Plan Review Details - Permit 21120607
| Plan Review Stops For Permit 21120607 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2022-05-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-05-17 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2022-05-17 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-04-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-04-12 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-12 07:46:52 | BUILDING PROVISO: THE SPIRAL STAIR IS PART OF A MEANS | | | OF EGRESS | | | TO THE PRODUCTION AREA, LIGHTING AND SOUND WITH A | | | OCCUPANT | | | LOAD OF 5 OR LESS. 2020 FBC-BUILDING CODE SECTION | | | 1011.10. | | | BUILDING PLAN REVIEW JIM WITMER 3/01/2022 & 4/12/2022. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-03-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-03-01 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-03-01 17:01:41 | BUILDING PROVISO: THE SPIRAL STAIR IS PART OF A MEANS | | | OF EGRESS | | | TO THE PRODUCTION AREA, LIGHTING AND SOUND WITH A | | | OCCUPANT | | | LOAD OF 5 OR LESS. 2020 FBC-BUILDING CODE SECTION | | | 1011.10. | | | BUILDING PLAN REVIEW JIM WITMER 3/01/2022. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-02-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2022-02-08 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-02-08 10:22:31 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. REVISION: 21120607 | | | W. P. B. PERMIT: 20120918 | | | ADD: 509 21ST. STREET | | | CONT: PATTERSON CONSTRUCTION | | | TEL: 561-437-3059 | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. DEC. 21/2021 | | | ACTION: FAILED | | | | | | 1) 2ND REQUEST. !!!!!!!!!THE REVISION 21120607 DOES NOT | | | SHOW A INCREASE IN VALUE ALL TOUGH THE PLANS CLEARLY | | | SHOW A SUBSTANIAL INCREASE IN THE SCOPE OF WORK. | | | INCLUDE ROOF VALUE OR STATE THAT THE ROOFING PERMIT IS | | | TO HAVE THE FEES PAID UNDER THE ROOF PERMIT. | | | 109.3 BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 2-3) COMPLIED. | | | 4) THE SHEET A-2.2, A-3.3 VS A3.4, CHOIR LOFT. | | | | | | 4A) SEMI-COMPLIED. THIS REVIEW CYCLE THE DOOR ROUGH | | | OPENING IS GIVEN FOR THE MASONRY OPENING, PLEASE | | | PROVIDE THE CLEAR WIDTH DOOR OPENING WITH THE DOOR | | | OPENED AT 90 DEGREES. 2017 FBC-B 1010.1.1 AND TABLE | | | 716.5 OPENING PROTECTIVES. | | | CHOIR | | | 1ST ROUND OF COMMENTS. THE DOORS LEADING THE STAIRWAY | | | VERTICAL SHAFT DO NOT GIVE ANY SIZE NOR FIRE RATING. | | | 2017 FBC-B 1010.1.1 AND TABLE 716.5 OPENING | | | PROTECTIVES. | | | | | | 4B) 2ND ROUND OF COMMENTS. SHEET A-3.4 IS LABELED THE | | | FIRST FLOOR LIFE SAFETY PLAN WHEREAS UPLOADED THE | | | ACTUAL PLAN IS A 2ND BASEMENT PLAN LOADED TWICE. | | | PROVIDE THE OCCUPANT LOAD FOR THE CHOIR LOFT. PLEASE | | | REVIEW 1011.10 OF THE FLORIDA BUILDING CODE SECTION | | | 1011.10 WHERE SPIRAL STARS IN A COMMERCIAL APPLICATION | | | CAN ONLY BE USED WHEN IN USE FOR A TECHNICAL PRODUCTION | | | AREAS IN ACCORDANCE WITH 410.6.SECTION 410.6 .3.1 NO | | | FEWER THAN ONE MEANS OF EGRESS SHALL BE PROVIDED FROM | | | TECHNICAL PRODUCTION AREAS. | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST ROUND OF COMMENTS. THE COVERSHEET NOR ANY LIFE | | | SAFETY SHEET GIVE THE OCCUPANT LOAD OF THE CHOIR LOFT, | | | THIS IS NEEDED TO DETERMINE THE OCCUPANT LOAD TO USE | | | THE STAIR TO THE CHOIR LOFT. 107.2.1.2. ADDITIONAL | | | INFORMATION REQUIRED. PLEASE SHOW COMPLIANCE FOR | | | 1011.10 SPIRAL STAIRWAY AND AN OCCUPANT LOAD OF NOT | | | MORE THAN 5 OCCUPNTS. | | | | | | 4C) IF THE SPIRAL STAIRCASE CAN BE CONSIDERED A MEANS | | | OF EGRESS PLEASE PROVIDE SHOP DRAWINGS IN COMPLIANCE | | | WITH 1011. 10 & 1011.11. | | | | | | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | | | | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING | | | FROM CITY HALL. | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2021-12-21 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2021-12-21 |
Time |
06:54 |
Sent To |
|
|
| Notes |
