthroop Date 2022-02-09 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-04 Cont ID  
Sent By jbrooks Date 2022-02-04 Time 13:21 Rev Time 0.00
Received By jbrooks Date 2022-01-27 Time 13:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-21 Cont ID  
Sent By jbrooks Date 2022-01-21 Time 12:16 Rev Time 0.00
Received By jbrooks Date 2022-01-18 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-12 Cont ID  
Sent By jbrooks Date 2022-01-12 Time 08:48 Rev Time 0.00
Received By jbrooks Date 2022-01-11 Time 08:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-15 Cont ID  
Sent By cthroop Date 2022-02-15 Time 10:52 Rev Time 0.00
Received By cthroop Date 2022-02-15 Time 10:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-02-10 Cont ID  
Sent By cthroop Date 2022-02-10 Time 14:10 Rev Time 0.00
Received By cthroop Date 2022-02-10 Time 13:52 Sent To  
Notes
2022-02-10 14:11:54SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 CFM
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 2ND REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: ENGINEERING CALCULATIONS IN SIGNATURE FOLDER HAS A
 COPY OF A DIGITAL SIGNATURE
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By jbrooks Date 2022-02-04 Time 13:22 Rev Time 0.00
Received By jbrooks Date 2022-02-04 Time 13:09 Sent To  
Notes
2022-02-04 13:22:55JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL OR DROP OFF ONE ORIGINAL SIGNED
 AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE TO:
 JONATHAN BROOKS
 BUILDING PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6656.
  