Plan Review Details - Permit 21120607
Plan Review Stops For Permit 21120607
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-05-17 Cont ID  
Sent By jwitmer Date 2022-05-17 Time 09:39 Rev Time 0.00
Received By jwitmer Date 2022-05-17 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-12 Cont ID  
Sent By jwitmer Date 2022-04-12 Time 07:46 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-04-12 07:46:52BUILDING PROVISO: THE SPIRAL STAIR IS PART OF A MEANS
 OF EGRESS
 TO THE PRODUCTION AREA, LIGHTING AND SOUND WITH A
 OCCUPANT
 LOAD OF 5 OR LESS. 2020 FBC-BUILDING CODE SECTION
 1011.10.
 BUILDING PLAN REVIEW JIM WITMER 3/01/2022 & 4/12/2022.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 17:02 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-03-01 17:01:41BUILDING PROVISO: THE SPIRAL STAIR IS PART OF A MEANS
 OF EGRESS
 TO THE PRODUCTION AREA, LIGHTING AND SOUND WITH A
 OCCUPANT
 LOAD OF 5 OR LESS. 2020 FBC-BUILDING CODE SECTION
 1011.10.
 BUILDING PLAN REVIEW JIM WITMER 3/01/2022.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-08 Cont ID  
Sent By jwitmer Date 2022-02-08 Time 10:22 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-02-08 10:22:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21120607
 W. P. B. PERMIT: 20120918
 ADD: 509 21ST. STREET
 CONT: PATTERSON CONSTRUCTION
 TEL: 561-437-3059
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 21/2021
 ACTION: FAILED
  
 1) 2ND REQUEST. !!!!!!!!!THE REVISION 21120607 DOES NOT
 SHOW A INCREASE IN VALUE ALL TOUGH THE PLANS CLEARLY
 SHOW A SUBSTANIAL INCREASE IN THE SCOPE OF WORK.
 INCLUDE ROOF VALUE OR STATE THAT THE ROOFING PERMIT IS
 TO HAVE THE FEES PAID UNDER THE ROOF PERMIT.
 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2-3) COMPLIED.
 4) THE SHEET A-2.2, A-3.3 VS A3.4, CHOIR LOFT.
  
 4A) SEMI-COMPLIED. THIS REVIEW CYCLE THE DOOR ROUGH
 OPENING IS GIVEN FOR THE MASONRY OPENING, PLEASE
 PROVIDE THE CLEAR WIDTH DOOR OPENING WITH THE DOOR
 OPENED AT 90 DEGREES. 2017 FBC-B 1010.1.1 AND TABLE
 716.5 OPENING PROTECTIVES.
 CHOIR
 1ST ROUND OF COMMENTS. THE DOORS LEADING THE STAIRWAY
 VERTICAL SHAFT DO NOT GIVE ANY SIZE NOR FIRE RATING.
 2017 FBC-B 1010.1.1 AND TABLE 716.5 OPENING
 PROTECTIVES.
  
 4B) 2ND ROUND OF COMMENTS. SHEET A-3.4 IS LABELED THE
 FIRST FLOOR LIFE SAFETY PLAN WHEREAS UPLOADED THE
 ACTUAL PLAN IS A 2ND BASEMENT PLAN LOADED TWICE.
 PROVIDE THE OCCUPANT LOAD FOR THE CHOIR LOFT. PLEASE
 REVIEW 1011.10 OF THE FLORIDA BUILDING CODE SECTION
 1011.10 WHERE SPIRAL STARS IN A COMMERCIAL APPLICATION
 CAN ONLY BE USED WHEN IN USE FOR A TECHNICAL PRODUCTION
 AREAS IN ACCORDANCE WITH 410.6.SECTION 410.6 .3.1 NO
 FEWER THAN ONE MEANS OF EGRESS SHALL BE PROVIDED FROM
 TECHNICAL PRODUCTION AREAS.
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST ROUND OF COMMENTS. THE COVERSHEET NOR ANY LIFE
 SAFETY SHEET GIVE THE OCCUPANT LOAD OF THE CHOIR LOFT,
 THIS IS NEEDED TO DETERMINE THE OCCUPANT LOAD TO USE
 THE STAIR TO THE CHOIR LOFT. 107.2.1.2. ADDITIONAL
 INFORMATION REQUIRED. PLEASE SHOW COMPLIANCE FOR
 1011.10 SPIRAL STAIRWAY AND AN OCCUPANT LOAD OF NOT
 MORE THAN 5 OCCUPNTS.
  