| 2021-12-21 09:13:23 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION | | | SERVICES/ BUILDING DIVISION | | | 2017 FBC- BUILDING PLAN REVIEW | | | W. P. B. REVISION: 21120607 | | | W. P. B. PERMIT: 20120918 | | | ADD: 509 21ST. STREET | | | CONT: PATTERSON CONSTRUCTION | | | TEL: 561-437-3059 | | | E-MAIL: [email protected] | | | | | | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW | | | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES | | | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA | | | BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: TUES. DEC. 21/2021 | | | ACTION: BUILDING PROVISO | | | | | | 1) THE REVISION 21120607 DOES NOT SHOW A INCREASE IN | | | VALUE ALL TOUGH THE PLANS CLEARLY SHOW A SUBSTANIAL | | | INCREASE IN THE SCOPE OF WORK. | | | 109.3 BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | 2) SHEET A-3.1 & A-3.2 BOTH SHOW A NEW VERTICAL | | | PLATFORM LIFT. THE FLOOR PLAN DOES NOT PROVIDE A | | | DETAIL/ SECTION OF THE VERTICAL SHAFT NOR THE HOUR | | | RATING OF HE SHAFT NOR RATING OF THE OPENING | | | PROTECTIVES ( FIRE RATED DOORS). 2017 FBC-BUILDING CODE | | | SECTIONS 707.3.1 SHAFT CONSTRUCTION, 3002.1 HOISTWAY | | | ENCLOSURE PROTECTION AND OPENING PROTECTION TABLE | | | 716.5. | | | | | | 3) THE PLAN STATES A PLATFORM LIFT, PLATFORM LIFTS NEED | | | TO SHOW COMPLIANCE WITH SECTION 410 OF THE 2017 ACCESS. | | | CODE. DOES THE DESIGNER OF RECORD MEAN A LULA LIFT IN | | | ACCORDANCE WITH 408 OF THE 2017 ACCESSIBILITY CODE. | | | PLEASE PROVIDE DETAILS, SECTIONS AND THE APPROPRIATE | | | LITERATURE FOR THE TYPE OF LIFT TO BE INSTALLED. | | | 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. | | | | | | 4) THE SHEET A-2.2 DATED 2/10/2021 SHOWER STAIRS TO | | | CHOIR LOFT TO BE DEMOLISHED, WOOD PLATFORM FRAME OVER | | | EXISTING METAL POST TO REMAIN, THIS WAS THE SHEET THAT | | | WAS PERMITTED, NO STAIRWAY TO THE CHOIR LOFT. | | | THIS REVISION # 2 SHEETS A5.1 AND A-7.1 AND OTHER | | | SHEETS SHOW A NEW SPIRAL STAIRWAY FROM THE BASEMENT | | | LEVEL, TO FIRST FLOOR AND TO THE CHOIR LOFT. NEITHER | | | LIFE SAFETY SHEET A.3.3 LIFE SAFETY SHEET BASEMENT NOR | | | A3.4 THE FIRST FLOOR LIFE SAFETY SHEET SHOW THE SPIRAL | | | STAIR PART OF THE LIFE SAFETY PLAN. | | | | | | 4A) THE DOORS LEADING THE STAIRWAY VERTICAL SHAFT DO | | | NOT GIVE ANY SIZE NOR FIRE RATING. 2017 FBC-B 1010.1.1 | | | AND TABLE 716.5 OPENING PROTECTIVES. | | | | | | 4B) THE COVERSHEET NOR ANY LIFE SAFETY SHEET GIVE THE | | | OCCUPANT LOAD OF THE CHOIR LOFT, THIS IS NEEDED TO | | | DETERMINE THE OCCUPANT LOAD TO USE THE STAIR TO THE | | | CHOIR LOFT. 107.2.1.2. ADDITIONAL INFORMATION REQUIRED. | | | PLEASE SHOW COMPLIANCE FOR 1011.10 SPIRAL STAIRWAY AND | | | AN OCCUPANT LOAD OF NOT MORE THAN 5 OCCUPNTS. | | | | | | 4C) IF THE SPIRAL STAIRCASE CAN BE CONSIDERED A MEANS | | | OF EGRESS PLEASE PROVIDE SHOP DRAWINGS IN COMPLIANCE | | | WITH 1011. 10 & 1011.11. | | | | | | 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS | | | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT | | | REVIEW CYCLE. | | | | | | | | | AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING | | | FROM CITY HALL. | | | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM | | | PART-TIME/ RETIRED. | | | | | | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET | | | BACK INTO THE OFFICE CALL | | | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. | | | THANK YOU. | | | | | | JAMES A. WITMER BN, PX, SFP, CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES | | | DEPARTMENT | | | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 | | | TEL: 561-805-6717 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-01-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-01-19 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-01-19 |
Time |
09:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2022-02-28 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-02-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-02-28 |
Time |
11:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-02-11 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-02-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-02-11 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-02-07 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-02-07 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-02-07 |
