Plan Review Details - Permit 21120435
Plan Review Stops For Permit 21120435
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2022-08-31 Cont ID  
Sent By jgomez Date 2022-08-31 Time 11:20 Rev Time 0.00
Received By jgomez Date 2022-08-31 Time 11:19 Sent To  
Notes
2022-08-31 11:21:06BUILDING REVIEW APPROVED WITH PROVISO:
 NOTE: PROVIDE INFORMATION FOR REVIEW PRIOR TO
 INSTALLATION & INSPECTION TO AVOID CONFLICTS /DELAYS.
  
 1- DESIGN CRITERIA ON SHEET T-1: REVISE ROOF COMPONENTS
 & CLADDING DESIGN PRESSURES. TABLE R301.2(2) AND TABLE
 R301.2(3)FBC-RESIDENTIAL.
 2- PROVIDE COMPLETE DETAILS/SPECS FOR SECOND FLOOR WALL
 SEATING ON TOP OF EXISTING STRUCTURE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS (TOP & BOTTOM),
 INTERIOR/EXTERIOR CONSTRUCTION, INSULATION, ETC.
 3- GLAZING IN BALCONY GUARDRAIL: PROVIDE SIGNED/SEALED
 ENGINEERING (SHOP DRAWINGS) FOR GLAZED RAILINGS. SHOP
 DRAWINGS (REVIEWED BY ARCHITECT OF RECORD BEFORE
 SUBMITTAL). IMPORTANT NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H"
 4- BUILDING THERMAL ENVELOPE. ARCHITECT OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE AND SPECIFY
 INSULATION MATERIALS AND THEIR R-VALUES.(ROOF, WALLS,
 RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION.
 5- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS. NOTE: ARCHITECT TO
 REVIEW/APPROVE PRIOR TO SUBMITTAL.
 6- REVISE ENERGY CALCULATIONS: A)NEED BUILDER'S NAME.
 B)PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE
 CONDITIONED FLOOR AREA TO MATCH PLANS. C)REVISE R-VALUE
 OF FLOOR OVER GARAGE TO MATCH PLANS. D)WALL TYPES
 INFORMATION IS MISSING THE EXTERIOR FRAMED WALL ABOVE
 EXISTING CONCRETE BLOCK WALL. E)ATTIC IS DESIGNED AS
 UNVENTED. SEE PLANS AND REVISE AS REQUIRED. F)REVISE
 DOORS TYPE & SIZES TO MATCH PLANS. NOTE: GLAZED FRENCH
 DOORS NEED TO BE INCLUDED IN THE GLAZING AREA. G)REVISE
 WINDOW AREA AND WINDOW OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. H)REVISE ROOF TYPE INFORMATION TO MATCH
 PLANS. I)BUILDER TO COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
 7- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL
 A) WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION
 SIZE).
 B) ARCHITECT TO REVIEW ABOVE PRODUCT APPROVALS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2022-08-29 Cont ID  
Sent By jgomez Date 2022-08-29 Time 14:41 Rev Time 0.00
Received By jgomez Date 2022-08-29 Time 14:02 Sent To  
Notes
2022-08-29 14:44:06BUILDING REVIEW COMMENTS. FIFTH REVIEW.
  
 PREVIOUS COMMENT NOT ADDRESSED:
 1- NEW ENERGY CALCULATIONS WERE UPLOADED:
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY AT THE OWNER/AGENT LINE AT THE BOTTOM OF FORM
 THAT THE BUILDING IS IN COMPLIANCE WITH THE CODE, AS
 PER SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION AS REQUIRED BY SECTION R103.1.1.2 FBC-ENERGY
 CONSERVATION.
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- DESIGN CRITERIA ON SHEET T-1: REVISE ROOF COMPONENTS
 & CLADDING DESIGN PRESSURES. TABLE R301.2(2) AND TABLE
 R301.2(3)FBC-RESIDENTIAL.
  
 2- PROVIDE COMPLETE DETAILS/SPECS FOR SECOND FLOOR WALL
 SEATING ON TOP OF EXISTING STRUCTURE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS (TOP & BOTTOM),
 INTERIOR/EXTERIOR CONSTRUCTION, INSULATION, ETC.
  
 3- GLAZING IN BALCONY GUARDRAIL: PROVIDE SIGNED/SEALED
 ENGINEERING (SHOP DRAWINGS) FOR GLAZED RAILINGS. SHOP
 DRAWINGS (REVIEWED BY ARCHITECT OF RECORD BEFORE
 SUBMITTAL). IMPORTANT NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H"
  
 4- BUILDING THERMAL ENVELOPE. ARCHITECT OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE AND SPECIFY
 INSULATION MATERIALS AND THEIR R-VALUES.(ROOF, WALLS,
 RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 5- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS. NOTE: ARCHITECT TO
 REVIEW/APPROVE PRIOR TO SUBMITTAL.
  