 4C) IF THE SPIRAL STAIRCASE CAN BE CONSIDERED A MEANS
 OF EGRESS PLEASE PROVIDE SHOP DRAWINGS IN COMPLIANCE
 WITH 1011. 10 & 1011.11.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By jwitmer Date 2021-12-21 Time 09:13 Rev Time 0.00
Received By jwitmer Date 2021-12-21 Time 06:54 Sent To  
Notes
2021-12-21 09:13:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 21120607
 W. P. B. PERMIT: 20120918
 ADD: 509 21ST. STREET
 CONT: PATTERSON CONSTRUCTION
 TEL: 561-437-3059
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 21/2021
 ACTION: BUILDING PROVISO
  
 1) THE REVISION 21120607 DOES NOT SHOW A INCREASE IN
 VALUE ALL TOUGH THE PLANS CLEARLY SHOW A SUBSTANIAL
 INCREASE IN THE SCOPE OF WORK.
 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDERESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) SHEET A-3.1 & A-3.2 BOTH SHOW A NEW VERTICAL
 PLATFORM LIFT. THE FLOOR PLAN DOES NOT PROVIDE A
 DETAIL/ SECTION OF THE VERTICAL SHAFT NOR THE HOUR
 RATING OF HE SHAFT NOR RATING OF THE OPENING
 PROTECTIVES ( FIRE RATED DOORS). 2017 FBC-BUILDING CODE
 SECTIONS 707.3.1 SHAFT CONSTRUCTION, 3002.1 HOISTWAY
 ENCLOSURE PROTECTION AND OPENING PROTECTION TABLE
 716.5.
  
 3) THE PLAN STATES A PLATFORM LIFT, PLATFORM LIFTS NEED
 TO SHOW COMPLIANCE WITH SECTION 410 OF THE 2017 ACCESS.
 CODE. DOES THE DESIGNER OF RECORD MEAN A LULA LIFT IN
 ACCORDANCE WITH 408 OF THE 2017 ACCESSIBILITY CODE.
 PLEASE PROVIDE DETAILS, SECTIONS AND THE APPROPRIATE
 LITERATURE FOR THE TYPE OF LIFT TO BE INSTALLED.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 4) THE SHEET A-2.2 DATED 2/10/2021 SHOWER STAIRS TO
 CHOIR LOFT TO BE DEMOLISHED, WOOD PLATFORM FRAME OVER
 EXISTING METAL POST TO REMAIN, THIS WAS THE SHEET THAT
 WAS PERMITTED, NO STAIRWAY TO THE CHOIR LOFT.
 THIS REVISION # 2 SHEETS A5.1 AND A-7.1 AND OTHER
 SHEETS SHOW A NEW SPIRAL STAIRWAY FROM THE BASEMENT
 LEVEL, TO FIRST FLOOR AND TO THE CHOIR LOFT. NEITHER
 LIFE SAFETY SHEET A.3.3 LIFE SAFETY SHEET BASEMENT NOR
 A3.4 THE FIRST FLOOR LIFE SAFETY SHEET SHOW THE SPIRAL
 STAIR PART OF THE LIFE SAFETY PLAN.
  
 4A) THE DOORS LEADING THE STAIRWAY VERTICAL SHAFT DO
 NOT GIVE ANY SIZE NOR FIRE RATING. 2017 FBC-B 1010.1.1
 AND TABLE 716.5 OPENING PROTECTIVES.
  
 4B) THE COVERSHEET NOR ANY LIFE SAFETY SHEET GIVE THE
 OCCUPANT LOAD OF THE CHOIR LOFT, THIS IS NEEDED TO
 DETERMINE THE OCCUPANT LOAD TO USE THE STAIR TO THE
 CHOIR LOFT. 107.2.1.2. ADDITIONAL INFORMATION REQUIRED.
 PLEASE SHOW COMPLIANCE FOR 1011.10 SPIRAL STAIRWAY AND
 AN OCCUPANT LOAD OF NOT MORE THAN 5 OCCUPNTS.
  
 4C) IF THE SPIRAL STAIRCASE CAN BE CONSIDERED A MEANS
 OF EGRESS PLEASE PROVIDE SHOP DRAWINGS IN COMPLIANCE
 WITH 1011. 10 & 1011.11.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-19 Cont ID  
Sent By jleahy Date 2022-01-19 Time 10:52 Rev Time 0.00
Received By jleahy Date 2022-01-19 Time 09:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-02-28 Cont ID  
Sent By pleduc Date 2022-02-28 Time   Rev Time 0.00
Received By pleduc Date 2022-02-28 Time 11:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-02-11 Cont ID  
Sent By pleduc Date 2022-02-11 Time   Rev Time 0.00
Received By pleduc Date 2022-02-11 Time 11:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-07 Cont ID  
Sent By pleduc Date 2022-02-07 Time   Rev Time 0.00
Received By pleduc Date 2022-02-07 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-12-22 Cont ID  
Sent By pleduc Date 2021-12-22 Time   Rev Time 0.00
Received By pleduc Date 2021-12-21 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 17:24 Rev Time 0.00
Received By medwards Date 2022-05-12 Time 08:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 17:11 Rev Time 0.00
Received By medwards Date 2022-04-10 Time 08:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 09:03 Rev Time 0.00
Received By medwards Date 2022-02-27 Time 08:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-22 Cont ID  
Sent By medwards Date 2022-02-22 Time 17:23 Rev Time 0.00
Received By medwards Date 2022-02-06 Time 09:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-19 Cont ID  
Sent By jleahy Date 2022-01-19 Time 10:53 Rev Time 0.00
Received By jleahy Date 2021-12-15 Time 14:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 17:23 Rev Time 0.00
Received By medwards Date 2022-05-24 Time 17:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 16:57 Rev Time 0.00
Received By medwards Date 2022-04-26 Time 16:57 Sent To  
Notes
2022-04-26 17:10:511ST REVIEW FMC
 PERMIT: 21120607
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE RESPONSE LETTER REFERENCED IN THE RESUBMITTAL
 LETTER WAS NOT INCLUDED. THERE IS A NOTE ON SHEET M02
 THAT STATES THE ROOM WILL NOT HAVE MORE THAN 63
 OCCUPANTS IN ACCORDANCE WITH THE OWNER?S DESIGN
 REQUIREMENTS AND STATISTICAL DATA. THE STATISTICAL DATA
 WILL NEED TO BE INCLUDED IN THE RESUBMITTAL FOR REVIEW.
 SEE EXCEPTION BELOW
  