Time |
10:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-12-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-12-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-12-21 |
Time |
15:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-24 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-12 |
Time |
08:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-26 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-10 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-03-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-10 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-27 |
Time |
08:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-22 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-06 |
Time |
09:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-01-19 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-12-15 |
Time |
14:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-24 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-24 |
Time |
17:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-26 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-26 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2022-04-26 17:10:51 | 1ST REVIEW FMC | | | PERMIT: 21120607 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE RESPONSE LETTER REFERENCED IN THE RESUBMITTAL | | | LETTER WAS NOT INCLUDED. THERE IS A NOTE ON SHEET M02 | | | THAT STATES THE ROOM WILL NOT HAVE MORE THAN 63 | | | OCCUPANTS IN ACCORDANCE WITH THE OWNER?S DESIGN | | | REQUIREMENTS AND STATISTICAL DATA. THE STATISTICAL DATA | | | WILL NEED TO BE INCLUDED IN THE RESUBMITTAL FOR REVIEW. | | | SEE EXCEPTION BELOW | | | | | | 403.3.1.1 EXCEPTION: THE OCCUPANT LOAD IS NOT REQUIRED | | | TO BE DETERMINED BASED ON THE ESTIMATED MAXIMUM | | | OCCUPANT LOAD RATE INDICATED IN TABLE 403.3.1.1 WHERE | | | APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY OF | | | AN ALTERNATE ANTICIPATED OCCUPANT DENSITY. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-03-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-10 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-10 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2022-03-10 08:37:31 | SHEET M1.1 INDICATES THAT THE OAF-1 IS INTRODUCING 1000 | | | CFM'S OF OUTDOOR AIR TO THE SOCIAL HALL. FBC M SECTION | | | 403.3.1.1 TELLS US THAT WE MUST USE TABLE 403.3.1.1 TO | | | DETERMINE HOW MUCH OUTDOOR AIR IS REQUIRED FOR EACH USE | | | OF SPACE, BASED ON THE SQURE FOOTAGE AND THE USE OF | | | SPACE IS A MULTI-USE ASSEMBLY THE REQUIRED OUTDOOR AIR | | | WILL BE 1,514 CFM'S. UNLESS THE ENGINEER DESIGNS A | | | SYSTEM BASED ON THE EXCEPTION OF FBC M 403.2 THE | | | OUTDOOR AIR REQUIRED WILL BE 1,514 CFM'S FOR THIS | | | SPACE. | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-02-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-22 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-22 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2022-02-22 17:17:15 | YOUR RESPONSE FOR PREVIOUS COMMENT 5 BELOW DOES NOT | | | MAKE SENSE AS THE SHEET REFERENCED IN YOUR COMMENT DOES | | | NOT EXIST IN THIS PACKAGE AND THERE ARE SEVERAL UNITS | | | CONDITIONING THE SOCIAL HALL, SOME ARE NOT LISTED IN | | | YOUR RESPONSE. | | | | | | 5) SHEET M11 DETAIL 5 SHEET M1.3 IS NOT IN THIS | | | PACKAGE. PLEASE PROVIDE A DETAIL OF HOW THE OUTDOOR AIR | | | WILL BE CONDITIONED BEFORE IT ENTERS THE SPACE. FBC | | | 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-20 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-20 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2021-12-20 17:10:20 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21120607 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M0.2: IN THE VENTILATION CALCULATIONS, PLEASE | | | REFERENCE THE 2020 FBC MECHANICAL CODE. THE ASHRAE | | | 170-2017 IS FOR HEALTH CARE FACILITIES, PLEASE EXPLAIN | | | HOW THIS APPLIES TO THIS OCCUPANCY. | | | | | | 