 6- REVISE ENERGY CALCULATIONS: A)NEED BUILDER'S NAME.
 B)PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE
 CONDITIONED FLOOR AREA TO MATCH PLANS. C)REVISE R-VALUE
 OF FLOOR OVER GARAGE TO MATCH PLANS. D)WALL TYPES
 INFORMATION IS MISSING THE EXTERIOR FRAMED WALL ABOVE
 EXISTING CONCRETE BLOCK WALL. E)ATTIC IS DESIGNED AS
 UNVENTED. SEE PLANS AND REVISE AS REQUIRED. F)REVISE
 DOORS TYPE & SIZES TO MATCH PLANS. NOTE: GLAZED FRENCH
 DOORS NEED TO BE INCLUDED IN THE GLAZING AREA. G)REVISE
 WINDOW AREA AND WINDOW OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. H)REVISE ROOF TYPE INFORMATION TO MATCH
 PLANS. I)BUILDER TO COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 7- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL
 A) WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION
 SIZE).
 B) ARCHITECT TO REVIEW ABOVE PRODUCT APPROVALS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-07-18 Cont ID  
Sent By jgomez Date 2022-07-18 Time 17:09 Rev Time 0.00
Received By jgomez Date 2022-07-18 Time 15:57 Sent To  
Notes
2022-07-18 17:12:20BUILDING REVIEW COMMENTS:
 1- NEW ENERGY CALCULATIONS WERE UPLOADED. THE ENERGY
 FORM R405-2020 IS REQUIRED TO BE SIGNED AND DATED BY
 THE OWNER, ARCHITECT OR OWNER'S LEGALLY DESIGNATED
 AGENT AT THE BOTTOM OF FORM SUBMITTED AS REQUIRED BY
 SECTION 553.907, FLORIDA STATUTES, PRIOR TO RECEIVING
 THE PERMIT TO BEGIN CONSTRUCTION OR RENOVATION. SECTION
 R101.5.1.1.2 FBC-RESIDENTIAL.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- DESIGN CRITERIA ON SHEET T-1: REVISE ROOF COMPONENTS
 & CLADDING DESIGN PRESSURES. TABLE R301.2(2) AND TABLE
 R301.2(3)FBC-RESIDENTIAL.
  
 2- PROVIDE COMPLETE DETAILS/SPECS FOR SECOND FLOOR WALL
 SEATING ON TOP OF EXISTING STRUCTURE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS (TOP & BOTTOM),
 INTERIOR/EXTERIOR CONSTRUCTION, INSULATION, ETC.
  
 3- GLAZING IN BALCONY GUARDRAIL: PROVIDE SIGNED/SEALED
 ENGINEERING (SHOP DRAWINGS) FOR GLAZED RAILINGS. SHOP
 DRAWINGS (REVIEWED BY ARCHITECT OF RECORD BEFORE
 SUBMITTAL). IMPORTANT NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H"
  
 4- BUILDING THERMAL ENVELOPE. ARCHITECT OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE AND SPECIFY
 INSULATION MATERIALS AND THEIR R-VALUES.(ROOF, WALLS,
 RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 5- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS. NOTE: ARCHITECT TO
 REVIEW/APPROVE PRIOR TO SUBMITTAL.
  
 6- REVISE ENERGY CALCULATIONS: A)NEED BUILDER'S NAME.
 B)PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE
 CONDITIONED FLOOR AREA TO MATCH PLANS. C)REVISE R-VALUE
 OF FLOOR OVER GARAGE TO MATCH PLANS. D)WALL TYPES
 INFORMATION IS MISSING THE EXTERIOR FRAMED WALL ABOVE
 EXISTING CONCRETE BLOCK WALL. E)ATTIC IS DESIGNED AS
 UNVENTED. SEE PLANS AND REVISE AS REQUIRED. F)REVISE
 DOORS TYPE & SIZES TO MATCH PLANS. NOTE: GLAZED FRENCH
 DOORS NEED TO BE INCLUDED IN THE GLAZING AREA. G)REVISE
 WINDOW AREA AND WINDOW OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. H)REVISE ROOF TYPE INFORMATION TO MATCH
 PLANS. I)BUILDER TO COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 7- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL
 A) WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION
 SIZE).
 B) ARCHITECT TO REVIEW ABOVE PRODUCT APPROVALS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-05-26 Cont ID  
Sent By jgomez Date 2022-05-26 Time 14:26 Rev Time 0.00
Received By jgomez Date 2022-05-26 Time 13:49 Sent To  
Notes
2022-05-26 14:26:53BUILDING REVIEW APPROVED WITH PROVISO:
 1- DESIGN CRITERIA ON SHEET T-1: REVISE ROOF COMPONENTS
 & CLADDING DESIGN PRESSURES. TABLE R301.2(2) AND TABLE
 R301.2(3)FBC-RESIDENTIAL.
  