 403.3.1.1 EXCEPTION: THE OCCUPANT LOAD IS NOT REQUIRED
 TO BE DETERMINED BASED ON THE ESTIMATED MAXIMUM
 OCCUPANT LOAD RATE INDICATED IN TABLE 403.3.1.1 WHERE
 APPROVED STATISTICAL DATA DOCUMENT THE ACCURACY OF
 AN ALTERNATE ANTICIPATED OCCUPANT DENSITY.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 08:31 Rev Time 0.00
Received By medwards Date 2022-03-10 Time 08:31 Sent To  
Notes
2022-03-10 08:37:31SHEET M1.1 INDICATES THAT THE OAF-1 IS INTRODUCING 1000
 CFM'S OF OUTDOOR AIR TO THE SOCIAL HALL. FBC M SECTION
 403.3.1.1 TELLS US THAT WE MUST USE TABLE 403.3.1.1 TO
 DETERMINE HOW MUCH OUTDOOR AIR IS REQUIRED FOR EACH USE
 OF SPACE, BASED ON THE SQURE FOOTAGE AND THE USE OF
 SPACE IS A MULTI-USE ASSEMBLY THE REQUIRED OUTDOOR AIR
 WILL BE 1,514 CFM'S. UNLESS THE ENGINEER DESIGNS A
 SYSTEM BASED ON THE EXCEPTION OF FBC M 403.2 THE
 OUTDOOR AIR REQUIRED WILL BE 1,514 CFM'S FOR THIS
 SPACE.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-22 Cont ID  
Sent By medwards Date 2022-02-22 Time 17:18 Rev Time 0.00
Received By medwards Date 2022-02-22 Time 17:16 Sent To  
Notes
2022-02-22 17:17:15YOUR RESPONSE FOR PREVIOUS COMMENT 5 BELOW DOES NOT
 MAKE SENSE AS THE SHEET REFERENCED IN YOUR COMMENT DOES
 NOT EXIST IN THIS PACKAGE AND THERE ARE SEVERAL UNITS
 CONDITIONING THE SOCIAL HALL, SOME ARE NOT LISTED IN
 YOUR RESPONSE.
  
 5) SHEET M11 DETAIL 5 SHEET M1.3 IS NOT IN THIS
 PACKAGE. PLEASE PROVIDE A DETAIL OF HOW THE OUTDOOR AIR
 WILL BE CONDITIONED BEFORE IT ENTERS THE SPACE. FBC
 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-20 Cont ID  
Sent By medwards Date 2021-12-20 Time 17:10 Rev Time 0.00
Received By medwards Date 2021-12-20 Time 17:09 Sent To  
Notes
2021-12-20 17:10:201ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120607
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2: IN THE VENTILATION CALCULATIONS, PLEASE
 REFERENCE THE 2020 FBC MECHANICAL CODE. THE ASHRAE
 170-2017 IS FOR HEALTH CARE FACILITIES, PLEASE EXPLAIN
 HOW THIS APPLIES TO THIS OCCUPANCY.
  
 2) SHEET M0.2: VENTILATION CALCULATIONS: THE MEETING
 ROOM APPEARS TO BE CALCULATED AS A CONFERENCE ROOM,
 THIS AREA SHOULD BE CALCULATED AS A MULTIUSE ASSEMBLY.
 FBC M TABLE 403.3.1.1
  
