Plan Review Details - Permit 21120532
| Plan Review Stops For Permit 21120532 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-14 |
Time |
15:12 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-14 |
Time |
15:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-02-10 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-10 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2022-02-10 12:30:45 | 2ND ELECTRIC REVIE FAILED | | | ELECTRIC REVIEW COMMENTS 2-7 HAVE BEEN ADEQUATELY | | | ADDRESSED | | | 1) COMMENT # 1 HAS NOT BEEN ADDRESSED . CONDUCTOR | | | AMPACITY MUST BE BASED ON 75 DEGREE C AS PER NEC | | | 110.14(C)(1)(B)(1).350 CU MCM AMPACITY DETAILED AS | | | 310-AMPS NEC 310.15(B)(16) THREE SETS OF CONDUCTORS | | | DOES NOT PROVIDE ADEQUATE AMPACITY FOR 1000-AMP | | | SERVICE. NEC 240.4(C). PLEASE CORRECT AS NESSECARY. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-04 |
Time |
10:09 |
Rev Time |
|
| Received By |
mpeterso |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-04 10:12:27 | ELECTRICAL PLAN REVIEW FAILED | | | 1) RISER DIAGRAM SHOWS WIRE SIZE FOR SERVICE ENTRANCE | | | AND CONDUCTORS FED FROM A 1000-AMP ADJUSTABLE TRIP | | | BREAKER TO BE (3) SETS OF 350 KCMIL WIRE. IF ASSUMED | | | THE CONDUCTOR IS COPPER (THE RISER DOES NOT STATE SUCH) | | | THE AMPACITY AT 75 DEGREE C IS 310- AMPS. 310X 3 = | | | 930-AMPS. NEC 210.240.4 (C) STATES CONDUCTORS WITH | | | OVERCURRENT DEVICES OVER 800-AMPS TO BE SIZED EQUAL TO, | | | OR ABOVE THE RATING OF THE OVERCURRENT DEVICE. PLEASE | | | CORRECT THE SIZE OF THE CONDUCTORS OR BREAKER SETTINGS | | | TO BE CODE COMPLIANT | | | 2) THE LABELING ON THE SERVICE MAIN STATES MAIN 3 OF 3. | | | IF THIS SERVICE IS THE ONLY ONE FEEDING THIS STRUCTURE, | | | PLEASE RE-LABEL IT ACCORDINGLY AND, OR, SHOW ALL OTHER | | | SERVICES THAT EXIST AND ARE TO REMAIN. | | | 3) DRAWING DO NOT STATE AVAILABLE FAULT CURRENT | | | AVAILABLE FOR EQUIPMENT AND SPD DEVICES AS PER NEC | | | 110.10, 110.24 AND NEC 285.7 | | | 4) PLEASE PROVIDE NOTES STATING, ?ARC FLASH? LABELING | | | IS TO BE INSTALLED AS PER NEC 110.16 | | | 5) PLEASE SHOW LOCATION OF PANEL ?B? ON SHEET ?E-3? FBC | | | 107.2 | | | 6) PLEASE CHANGE AC PANEL SCHEDULES TO REFLECT PANELS | | | C-H, NOT C-J. FBC 107.2 | | | 7) PLEASE PROVIDE SPECIFICATIONS FOR EMERGENCY LIGHTING | | | THAT CONFORMS TO 2020 FBC 1008.1 | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-14 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-08 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-10 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-10 |
Time |
12:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-04 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-13 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-03-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-09 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-09 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2022-03-09 07:50:37 | ORIGINAL SIGNED AND SEALED DRAWING (E-4) TO STORAGE |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-10 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-10 |
Time |
12:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-12-14 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-12-14 |
Time |
07:44 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-12-14 |
Time |
07:44 |
Sent To |
|
|
| Notes |
|
|
|