Plan Review Details - Permit 21120574
Plan Review Stops For Permit 21120574
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-03-11 Cont ID  
Sent By cpuell Date 2022-03-11 Time 16:02 Rev Time 0.00
Received By cpuell Date 2022-03-11 Time 16:02 Sent To  
Notes
2022-03-11 16:02:30ADDRESS APPROPRIATE FOR PROJECT.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-06-27 Cont ID  
Sent By sberglun Date 2022-06-27 Time 11:47 Rev Time 0.00
Received By sberglun Date 2022-06-27 Time 11:47 Sent To  
Notes
2022-06-27 11:47:371) CITY UTILITIES ARE SHOWN INCORRECTLY ON PLANS.
 PLEASE CONTACT JANICE TARBILL, [email protected] FOR
 AS-BUILT INFORMATION. PLEASE INCLUDE AS-BUILT
 INFORMATION IN YOUR RESUBMITTAL.
 2) PLEASE PROVIDE PROFILE FOR PROPOSED UNDERGROUND
 ELECTRIC SHOWING ALL CROSSING DATA FOR OTHER UTILITIES.
 3) ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE
 REQUIRED PER CITY STANDARD.
  
 SUZANNE BERGLUND
 [email protected]
 561-494-1075
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-27 Cont ID  
Sent By lmarchan Date 2022-06-27 Time 15:50 Rev Time 0.00
Received By lmarchan Date 2021-12-13 Time 12:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-17 Cont ID  
Sent By shill Date 2021-12-17 Time 12:56 Rev Time 0.00
Received By shill Date 2021-12-17 Time 12:56 Sent To  
Notes
2021-12-17 12:57:01SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMUNICATIONS APPLICATIONS - NEW PROCESS EFFECTIVE
 12/6/2021
  
 1. FOR ALL FUTURE SUBMITTALS, PRIOR TO SUBMISSION,
 CONTACT [email protected] TO OBTAIN THE CORRECT ADDRESS
 FOR YOUR APPLICATION. SHE WILL ASSIGN AN ADDRESS VIA
 EMAIL. WHEN YOU SUBMIT THE APPLICATION, INCLUDE THE
 EMAIL AS AN ATTACHMENT.
  
 2. FOR ALL FUTURE SUBMITTALS, TO SUBMIT THE
 COMMUNICATIONS APPLICATION, EMAIL THE COMPLETED
 APPLICATION TO [email protected]. THEY WILL
 GENERATE YOUR APPLICATION AND SEND YOU INSTRUCTIONS TO
 UPLOAD YOUR PLANS.
  
 3. FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS. IT APPEARS THAT THE
 DOCUMENTS SUBMITTED PAPER TO THE BUILDING DIVISION WERE
 DIGITALLY SIGNED PLANS THAT WERE PRINTED.
  
 IF THIS APPLICATION FAILS REVIEW - WHEN RESUBMITTING,
 UPLOAD INDIVIDUALLY SIGNED AND SEALED DRAWINGS IF
 POSSIBLE. IF YOU CANNOT OBTAIN PLANS IN THAT FORMAT,
 UPLOAD THE SINGLE MULTIPAGE DIGITALY SIGNED PDF TO THE
 SIGNATURE FOLDER.
  
 IF THIS APPLICATION PASSES REVIEW - UPLOAD THE
 DIGITALLY SIGNED DOCUMENTS (SHOULD BE IDENTICAL TO THE
 DOCUMENTS REVIEWED) TO THE SIGNATURE FOLDER.
  
 IF THE ENGINEER DOES NOT HAVE A DIGITAL SIGNATURE,
 PLEASE CONTACT ME DIRECTLY TO DISCUSS OPTIONS.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-03-10 Cont ID  
Sent By eshneide Date 2022-03-10 Time 17:27 Rev Time 0.25
Received By eschneid Date 2022-03-10 Time 17:27 Sent To  
Notes
2022-03-10 17:28:08INSUFFICIENT
  
 1) THIS LOCATION IS WITHIN A HISTORIC DISTRICT. PLEASE
 PROVIDE A COPY OF THE STATE HISTORIC PRESERVATION
 OFFICE APPROVAL OF THIS LOCATION.
  
 2) THE SURVEY AND ENGINEERING PLANS REFERENCE A WOOD
 DISTRIBUTION POLE TO ESTABLISH THE HEIGHT OF A NEARBY
 POLE TO JUSTIFY THE HEIGHT OF THE PROPOSED WIRELESS
 FACILITY POLE; HOWEVER, THE GOOGLE STREET VIEW SHOWS
 THE POLE AS CONCRETE. THE CORRECT INFORMATION MUST BE
 PROVIDED ON THE SURVEY AND THE PLANS SO THAT STAFF CAN
 VERIFY COMPLIANCE WITH THE CODE REQUIREMENTS.
  
 3) THE PLANS DO NOT CLEARLY SHOW THE POLE BASE PLATE
 NOT ENCROACHING ON THE SIDEWALK. PLEASE PROVIDE
 VERIFICATION THAT THE EDGE OF THE BASE PLATE WILL NOT
 OVERLAP THE SIDEWALK.
  
 4) THE BORE PIT FOR THE HANDHOLE BY THE POLE NOTES ON
 SHEET P-1 STATE THAT THE SIDEWALK WILL BE RESTORED;
 HOWEVER, THE PARKWAY WHICH WILL NEED RESTORATION.
 PLEASE UPDATE THE NOTATIONS ACCORDINGLY.
  
 5) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC
 WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH
 EXISTING UTILITIES.
  
 6) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  