 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC C403.2.1
  
 4) PLEASE MAKE SURE ALL OUTDOOR AIR INTAKES ARE 10 FEET
 FROM EXHAUST TERMINATIONS. FBC M 401.4-2
  
 5) SHEET M11 DETAIL 5 SHEET M1.3 IS NOT IN THIS
 PACKAGE. PLEASE PROVIDE A DETAIL OF HOW THE OUTDOOR AIR
 WILL BE CONDITIONED BEFORE IT ENTERS THE SPACE. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2022-05-23 Cont ID  
Sent By ccole Date 2022-05-23 Time 14:37 Rev Time 0.00
Received By ccole Date 2022-05-23 Time 14:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2022-04-25 Cont ID  
Sent By ccole Date 2022-04-25 Time 13:34 Rev Time 0.00
Received By ccole Date 2022-04-25 Time 11:06 Sent To  
Notes
2022-04-25 13:35:123RD REVIEW FBC-2017 PLUMBING
 PERMIT- 21120607
 4/25/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-3.1: REFER TO SEC. 403.2 FBC P SEPARATE
 FACILITES- TWO FEMALE WATER CLOSETS ARE REQUIRED. WHERE
 IT IS SHOWN ON THE PLANS PLEASE LABEL THE UNISEX TOILET
 ROOM AS FEMALE TO MEET THE REQUIREMENT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-03-02 Cont ID  
Sent By ccole Date 2022-03-02 Time 14:29 Rev Time 0.00
Received By ccole Date 2022-03-02 Time 14:29 Sent To  
Notes
2022-03-02 14:31:172ND REVIEW FBC-2017 PLUMBING
 PERMIT- 21120607
 2/16/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. FAILED IST AND 2ND REVIEW
 COMMENTS LISTED BELOW.
  
 1) 2ND REQUEST- FAILED. SHEET A-3.1: THE PLUMBING
 FIXTURE CALCULATIONS DO NOT INCLUDE THE REQUIRED
 SERVICE SINKS AND DRINKING FOUNTAINS, AND THEIR
 LOCATIONS ARE NOT SHOWN ON THE PLANS- TABLE 403.1 FBC
 P. PLEASE REVISE THE PLANS TO INCLUDE THE REQUIRED
 FIXTURES. THE CALCULATIONS FOR A3 SHOWN ON THE PLAN ARE
 INCORRECT. FEMALE WATER CLOSETS ARE CALCULATED AT 1 PER
 75 FOR CHURCHES- TABLE 403.1 FBC P. THE 2ND REQUIRED
 FEMALE WATER CLOSET PREVIOUSLY SHOWN IN THE
 CALCULATIONS WAS REMOVED FROM THE RESUBMITTED PLAN.
  
 3) 2ND REQUEST- FAILED SHEET A-7.4 ITEMS C, D, & E.
 A-7.4:
 C) FAILED. HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- 606.3. NOT PROVIDED.
 D) FAILED. HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3. THE
 MEASUREMENT SHOWN IS TO THE MIRROR FRAME, NOT THE
 REFLECTIVE SURFACE.
 E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THE 2'11"
 MEASUREMENT IN ELEV. 3 IS SHOWN TO THE CENTER OF THE
 GRAB BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE.
 NOTE- THE GRAB BARS LISTED IN THE SCHEDULE DO NOT MATCH
 THE GRAB BARS IN THE DRAWINGS. PLEASE SEE FIGURES
 604.5.1 & 604.5.2 FBC ACC: SHOW THE 12-INCH MAX SPACING
 AND MIN. 54-INCH EXTENSION FOR THE SIDE GRAB BAR, AND
 SHOW THE REAR GRAB BAR WILL EXTEND MIN. 12-INCHES ONE
 WAY FROM THE CENTERLINE OF THE WATER CLOSET, AND MIN.
 24-INCHES FROM THE CENTERLINE TO THE OPEN SIDE.
  
 4) 2ND REQUEST FAILED SHEET A7.4- ITEMS A, C, D, E, F,
 & H: PLEASE PROVIDE AN ENLARGED DRAWING OF THE PRIEST
 OFFICE BATHROOM WITH FIXTURE AND ACCESSORY ELEVATION
 DETAILS. PLEASE NOTE THAT PRIVATE BATHROOMS CONSTRUCTED
 UNDER THE FBC ACC SHALL BE IN COMPLIANCE WITH THE
 FOLLOWING CODE SECTIONS:
 A) FAILED. CLEAR FLOOR SPACES FOR WATER CLOSETS- SEC.
 604.3. MINIMUM 56-INCHES DEEP X 60-INCHES WIDE SPACE
 REQUIRED.
 B) FAILED. CLEAR FLOOR SPACES FOR LAVATORIES- SEC.
 606.2. THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE- SEC. 603.2.3.
 C) FAILED. CENTERLINE OF THE WATER CLOSET FROM THE SIDE
 WALL- SEC.604.2. THE WATER CLOSET IS NOT POSITIONED AT
 THE SIDE WALL.
 D) FAILED. HEIGHT OF MIRROR FROM FINISHED FLOOR TO
 REFLECTIVE SURFACE- SEC. 603.3. ELEVATION DETAIL DOES
 NOT PROVIDE A MEASUREMENT.
 E) FAILED. REINFORCEMENT LOCATIONS FOR FUTURE GRAB BARS
 AT WATER CLOSETS- SEC. 604.5 EXCEPTION 1. WATER CLOSET
 NOT POSITIONED FOR A FUTURE SIDE WALL GRAB BAR TO BE
 PROVIDED
 F) FAILED. SHOWER TYPE, SHOWER DIMENSIONS, CLEAR FLOOR
 SPACE FOR SHOWER, CONTROLS LOCATIONS, AND REINFORCEMENT
 LOCATIONS FOR FUTURE GRAB BARS- SECS. 608.1- 608.7. THE
 SHOWER IS NOT SET UP FOR ACCESSIBLE USE ACCORDING TO
 SECS- 608.1- 608.7
 H) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONT OF THE WATER CLOSET- SEC. AND
 FIGURE 604.7. WATER CLOSET AND TP DISPENSER NOT
 POSITIONED AT SIDE WALL.
  
