Plan Review Details - Permit 21120534
Plan Review Stops For Permit 21120534
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 12:52 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 12:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-29 Cont ID  
Sent By fgiaquin Date 2022-01-29 Time 19:43 Rev Time 0.00
Received By fgiaquin Date 2022-01-29 Time 18:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-09 Cont ID  
Sent By pleduc Date 2022-03-09 Time   Rev Time 0.00
Received By pleduc Date 2022-03-09 Time 10:26 Sent To  
Notes
2022-03-09 10:27:02FIRE PROVISO:
  
 THE A/C UNIT, DUCTWORK AND RCP WORK MAY INVOLVE
 SPRINKLER
 HEADS/PIPES, AS WELL AS, FIRE ALARM DEVICES/EQUIPMENT.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-01-12 Cont ID  
Sent By pleduc Date 2022-01-12 Time   Rev Time 0.00
Received By pleduc Date 2022-01-12 Time 10:53 Sent To  
Notes
2022-01-12 11:28:08FIRE PROVISO:
  
 THE A/C UNIT, DUCTWORK AND RCP WORK MAY INVOLVE
 SPRINKLER
 HEADS/PIPES, AS WELL AS, FIRE ALARM DEVICES/EQUIPMENT.
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-15 Cont ID  
Sent By medwards Date 2022-03-15 Time 11:47 Rev Time 0.00
Received By medwards Date 2022-03-08 Time 08:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-02-15 Cont ID  
Sent By lmarchan Date 2022-02-15 Time 09:03 Rev Time 0.00
Received By lmarchan Date 2022-01-11 Time 08:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-03-15 Cont ID  
Sent By medwards Date 2022-03-15 Time 11:38 Rev Time 0.00
Received By medwards Date 2022-03-15 Time 11:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By medwards Date 2022-01-14 Time 05:57 Rev Time 0.00
Received By medwards Date 2022-01-14 Time 05:57 Sent To  
Notes
2022-01-14 05:58:001ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120534
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REMOVE ALL ALTERNATES FROM THIS SHEET AS WE
 WILL REVIEW ONLY WHAT IS PERTINENT TO THIS PROJECT. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-15 Cont ID  
Sent By medwards Date 2022-03-15 Time 11:39 Rev Time 0.00
Received By medwards Date 2022-03-15 Time 11:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 12:57 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 12:57 Sent To  
Notes
2022-02-04 13:01:26SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING E1.0 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-02-15 Cont ID  
Sent By eschneid Date 2022-02-15 Time 08:54 Rev Time 0.25
Received By eschneid Date 2022-02-15 Time 08:54 Sent To  
Notes
***NONE***