2) SHEET M0.2: VENTILATION CALCULATIONS: THE MEETING | | | ROOM APPEARS TO BE CALCULATED AS A CONFERENCE ROOM, | | | THIS AREA SHOULD BE CALCULATED AS A MULTIUSE ASSEMBLY. | | | FBC M TABLE 403.3.1.1 | | | | | | 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FBC EC C403.2.1 | | | | | | 4) PLEASE MAKE SURE ALL OUTDOOR AIR INTAKES ARE 10 FEET | | | FROM EXHAUST TERMINATIONS. FBC M 401.4-2 | | | | | | 5) SHEET M11 DETAIL 5 SHEET M1.3 IS NOT IN THIS | | | PACKAGE. PLEASE PROVIDE A DETAIL OF HOW THE OUTDOOR AIR | | | WILL BE CONDITIONED BEFORE IT ENTERS THE SPACE. FBC | | | 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-23 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-23 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2022-04-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-04-25 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-04-25 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2022-04-25 13:35:12 | 3RD REVIEW FBC-2017 PLUMBING | | | PERMIT- 21120607 | | | 4/25/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-3.1: REFER TO SEC. 403.2 FBC P SEPARATE | | | FACILITES- TWO FEMALE WATER CLOSETS ARE REQUIRED. WHERE | | | IT IS SHOWN ON THE PLANS PLEASE LABEL THE UNISEX TOILET | | | ROOM AS FEMALE TO MEET THE REQUIREMENT. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-03-02 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-03-02 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2022-03-02 14:31:17 | 2ND REVIEW FBC-2017 PLUMBING | | | PERMIT- 21120607 | | | 2/16/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED IST AND 2ND REVIEW | | | COMMENTS LISTED BELOW. | | | | | | 1) 2ND REQUEST- FAILED. SHEET A-3.1: THE PLUMBING | | | FIXTURE CALCULATIONS DO NOT INCLUDE THE REQUIRED | | | SERVICE SINKS AND DRINKING FOUNTAINS, AND THEIR | | | LOCATIONS ARE NOT SHOWN ON THE PLANS- TABLE 403.1 FBC | | | P. PLEASE REVISE THE PLANS TO INCLUDE THE REQUIRED | | | FIXTURES. THE CALCULATIONS FOR A3 SHOWN ON THE PLAN ARE | | | INCORRECT. FEMALE WATER CLOSETS ARE CALCULATED AT 1 PER | | | 75 FOR CHURCHES- TABLE 403.1 FBC P. THE 2ND REQUIRED | | | FEMALE WATER CLOSET PREVIOUSLY SHOWN IN THE | | | CALCULATIONS WAS REMOVED FROM THE RESUBMITTED PLAN. | | | | | | 3) 2ND REQUEST- FAILED SHEET A-7.4 ITEMS C, D, & E. | | | A-7.4: | | | C) FAILED. HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER | | | SURFACES FROM THE FINISHED FLOORS- 606.3. NOT PROVIDED. | | | D) FAILED. HEIGHTS OF THE MIRRORS FROM THE FINISHED | | | FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3. THE | | | MEASUREMENT SHOWN IS TO THE MIRROR FRAME, NOT THE | | | REFLECTIVE SURFACE. | | | E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF | | | GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, | | | FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THE 2'11" | | | MEASUREMENT IN ELEV. 3 IS SHOWN TO THE CENTER OF THE | | | GRAB BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE. | | | NOTE- THE GRAB BARS LISTED IN THE SCHEDULE DO NOT MATCH | | | THE GRAB BARS IN THE DRAWINGS. PLEASE SEE FIGURES | | | 604.5.1 & 604.5.2 FBC ACC: SHOW THE 12-INCH MAX SPACING | | | AND MIN. 54-INCH EXTENSION FOR THE SIDE GRAB BAR, AND | | | SHOW THE REAR GRAB BAR WILL EXTEND MIN. 12-INCHES ONE | | | WAY FROM THE CENTERLINE OF THE WATER CLOSET, AND MIN. | | | 24-INCHES FROM THE CENTERLINE TO THE OPEN SIDE. | | | | | | 4) 2ND REQUEST FAILED SHEET A7.4- ITEMS A, C, D, E, F, | | | & H: PLEASE PROVIDE AN ENLARGED DRAWING OF THE PRIEST | | | OFFICE BATHROOM WITH FIXTURE AND ACCESSORY ELEVATION | | | DETAILS. PLEASE NOTE THAT PRIVATE BATHROOMS CONSTRUCTED | | | UNDER THE FBC ACC SHALL BE IN COMPLIANCE WITH THE | | | FOLLOWING CODE SECTIONS: | | | A) FAILED. CLEAR FLOOR SPACES FOR WATER CLOSETS- SEC. | | | 604.3. MINIMUM 56-INCHES DEEP X 60-INCHES WIDE SPACE | | | REQUIRED. | | | B) FAILED. CLEAR FLOOR SPACES FOR LAVATORIES- SEC. | | | 606.2. THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR | | | SPACE- SEC. 603.2.3. | | | C) FAILED. CENTERLINE OF THE WATER CLOSET FROM THE SIDE | | | WALL- SEC.604.2. THE WATER CLOSET IS NOT POSITIONED