 13) 2ND REQUEST- FAILED SHEET P0.1: PROVIDE SHOWER PAN
 DRAIN, LINER, AND WALL FINISH DETAILS- SECS. 417.3,
 417.4.1, & 417.5.2 FBC P. NOT PROVIDED. PLEASE NOTE
 THAT THE 3'-4" CERAMIC WALL HEIGHTS SHOWN ON SHEET A7.4
 ARE NOT IN COMPLIANCE WITH SEC. 1210.2.2 FBC B WHICH
 REQUIRES THE TILE TO BE 4FT. IN HEIGHT AT THE WATER
 CLOSETS.
  
 NEW COMMENT
 1) SHEETS P0.1 & P0.2: REFER TO SEC. 607.1.1 FBC P AND
 PROVIDE EITHER A MASTER THERMOSTATIC MIXING VALVE AT
 THE WATER HEATER OR INDIVIDUAL MIXING VALVES AT
 FIXTURES SUPPLYING HOT WATER INCLUDING THE HAND SINKS,
 MOP SINKS, AND 3-COMPARTMENT SINKS. PLEASE NOTE THE
 LAVATORY SINKS ARE APPROVED FOR DELIVERY OF TEMPERED
 WATER USING THE ASSE 1070 MIXING VALVES.
  
 2) DRINKING FOUNTAINS: REFER TO SECTIONS 306, 307, AND
 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION
 DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE
 CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW
 THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-02-16 Cont ID  
Sent By ccole Date 2022-02-16 Time 10:17 Rev Time 0.00
Received By ccole Date 2022-02-16 Time 06:53 Sent To  
Notes
2022-02-16 10:19:252ND REVIEW FBC-2017 PLUMBING
 PERMIT- 21120607
 2/16/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES FOR
 FURTHER CLARIFICATION. CONCERNING THE ACCESSIBILITY
 FAILURES LISTED BELOW IT?S IMPORTANT TO NOTE THAT
 CHURCHES ARE EXEMPT FROM MEETING ADA REQUIRMENTS
 HOWEVER THE ARCHITECT IS CHOOSING TO COMPLY WITH THE
 FLORIDA ACCESSIBILTY CODE- 2017. PLEASE REVIEW SEC.
 101.1.4 FBC ACC: "THIS CODE IS NOT INTENDED TO EXPAND
 OR DIMINISH THE DEFENSES AVAILABLE TO A PLACE OF PUBLIC
 ACCOMMODATION OR A COMMERCIAL FACILITY UNDER THE
 AMERICANS WITH DISABILITIES ACT AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN, INCLUDING, BUT NOT LIMITED TO,
 THE READILY ACHIEVABLE STANDARD, AND THE STANDARDS
 APPLICABLE TO ALTERATIONS TO PLACES OF PUBLIC
 ACCOMMODATION AND COMMERCIAL FACILITIES."
 THE ARCHITECT SHOULD CLARIFY ON THE PLANS IF EXEMPTION
 IS BEING CLAIMED FOR THE CHURCH, HOWEVER THE CURRENT
 REVIEW WILL REMAIN BASED ON THE FBC ACC UNTIL FURTHER
 INFORMATION IS PROVIDED.
  
 1) FAILED. SHEET A-3.1: THE PLUMBING FIXTURE
 CALCULATIONS DO NOT INCLUDE THE REQUIRED SERVICE SINKS
 AND DRINKING FOUNTAINS, AND THEIR LOCATIONS ARE NOT
 SHOWN ON THE PLANS- TABLE 403.1 FBC P. PLEASE REVISE
 THE PLANS TO INCLUDE THE REQUIRED FIXTURES. THE 2ND
 REQUIRED FEMALE WATER CLOSET PREVIOUSLY SHOWN IN THE
 CALCULATIONS WAS REMOVED FROM THE RESUBMITTED PLAN.
 REFER TO TABLE 403.1 FBC P- 2 FEMALE WATER CLOSETS ARE
 REQUIRED, HOWEVER ONLY 1 IS SHOWN. PLEASE INDICATE HOW
 THE PLAN IS MEETING COMPLIANCE.
  