 2- PROVIDE COMPLETE DETAILS/SPECS FOR SECOND FLOOR WALL
 SEATING ON TOP OF EXISTING STRUCTURE. SPECIFY ALL
 FRAMING MEMBERS AND CONNECTORS (TOP & BOTTOM),
 INTERIOR/EXTERIOR CONSTRUCTION, INSULATION, ETC.
  
 3- GLAZING IN BALCONY GUARDRAIL: PROVIDE SIGNED/SEALED
 ENGINEERING (SHOP DRAWINGS) FOR GLAZED RAILINGS. SHOP
 DRAWINGS (REVIEWED BY ARCHITECT OF RECORD BEFORE
 SUBMITTAL). IMPORTANT NOTE: TABLE R301.5
 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE NOTE
 "H"
  
 4- BUILDING THERMAL ENVELOPE. ARCHITECT OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE AND SPECIFY
 INSULATION MATERIALS AND THEIR R-VALUES.(ROOF, WALLS,
 RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY SEC.
 R103.2 FBC-ENERGY CONSERVATION.
  
 5- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE
 INSULATION SPECIFIED ON PLANS. NOTE: ARCHITECT TO
 REVIEW/APPROVE PRIOR TO SUBMITTAL.
  
 6- REVISE ENERGY CALCULATIONS: A)NEED BUILDER'S NAME.
 B)PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE
 CONDITIONED FLOOR AREA TO MATCH PLANS. C)REVISE R-VALUE
 OF FLOOR OVER GARAGE TO MATCH PLANS. D)WALL TYPES
 INFORMATION IS MISSING THE EXTERIOR FRAMED WALL ABOVE
 EXISTING CONCRETE BLOCK WALL. E)ATTIC IS DESIGNED AS
 UNVENTED. SEE PLANS AND REVISE AS REQUIRED. F)REVISE
 DOORS TYPE & SIZES TO MATCH PLANS. NOTE: GLAZED FRENCH
 DOORS NEED TO BE INCLUDED IN THE GLAZING AREA. G)REVISE
 WINDOW AREA AND WINDOW OVERHANG DEPTH AND SEPARATION TO
 MATCH PLANS. H)REVISE ROOF TYPE INFORMATION TO MATCH
 PLANS. I)BUILDER TO COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 7- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL
 A) WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION
 SIZE).
 B) ARCHITECT TO REVIEW ABOVE PRODUCT APPROVALS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-25 Cont ID  
Sent By jgomez Date 2022-05-25 Time 16:12 Rev Time 0.00
Received By jgomez Date 2022-05-24 Time 18:50 Sent To  
Notes
2022-05-25 16:14:11RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21120435
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***IMPORTANT***
 ENERGY CALCULATIONS NEED TO BE CERTIFIED BY THE OWNER
 OR AUTHORIZED AGENT BEFORE ISSUING THE PERMIT.
  
 1- OK
  
 ORIGINAL COMMENT:
 2-DESIGN CRITERIA ON SHEET T-1:
 B)REVISE ROOF COMPONENTS & CLADDING DESIGN PRESSURES.
 BASED ON HEIGHT OF BUILDING SHOWN ON EXTERIOR
 ELEVATIONS ON SHEET A-4, THE MULTIPLYING FACTOR TO USE
 FROM TABLE R301.2(3) IS 1.35 NOT 1.21. REVISE DESIGN
 PRESSURES AS REQUIRED. ALSO, WORST CASE SCENARIO IS FOR
 AN EFFECTIVE AREA OF 10PSF IN ROOF ZONE 3. REVISE
 DESIGN PRESSURES ACCORDINGLY.
 NOTE: PROPOSED ADDITION HAS A FLAT ROOF.
  
 RESPONSE:
 REVISE ROOF DESIGN PRESSURES. ROOF ZONE 3 IS THE WORST
 CASE AREA.
  
 ORIGINAL COMMENT:
 3- PLANS DON'T PROVIDE ANY INFORMATION FOR CONSTRUCTION
 OF NEW SECOND FLOOR WALL SEATING ON TOP OF EXISTING
 STRUCTURE. PROVIDE COMPLETE DETAILS AND SPECIFICATION
 FOR THIS WALL. PROVIDE COMPLETE WALL SECTION SHOWING
 THE LOAD PATH AS REQUIRED BY SEC. R601.2
 FBC-RESIDENTIAL.
  
 RESPONSE:
 NO INFORMATION WAS GIVEN FOR WALL CONSTRUCTION
 (INTERIOR/EXTERIOR, INSULATION, ETC.). NO STRUCTURAL
 CONNECTORS WERE SPECIFIED.
  