AT | | | THE SIDE WALL. | | | D) FAILED. HEIGHT OF MIRROR FROM FINISHED FLOOR TO | | | REFLECTIVE SURFACE- SEC. 603.3. ELEVATION DETAIL DOES | | | NOT PROVIDE A MEASUREMENT. | | | E) FAILED. REINFORCEMENT LOCATIONS FOR FUTURE GRAB BARS | | | AT WATER CLOSETS- SEC. 604.5 EXCEPTION 1. WATER CLOSET | | | NOT POSITIONED FOR A FUTURE SIDE WALL GRAB BAR TO BE | | | PROVIDED | | | F) FAILED. SHOWER TYPE, SHOWER DIMENSIONS, CLEAR FLOOR | | | SPACE FOR SHOWER, CONTROLS LOCATIONS, AND REINFORCEMENT | | | LOCATIONS FOR FUTURE GRAB BARS- SECS. 608.1- 608.7. THE | | | SHOWER IS NOT SET UP FOR ACCESSIBLE USE ACCORDING TO | | | SECS- 608.1- 608.7 | | | H) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER | | | MEASURED FROM THE FRONT OF THE WATER CLOSET- SEC. AND | | | FIGURE 604.7. WATER CLOSET AND TP DISPENSER NOT | | | POSITIONED AT SIDE WALL. | | | | | | 13) 2ND REQUEST- FAILED SHEET P0.1: PROVIDE SHOWER PAN | | | DRAIN, LINER, AND WALL FINISH DETAILS- SECS. 417.3, | | | 417.4.1, & 417.5.2 FBC P. NOT PROVIDED. PLEASE NOTE | | | THAT THE 3'-4" CERAMIC WALL HEIGHTS SHOWN ON SHEET A7.4 | | | ARE NOT IN COMPLIANCE WITH SEC. 1210.2.2 FBC B WHICH | | | REQUIRES THE TILE TO BE 4FT. IN HEIGHT AT THE WATER | | | CLOSETS. | | | | | | NEW COMMENT | | | 1) SHEETS P0.1 & P0.2: REFER TO SEC. 607.1.1 FBC P AND | | | PROVIDE EITHER A MASTER THERMOSTATIC MIXING VALVE AT | | | THE WATER HEATER OR INDIVIDUAL MIXING VALVES AT | | | FIXTURES SUPPLYING HOT WATER INCLUDING THE HAND SINKS, | | | MOP SINKS, AND 3-COMPARTMENT SINKS. PLEASE NOTE THE | | | LAVATORY SINKS ARE APPROVED FOR DELIVERY OF TEMPERED | | | WATER USING THE ASSE 1070 MIXING VALVES. | | | | | | 2) DRINKING FOUNTAINS: REFER TO SECTIONS 306, 307, AND | | | 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION | | | DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE | | | CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW | | | THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A | | | FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION | | | 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE | | | FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2 | | | PROTRUSION LIMITS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-02-16 |
Time |
10:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-16 |
Time |
06:53 |
Sent To |
|
|
| Notes |
| 2022-02-16 10:19:25 | 2ND REVIEW FBC-2017 PLUMBING | | | PERMIT- 21120607 | | | 2/16/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE | | | 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES FOR | | | FURTHER CLARIFICATION. CONCERNING THE ACCESSIBILITY | | | FAILURES LISTED BELOW IT?S IMPORTANT TO NOTE THAT | | | CHURCHES ARE EXEMPT FROM MEETING ADA REQUIRMENTS | | | HOWEVER THE ARCHITECT IS CHOOSING TO COMPLY WITH THE | | | FLORIDA ACCESSIBILTY CODE- 2017. PLEASE REVIEW SEC. | | | 101.1.4 FBC ACC: "THIS CODE IS NOT INTENDED TO EXPAND | | | OR DIMINISH THE DEFENSES AVAILABLE TO A PLACE OF PUBLIC | | | ACCOMMODATION OR A COMMERCIAL FACILITY UNDER THE | | | AMERICANS WITH DISABILITIES ACT AND THE ADA STANDARDS | | | FOR ACCESSIBLE DESIGN, INCLUDING, BUT NOT LIMITED TO, | | | THE READILY ACHIEVABLE STANDARD, AND THE STANDARDS | | | APPLICABLE TO ALTERATIONS TO PLACES OF PUBLIC | | | ACCOMMODATION AND COMMERCIAL FACILITIES." | | | THE ARCHITECT SHOULD CLARIFY ON THE PLANS IF EXEMPTION | | | IS BEING CLAIMED FOR THE CHURCH, HOWEVER THE CURRENT | | | REVIEW WILL REMAIN BASED ON THE FBC ACC UNTIL FURTHER | | | INFORMATION IS PROVIDED. | | | | | | 1) FAILED. SHEET A-3.1: THE PLUMBING FIXTURE | | | CALCULATIONS DO NOT INCLUDE THE REQUIRED SERVICE SINKS | | | AND DRINKING FOUNTAINS, AND THEIR LOCATIONS ARE NOT | | | SHOWN ON THE PLANS- TABLE 403.1 FBC P. PLEASE REVISE | | | THE PLANS TO INCLUDE THE REQUIRED FIXTURES. THE 2ND | | | REQUIRED FEMALE WATER CLOSET PREVIOUSLY SHOWN IN THE | | | CALCULATIONS WAS REMOVED FROM THE RESUBMITTED PLAN. | | | REFER TO TABLE 403.1 FBC P- 2 FEMALE WATER CLOSETS ARE | | | REQUIRED, HOWEVER ONLY 1 IS SHOWN. PLEASE INDICATE HOW | | | THE PLAN IS MEETING COMPLIANCE. | | | | | | 3) FAILED ITEMS