 3) FAILED ITEMS C, D, & E. A-7.4: PLEASE INDICATE WHICH
 CODE IS BEING USED TO DESIGN THE MEN'S AND WOMEN'S
 HANDICAP BATHROOMS. ADA IS NOTED IN THE DETAILS HOWEVER
 SHEET A-3.3 INDICATES THE PLANS HAVE BEEN DESIGNED IN
 ACCORDANCE WITH FLORIDA BUILDING CODE- 2017. THE FBC-17
 INCLUDES FLORIDA ACCESSIBILITY CODE- 2017. PLEASE
 REVIEW SEE THE LIST OF FBC ACC COMPLIANCES BELOW AND
 REVISE THE PLAN:
 C) FAILED. HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- 606.3. NOT PROVIDED.
 D) FAILED. HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS TO THE REFLECTIVE SURFACES- SEC. 603.3. THE
 MEASUREMENT SHOWN IS TO THE MIRROR FRAME, NOT THE
 REFLECTIVE SURFACE.
 E) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THE 2'11"
 MEASUREMENT IN ELEV. 3 IS SHOWN TO THE CENTER OF THE
 GRAB BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE.
 NOTE- THE GRAB BARS LISTED IN THE SCHEDULE DO NOT MATCH
 THE GRAB BARS IN THE DRAWINGS. PLEASE SEE FIGURES
 604.5.1 & 604.5.2 FBC ACC: SHOW THE 12-INCH MAX SPACING
 AND MIN. 54-INCH EXTENSION FOR THE SIDE GRAB BAR, AND
 SHOW THE REAR GRAB BAR WILL EXTEND MIN. 12-INCHES ONE
 WAY FROM THE CENTERLINE OF THE WATER CLOSET, AND MIN.
 24-INCHES FROM THE CENTERLINE TO THE OPEN SIDE.
  
 4) FAILED. ITEMS A, C, D, E, F, & H. A-7.4: PLEASE
 PROVIDE AN ENLARGED DRAWING OF THE PRIEST OFFICE
 BATHROOM WITH FIXTURE AND ACCESSORY ELEVATION DETAILS.
 PLEASE NOTE THAT PRIVATE BATHROOMS CONSTRUCTED UNDER
 THE FBC ACC SHALL BE IN COMPLIANCE WITH THE FOLLOWING
 CODE SECTIONS:
 A) FAILED. CLEAR FLOOR SPACES FOR WATER CLOSETS- SEC.
 604.3. MINIMUM 56-INCHES DEEP X 60-INCHES WIDE SPACE
 REQUIRED.
 B) FAILED. CLEAR FLOOR SPACES FOR LAVATORIES- SEC.
 606.2. THE DOOR SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE- SEC. 603.2.3.
 C) FAILED. CENTERLINE OF THE WATER CLOSET FROM THE SIDE
 WALL- SEC.604.2. THE WATER CLOSET IS NOT POSITIONED AT
 THE SIDE WALL.
 D) FAILED. HEIGHT OF MIRROR FROM FINISHED FLOOR TO
 REFLECTIVE SURFACE- SEC. 603.3. ELEVATION DETAIL DOES
 NOT PROVIDE A MEASUREMENT.
 E) FAILED. REINFORCEMENT LOCATIONS FOR FUTURE GRAB BARS
 AT WATER CLOSETS- SEC. 604.5 EXCEPTION 1. WATER CLOSET
 NOT POSITIONED FOR A FUTURE SIDE WALL GRAB BAR TO BE
 PROVIDED
 F) FAILED. SHOWER TYPE, SHOWER DIMENSIONS, CLEAR FLOOR
 SPACE FOR SHOWER, CONTROLS LOCATIONS, AND REINFORCEMENT
 LOCATIONS FOR FUTURE GRAB BARS- SECS. 608.1- 608.7. THE
 SHOWER IS NOT SET UP FOR ACCESSIBLE USE ACCORDING TO
 SECS- 608.1- 608.7
 H) FAILED. CENTERLINE OF THE TOILET PAPER DISPENSER
 MEASURED FROM THE FRONT OF THE WATER CLOSET- SEC. AND
 FIGURE 604.7. WATER CLOSET AND TP DISPENSER NOT
 POSITIONED AT SIDE WALL.
  
 5) FAILED. A-7.4: IN STANDARD TOILET ROOMS THE WATER
 CLOSET AND VANITY SHALL NOT BE CLOSER THAN 30 INCHES
 CENTER TO CENTER- SEC. 405.3.1 FBC P. THE UNISEX PLAN
 SHOWS 28 INCHES. THE CORRECTED PLAN SHOWS THE LAVATORY
 SINK CENTERED AT 14-INCHES FROM THE SIDE WALL HOWEVER
 THE MINIMUM IS 15-INCHES. PLEASE CLARIFY THE DESIGN
 INTENTION CONCERNING THE FAMILY RESTROOM. IT IS NOT
 SHOWN TO BE ACCESSIBLE LIKE THE MEN'S AND WOMEN'S
 RESTROOMS.
  
 13) FAILED. P0.1: PROVIDE SHOWER PAN DRAIN, LINER, AND
 WALL FINISH DETAILS- SECS. 417.3, 417.4.1, & 417.5.2
 FBC P. NOT PROVIDED. PLEASE NOTE THAT THE 3'-4" CERAMIC
 WALL HEIGHTS SHOWN ON SHEET A7.4 ARE NOT IN COMPLIANCE
 WITH SEC. 1210.2.2 FBC B WHICH REQUIRES THE TILE TO BE
 4FT. IN HEIGHT AT THE WATER CLOSETS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-30 Cont ID  
Sent By ccole Date 2021-12-30 Time 11:05 Rev Time 0.00
Received By ccole Date 2021-12-29 Time 16:29 Sent To  
Notes
2021-12-30 11:05:281ST REVIEW FBC-2017 PLUMBING
 PERMIT- 21120607
 12/30/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-3.1: THE PLUMBING FIXTURE CALCULATIONS DO
 NOT INCLUDE THE REQUIRED SERVICE SINKS AND DRINKING
 FOUNTAINS, AND THEIR LOCATIONS ARE NOT SHOWN ON THE
 PLANS- TABLE 403.1 FBC P. PLEASE REVISE THE PLANS TO
 INCLUDE THE REQUIRED FIXTURES.
  