C, D, & E. A-7.4: PLEASE INDICATE WHICH | | | CODE IS BEING USED TO DESIGN THE MEN'S AND WOMEN'S | | | HANDICAP BATHROOMS. ADA IS NOTED IN THE DETAILS HOWEVER | | | SHEET A-3.3 INDICATES THE PLANS HAVE BEEN DESIGNED IN | | | ACCORDANCE WITH FLORIDA BUILDING CODE- 2017. THE FBC-17 | | | INCLUDES FLORIDA ACCESSIBILITY CODE- 2017. PLEASE | | | REVIEW SEE THE LIST OF FBC ACC COMPLIANCES BELOW AND | | | REVISE THE PLAN: | | | C) FAILED. HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER | | | SURFACES FROM THE FINISHED FLOORS- 606.3. NOT PROVIDED. | | | D) FAILED. HEIGHTS OF THE MIRRORS FROM THE FINISHED | | | FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3. THE | | | MEASUREMENT SHOWN IS TO THE MIRROR FRAME, NOT THE | | | REFLECTIVE SURFACE. | | | E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF | | | GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, | | | FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THE 2'11" | | | MEASUREMENT IN ELEV. 3 IS SHOWN TO THE CENTER OF THE | | | GRAB BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE. | | | NOTE- THE GRAB BARS LISTED IN THE SCHEDULE DO NOT MATCH | | | THE GRAB BARS IN THE DRAWINGS. PLEASE SEE FIGURES | | | 604.5.1 & 604.5.2 FBC ACC: SHOW THE 12-INCH MAX SPACING | | | AND MIN. 54-INCH EXTENSION FOR THE SIDE GRAB BAR, AND | | | SHOW THE REAR GRAB BAR WILL EXTEND MIN. 12-INCHES ONE | | | WAY FROM THE CENTERLINE OF THE WATER CLOSET, AND MIN. | | | 24-INCHES FROM THE CENTERLINE TO THE OPEN SIDE. | | | | | | 4) FAILED. ITEMS A, C, D, E, F, & H. A-7.4: PLEASE | | | PROVIDE AN ENLARGED DRAWING OF THE PRIEST OFFICE | | | BATHROOM WITH FIXTURE AND ACCESSORY ELEVATION DETAILS. | | | PLEASE NOTE THAT PRIVATE BATHROOMS CONSTRUCTED UNDER | | | THE FBC ACC SHALL BE IN COMPLIANCE WITH THE FOLLOWING | | | CODE SECTIONS: | | | A) FAILED. CLEAR FLOOR SPACES FOR WATER CLOSETS- SEC. | | | 604.3. MINIMUM 56-INCHES DEEP X 60-INCHES WIDE SPACE | | | REQUIRED. | | | B) FAILED. CLEAR FLOOR SPACES FOR LAVATORIES- SEC. | | | 606.2. THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR | | | SPACE- SEC. 603.2.3. | | | C) FAILED. CENTERLINE OF THE WATER CLOSET FROM THE SIDE | | | WALL- SEC.604.2. THE WATER CLOSET IS NOT POSITIONED AT | | | THE SIDE WALL. | | | D) FAILED. HEIGHT OF MIRROR FROM FINISHED FLOOR TO | | | REFLECTIVE SURFACE- SEC. 603.3. ELEVATION DETAIL DOES | | | NOT PROVIDE A MEASUREMENT. | | | E) FAILED. REINFORCEMENT LOCATIONS FOR FUTURE GRAB BARS | | | AT WATER CLOSETS- SEC. 604.5 EXCEPTION 1. WATER CLOSET | | | NOT POSITIONED FOR A FUTURE SIDE WALL GRAB BAR TO BE | | | PROVIDED | | | F) FAILED. SHOWER TYPE, SHOWER DIMENSIONS, CLEAR FLOOR | | | SPACE FOR SHOWER, CONTROLS LOCATIONS, AND REINFORCEMENT | | | LOCATIONS FOR FUTURE GRAB BARS- SECS. 608.1- 608.7. THE | | | SHOWER IS NOT SET UP FOR ACCESSIBLE USE ACCORDING TO | | | SECS- 608.1- 608.7 | | | H) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER | | | MEASURED FROM THE FRONT OF THE WATER CLOSET- SEC. AND | | | FIGURE 604.7. WATER CLOSET AND TP DISPENSER NOT | | | POSITIONED AT SIDE WALL. | | | | | | 5) FAILED. A-7.4: IN STANDARD TOILET ROOMS THE WATER | | | CLOSET AND VANITY SHALL NOT BE CLOSER THAN 30 INCHES | | | CENTER TO CENTER- SEC. 405.3.1 FBC P. THE UNISEX PLAN | | | SHOWS 28 INCHES. THE CORRECTED PLAN SHOWS THE LAVATORY | | | SINK CENTERED AT 14-INCHES FROM THE SIDE WALL HOWEVER | | | THE MINIMUM IS 15-INCHES. PLEASE CLARIFY THE DESIGN | | | INTENTION CONCERNING THE FAMILY RESTROOM. IT IS NOT | | | SHOWN TO BE ACCESSIBLE LIKE THE MEN'S AND WOMEN'S | | | RESTROOMS. | | | | | | 13) FAILED. P0.1: PROVIDE SHOWER PAN DRAIN, LINER, AND | | | WALL FINISH DETAILS- SECS. 417.3, 417.4.1, & 417.5.2 | | | FBC P. NOT PROVIDED. PLEASE NOTE THAT THE 3'-4" CERAMIC | | | WALL HEIGHTS SHOWN ON SHEET A7.4 ARE NOT IN COMPLIANCE | | | WITH SEC. 1210.2.2 FBC B WHICH REQUIRES THE TILE TO BE | | | 4FT. IN HEIGHT AT THE WATER CLOSETS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-12-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-12-30 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-12-29 