 2) SHEET A3.1 & A-3.3: LABEL THE TOILETS ROOMS AS MALE,
 FEMALE, FAMILY, OR ASSISTED USE IN ACCORDANCE WITH
 SECS. 403.1.2 & 403.2 FBC P. PLEASE REMOVE THE
 "EXISTING TOILET ROOM TO REMAIN" NOTES. THE DEMOLITION,
 ARCHITECTURAL AND PLUMBING PLANS INDICATE NEW TOILET
 ROOMS- SEC. 107.2.1 WPB.
  
 3) A-7.4: PLEASE INDICATE WHICH CODE IS BEING USED TO
 DESIGN THE MEN'S AND WOMEN'S HANDICAP BATHROOMS. ADA IS
 NOTED IN THE DETAILS HOWEVER SHEET A-3.3 INDICATES THE
 PLANS HAVE BEEN DESIGNED IN ACCORDANCE WITH FLORIDA
 BUILDING CODE- 2017. THE FBC-17 INCLUDES FLORIDA
 ACCESSIBILITY CODE- 2017. PLEASE REVIEW SEE THE LIST OF
 FBC ACC COMPLIANCES BELOW AND REVISE THE PLAN:
 A) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 SHALL BE 16 INCHES MINIMUM TO 18 INCHES MAXIMUM- SEC.
 604.2. THE PLAN SHOWS 19-1/2-INCHES.
 B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS SHALL 17 INCHES MINIMUM AND 19 INCHES MAXIMUM TO
 THE TOP OF THE SEAT- 604.4.
 C) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER
 SURFACES FROM THE FINISHED FLOORS- 606.3.
 D) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. PLEASE NOTE THE 2'11"
 MEASUREMENT IN ELEV. 3 IS SHOWN TO THE CENTER OF THE
 GRAB BAR AND NOT TO THE TOP OF THE GRIPPING SURFACE.
 NOTE- THE GRAB BARS LISTED IN THE SCHEDULE DO NOT MATCH
 THE GRAB BARS IN THE DRAWINGS.
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS SHALL
 BE ON THE OPEN SIDES OF THE WATER CLOSETS, NOT ON THE
 CLOSED SIDES- 604.6.
 G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE
 604.7.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC.
 606.2 AND FIGURES 306.2 & 306.3.
 I) REACH HANDLE HEIGHTS OF THE DIAPER CHANGING STATIONS
 IN THE CLOSED POSITIONS, AND THE HAND TOWEL DISPENSERS
 (NOTE- DISPENSER LOCATIONS NOT SHOWN IN THE DRAWINGS)-
 SEC. 308.
  
 4) A-7.4: PLEASE PROVIDE AN ENLARGED DRAWING OF THE
 PRIEST OFFICE BATHROOM WITH FIXTURE AND ACCESSORY
 ELEVATION DETAILS. PLEASE NOTE THAT PRIVATE BATHROOMS
 CONSTRUCTED UNDER THE FBC ACC SHALL BE IN COMPLIANCE
 WITH THE FOLLOWING CODE SECTIONS:
 A) CLEAR FLOOR SPACES FOR WATER CLOSETS- SEC. 604.3.
 B) CLEAR FLOOR SPACES FOR LAVATORIES- SEC. 606.2.
 C) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SEC.604.2.
 D) HEIGHT OF MIRROR FROM FINISHED FLOOR TO REFLECTIVE
 SURFACE- SEC. 603.3
 E) REINFORCEMENT LOCATIONS FOR FUTURE GRAB BARS AT
 WATER CLOSETS- SEC. 604.5 EXCEPTION 1.
 F) SHOWER TYPE, SHOWER DIMENSIONS, CLEAR FLOOR SPACE
 FOR SHOWER, CONTROLS LOCATIONS, AND REINFORCEMENT
 LOCATIONS FOR FUTURE GRAB BARS- SECS. 608.1- 608.7.
 G) LOCATION OF THE WATER CLOSET FLUSH CONTROL- SEC.
 604.6.
 H) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SEC. AND FIGURE
 604.7.
  
 5) A-7.4: IN STANDARD TOILET ROOMS THE WATER CLOSET AND
 VANITY SHALL NOT BE CLOSER THAN 30 INCHES CENTER TO
 CENTER- SEC. 405.3.1 FBC P. THE UNISEX PLAN SHOWS 28
 INCHES.
  
 6) P0.1, P0.2, & P1.1: SINKS AND DISHWASHERS IN FOOD
 PREP AREAS SHALL DISCHARGE THROUGH AN INDIRECT WASTE
 PIPE INTO APPROVED WASTE RECEPTORS- SECS. 802.1,
 802.1.1, 802.1.6, 802.1.7, 802.2, AND 802.3 FBC P.
 PLEASE REVISE THE PLANS ACCORDINGLY.
  
 7) P0.1, P0.2, & P1.1: A GREASE INTERCEPTOR IS REQUIRED
 TO RECEIVE THE DRAINAGE FROM THE SINK AND DISHWASHER IN
 THE FOOD PREP AREAS- SEC. 1003.3.1 FBC P. INSTALLATION
 OF THE INTERCEPTOR SHALL BE UNDER SEPARATE PERMIT- SEC.
 105.1 WPB.
 A) REVISE THE PLANS TO SHOW THE LOCATION OF THE
 INTERCEPTOR AND PLUMBING PIPING REQUIREMENTS. SHOW THE
 GREASE WASTE PIPING RUNS FROM THE FIXTURES TO THE
 INTERCEPTOR AND FROM THE INTERCEPTOR TO POINT OF
 CONNECTION TO THE EXISTING BUILDING OR SEWER DRAIN.
 SHOW LOCATIONS OF ALL REQUIRED CLEANOUTS AND VENTS PER
 MANUFACTURER'S SPECIFICATIONS- SECTION 1003.3.4 FBC P
 AND SECTION 107.2.1 WPB.
 B) PROVIDE GREASE WASTE CALCULATIONS AND INTERCEPTOR
 EQUIPMENT SCHEDULE ON THE PLAN IN COMPLIANCE WITH
 SECTION 1003.3.5 FBC P.
  
 8) P0.1: PLEASE INCLUDE THE TOILET ROOM, BATHROOM, FOOD
 PREP, AND SACRISTY FIXTURES AND FAUCETS IN THE
 SCHEDULE- SEC. 107.2.1 WPB AND TABLE 604.5 FBC P.
  
 9) P0.1: PLEASE INCLUDE THE EFFICIENCY RATING OF THE
 WATER HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 10) P0.1, P1.0 & P1.1: SHOW THE WATER HEATER PAN DRAIN
 LINE RUN TO DISCHARGE LOCATION- SEC. 504.7.2 FBC P.
  
 11) P1.0 & P1.1: THE 1/2-INCH HOT WATER SUPPLY PIPES TO
 THE LAVATORIES ARE EXCEEDING THE MAXIMUM 2 FT. LENGTHS
 ALLOWED FROM THE NEAREST HOT WATER SOURCE TO THE
 FIXTURE SUPPLY PIPE TERMINATION POINT- SEC. C404.5.1
 FBC EC. EITHER PROVIDE RECIRCULATION LOOPS AT THE
 LAVATORIES OR POINT OF USE WATER HEATERS.
  
 12) P0.1, P1.0, & P1.1: INDICATE HOW TEMPERED WATER
 WILL BE DELIVERED FROM THE LAVATORIES- SEC. 416.5 FBC
 P.
  
 13) P0.1: PROVIDE SHOWER PAN DRAIN, LINER, AND WALL
 FINSIH DETAILS- SECS. 417.3, 417.4.1, & 417.5.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 17:24 Rev Time 0.00
Received By medwards Date 2022-05-24 Time 17:24 Sent To  
Notes
2022-05-17 09:43:205/17/22 ARCHITECTURAL SHEETS DIGITALLY SIGNED & SEALED.
 JW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 17:11 Rev Time 0.00
Received By medwards Date 2022-04-26 Time 17:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-10 Cont ID  
Sent By medwards Date 2022-03-10 Time 09:02 Rev Time 0.00
Received By medwards Date 2022-03-10 Time 09:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-22 Cont ID  
Sent By medwards Date 2022-02-22 Time 17:23 Rev Time 0.00
Received By medwards Date 2022-02-22 Time 17:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-19 Cont ID  
Sent By jleahy Date 2022-01-19 Time 10:53 Rev Time 0.00
Received By jleahy Date 2022-01-19 Time 10:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-03-02 Cont ID  
Sent By vbroglia Date 2022-03-02 Time 14:12 Rev Time 0.00
Received By vbroglia Date 2022-03-02 Time 14:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-02-11 Cont ID  
Sent By vbroglia Date 2022-02-11 Time 14:39 Rev Time 0.00
Received By vbroglia Date 2022-02-11 Time 14:39 Sent To  
Notes
2022-02-11 14:55:042/11/22 FAILED- DEMOLATION PERMITS NEEDED BEFORE TO
 ALLOW STAFF TO MOVE FORWARD
  
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-28 Cont ID  
Sent By vbroglia Date 2021-12-28 Time 09:52 Rev Time 0.00
Received By vbroglia Date 2021-12-28 Time 09:52 Sent To  
Notes
2021-12-28 09:57:2512/28/21 FAILED.
  
 PLEASE PROVIDE A SEPRATE PERMIT FOR EACH PROPOSED
 DEVELOPMENT. SEPRATE PERMITS REQUIRED FOR FENCE,
 LANDSCAPE, PARKING LOT, NEW ADDITIONS, ECT.
  
 PLEASE PROVIDE THE SETBACKS OF THE PRINCIPLE BUIDLING
 AND PROPOSED ADDITION, DIMENSIONS OF PARKING SPACE AND
 FENCE HEIGHT.
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  
  
  