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2021-12-30 11:05:28 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT- 21120607 | | | 12/30/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-3.1: THE PLUMBING FIXTURE CALCULATIONS DO | | | NOT INCLUDE THE REQUIRED SERVICE SINKS AND DRINKING | | | FOUNTAINS, AND THEIR LOCATIONS ARE NOT SHOWN ON THE | | | PLANS- TABLE 403.1 FBC P. PLEASE REVISE THE PLANS TO | | | INCLUDE THE REQUIRED FIXTURES. | | | | | | 2) SHEET A3.1 & A-3.3: LABEL THE TOILETS ROOMS AS MALE, | | | FEMALE, FAMILY, OR ASSISTED USE IN ACCORDANCE WITH | | | SECS. 403.1.2 & 403.2 FBC P. PLEASE REMOVE THE | | | "EXISTING TOILET ROOM TO REMAIN" NOTES. THE DEMOLITION, | | | ARCHITECTURAL AND PLUMBING PLANS INDICATE NEW TOILET | | | ROOMS- SEC. 107.2.1 WPB. | | | | | | 3) A-7.4: PLEASE INDICATE WHICH CODE IS BEING USED TO | | | DESIGN THE MEN'S AND WOMEN'S HANDICAP BATHROOMS. ADA IS | | | NOTED IN THE DETAILS HOWEVER SHEET A-3.3 INDICATES THE | | | PLANS HAVE BEEN DESIGNED IN ACCORDANCE WITH FLORIDA | | | BUILDING CODE- 2017. THE FBC-17 INCLUDES FLORIDA | | | ACCESSIBILITY CODE- 2017. PLEASE REVIEW SEE THE LIST OF | | | FBC ACC COMPLIANCES BELOW AND REVISE THE PLAN: | | | A) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS | | | SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM- SEC. | | | 604.2. THE PLAN SHOWS 19-1/2-INCHES. | | | B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED | | | FLOORS SHALL 17 INCHES MINIMUM AND 19 INCHES MAXIMUM TO | | | THE TOP OF THE SEAT- 604.4. | | | C) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER | | | SURFACES FROM THE FINISHED FLOORS- 606.3. | | | D) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO | | | THE REFLECTIVE SURFACES- SEC. 603.3 | | | E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, | | | FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THE 2'11" | | | MEASUREMENT IN ELEV. 3 IS SHOWN TO THE CENTER OF THE | | | GRAB BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE. | | | NOTE- THE GRAB BARS LISTED IN THE SCHEDULE DO NOT MATCH | | | THE GRAB BARS IN THE DRAWINGS. | | | F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS SHALL | | | BE ON THE OPEN SIDES OF THE WATER CLOSETS, NOT ON THE | | | CLOSED SIDES- 604.6. | | | G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED | | | FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE | | | 604.7. | | | H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. | | | 606.2 AND FIGURES 306.2 & 306.3. | | | I) REACH HANDLE HEIGHTS OF THE DIAPER CHANGING STATIONS | | | IN THE CLOSED POSITIONS, AND THE HAND TOWEL DISPENSERS | | | (NOTE- DISPENSER LOCATIONS NOT SHOWN IN THE DRAWINGS)- | | | SEC. 308. | | | | | | 4) A-7.4: PLEASE PROVIDE AN ENLARGED DRAWING OF THE | | | PRIEST OFFICE BATHROOM WITH FIXTURE AND ACCESSORY | | | ELEVATION DETAILS. PLEASE NOTE THAT PRIVATE BATHROOMS | | | CONSTRUCTED UNDER THE FBC ACC SHALL BE IN COMPLIANCE | | | WITH THE FOLLOWING CODE SECTIONS: | | | A) CLEAR FLOOR SPACES FOR WATER CLOSETS- SEC. 604.3. | | | B) CLEAR FLOOR SPACES FOR LAVATORIES- SEC. 606.2. | | | C) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- | | | SEC.604.2. | | | D) HEIGHT OF MIRROR FROM FINISHED FLOOR TO REFLECTIVE | | | SURFACE- SEC. 603.3 | | | E) REINFORCEMENT LOCATIONS FOR FUTURE GRAB BARS AT | | | WATER CLOSETS- SEC. 604.5 EXCEPTION 1. | | | F) SHOWER TYPE, SHOWER DIMENSIONS, CLEAR FLOOR SPACE | | | FOR SHOWER, CONTROLS LOCATIONS, AND REINFORCEMENT | | | LOCATIONS FOR FUTURE GRAB BARS- SECS. 608.1- 608.7. | | | G) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SEC. | | | 604.6. | | | H) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED | | | FROM THE FRONT OF THE WATER CLOSET- SEC. AND FIGURE | | | 604.7. | | | | | | 5) A-7.4: IN STANDARD TOILET ROOMS THE WATER CLOSET AND | | | VANITY SHALL NOT BE CLOSER THAN 30 INCHES CENTER TO | | | CENTER- SEC. 405.3.1 FBC P. THE UNISEX PLAN SHOWS 28 | | | INCHES. | | | | | | 6) P0.1, P0.2, & P1.1: SINKS AND DISHWASHERS IN FOOD | | | PREP AREAS SHALL DISCHARGE THROUGH AN INDIRECT WASTE | | | PIPE INTO APPROVED WASTE RECEPTORS- SECS. 802.1, | | | 802.1.1, 802.1.6, 802.1.7, 802.2, AND 802.3 FBC P. | | | PLEASE REVISE THE PLANS ACCORDINGLY. | | | | | | 7) P0.1, P0.2, & P1.1: A GREASE INTERCEPTOR IS REQUIRED | | | TO RECEIVE THE DRAINAGE FROM THE SINK AND DISHWASHER IN | | | THE FOOD PREP AREAS- SEC. 1003.3.1 FBC P. INSTALLATION | | | OF THE INTERCEPTOR SHALL BE UNDER SEPARATE PERMIT- SEC. | | | 105.1 WPB. | | | A) REVISE THE PLANS TO SHOW THE LOCATION OF THE | | | INTERCEPTOR AND PLUMBING PIPING REQUIREMENTS. SHOW THE | | | GREASE WASTE PIPING RUNS FROM THE FIXTURES TO THE | | | INTERCEPTOR AND FROM THE INTERCEPTOR TO POINT OF | | | CONNECTION TO THE EXISTING BUILDING OR SEWER DRAIN. | | | SHOW LOCATIONS OF ALL REQUIRED CLEANOUTS AND VENTS PER | | | MANUFACTURER'S SPECIFICATIONS- SECTION 1003.3.4 FBC P | | | AND SECTION 107.2.1 WPB. | | | B) PROVIDE GREASE WASTE CALCULATIONS AND INTERCEPTOR | | | EQUIPMENT SCHEDULE ON THE PLAN IN COMPLIANCE WITH | | | SECTION 1003.3.5 FBC P. | | | | | | 8) P0.1: PLEASE INCLUDE THE TOILET ROOM, BATHROOM, FOOD | | | PREP, AND SACRISTY FIXTURES AND FAUCETS IN THE | | | SCHEDULE- SEC. 107.2.1 WPB AND TABLE 604.5 FBC P. | | | | | | 9) P0.1: PLEASE INCLUDE THE EFFICIENCY RATING OF THE | | | WATER HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC. | | | | | | 10) P0.1, P1.0 & P1.1: SHOW THE WATER HEATER PAN DRAIN | | | LINE RUN TO DISCHARGE LOCATION- SEC. 504.7.2 FBC P. | | | | | | 11) P1.0 & P1.1: THE 1/2-INCH HOT WATER SUPPLY PIPES TO | | | THE LAVATORIES ARE EXCEEDING THE MAXIMUM 2 FT. LENGTHS | | | ALLOWED FROM THE NEAREST HOT WATER SOURCE TO THE | | | FIXTURE SUPPLY PIPE TERMINATION POINT- SEC. C404.5.1 | | | FBC EC. EITHER PROVIDE RECIRCULATION LOOPS AT THE | | | LAVATORIES OR POINT OF USE WATER HEATERS. | | | | | | 12) P0.1, P1.0, & P1.1: INDICATE HOW TEMPERED WATER | | | WILL BE DELIVERED FROM THE LAVATORIES- SEC. 416.5 FBC | | | P. | | | | | | 13) P0.1: PROVIDE SHOWER PAN DRAIN, LINER, AND WALL | | | FINSIH DETAILS- SECS. 417.3, 417.4.1, & 417.5.2 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-24 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-24 |
Time |
17:24 |
Sent To |
|
|
| Notes |
| 2022-05-17 09:43:20 | 5/17/22 ARCHITECTURAL SHEETS DIGITALLY SIGNED & SEALED. | | | JW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-26 |
Time |
17:11 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-26 |
Time |
17:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-03-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-10 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-10 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-02-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-22 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-22 |
Time |
17:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-01-19 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-01-19 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-01-19 |
Time |
10:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-03-02 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-03-02 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-03-02 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-11 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-02-11 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-02-11 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2022-02-11 14:55:04 | 2/11/22 FAILED- DEMOLATION PERMITS NEEDED BEFORE TO | | | ALLOW STAFF TO MOVE FORWARD | | | | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-12-28 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2021-12-28 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2021-12-28 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2021-12-28 09:57:25 | 12/28/21 FAILED. | | | | | | PLEASE PROVIDE A SEPRATE PERMIT FOR EACH PROPOSED | | | DEVELOPMENT. SEPRATE PERMITS REQUIRED FOR FENCE, | | | LANDSCAPE, PARKING LOT, NEW ADDITIONS, ECT. | | | | | | PLEASE PROVIDE THE SETBACKS OF THE PRINCIPLE BUIDLING | | | AND PROPOSED ADDITION, DIMENSIONS OF PARKING SPACE AND | | | FENCE HEIGHT. | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | | | | | | | |
|
|
|