 4- OK.
 5- OK.
 6- OK.
 7- OK.
 8- OK.
  
 9- DEFERRED SUBMITTAL: SHEET A-4. GLAZING IN BALCONY
 GUARDRAIL:
 PROVIDE SIGNED/SEALED ENGINEERING (SHOP DRAWINGS) FOR
 GLAZED RAILINGS. SHOP DRAWINGS (REVIEWED BY ARCHITECT
 OF RECORD BEFORE SUBMITTAL). IMPORTANT NOTE: TABLE
 R301.5 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE
 NOTE "H"
 NOTE: THIS COULD BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. SPECIFY IN PLANS IF DEFERRED SUBMITTAL.
  
 10-OK.
  
 ORIGINAL COMMENT:
 11- BUILDING THERMAL ENVELOPE.
 A)ARCHITECT OF RECORD NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND
 THEIR R-VALUES.(ROOF, WALLS, RAISED FLOOR ABOVE GARAGE,
 ETC.) AS REQUIRED BY SEC. R103.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 NO R-VALUE INFORMATION GIVEN FOR EXTERIOR WALLS
 INSULATION (FRAMED AND MASONRY WALL) AND FOR ROOF.
 NOTE: COORDINATE WITH ENERGY CALCULATIONS TO AVOID
 CONFLICTS/DELAYS.
  
 12- DEFERRED SUBMITTAL: HOUSE IS DESIGNED WITH UNVENTED
 ATTIC. ARCHITECT IS SPECIFYING ICYNENE SPRAY
 INSULATION. PROVIDE ICC EVALUATION REPORT FOR THE
 ICYNENE INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13- OK.
 14- OK.
  
 ORIGINAL COMMENT:
 15-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SECTION 553.907, FLORIDA STATUTES, PRIOR TO
 RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION. SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 C) PLANS SUBMITTED SHOW GARAGE WITH A/C. REVISE
 CONDITIONED FLOOR AREA TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)REVISE R-VALUE OF FLOOR OVER GARAGE TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)WALL TYPES INFORMATION ON PAGE ONE IS MISSING THE
 INFORMATION FOR EXTERIOR FRAMED WALL ABOVE EXISTING
 CONCRETE BLOCK WALL. COORDINATE WITH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F)ATTIC IS DESIGNED AS UNVENTED. SEE PLANS AND REVISE
 AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 G)REVISE DOORS INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVALS SUBMITTED.
 REVISE DOOR TYPE AND SIZES. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
 NOTE: GLAZED FRENCH DOORS NEED TO BE INCLUDED IN THE
 GLAZING AREA. REVISE AS REQUIRED.
  
 H)REVISE WINDOWS INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVALS SUBMITTED. REVISE WINDOW AREA AND WINDOW
 OVERHANG DEPTH AND SEPARATION TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 I)REVISE ROOF TYPE INFORMATION TO MATCH PLANS AND
 PRODUCT APPROVALS SUBMITTED. FBC- ENERGY CONSERVATION.
 THIS IS A FLAT ROOF NOT PITCH
  
 J)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
  
 16- DEFERRED PRODUCT APPROVAL:PROVIDE PRODUCT APPROVAL
 AS REQUIRED BY FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR.
  
 B)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS,
 INCLUDING THE ONES ALREADY SUBMITTED AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH PRODUCT APPROVAL LIST ON SHEET
 T-1. MAKE SURE ALL PRODUCT APPROVALS ARE LISTED AND
 NOA'S ARE CORRECT.
  
 18- WIND RESISTANCE OF EXTERIOR SOFFITS: TYPICAL WALL
 SECTIONS ONLY SPECIFY "7/8" STUCCO O/ MTL. LATH W/
 SMOOTH SAND FINISH". ARCHITECT OF RECORD TO PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE SOFFIT
 CONSTRUCTION SHOWING COMPLIANCE WITH SEC. R704
 FBC-RESIDENTIAL. NOTE: PROVIDE SPECIFICATIONS SHOWING
 COMPLIANCE WITH ASTM C1063 (SEE TABLE 3 OF ASTM C1063).
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By jgomez Date 2022-03-28 Time 17:59 Rev Time 0.00
Received By jgomez Date 2022-03-28 Time 10:51 Sent To  
Notes
2022-03-28 18:00:59RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21120435
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 OF RECORD. ALL DRAWINGS NEED TO BE SIGNED AND SEALED AS
 REQUIRED BY CHAPTER 481 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ARCHITECT'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY PLANS WITH
 ARCHITECT'S ORIGINAL SEAL AND SIGNATURE.
  
 2-DESIGN CRITERIA ON SHEET T-1:
 A)REVISE WALLS COMPONENTS & CLADDING DESIGN PRESSURES.
 BASED ON HEIGHT OF BUILDING SHOWN ON EXTERIOR
 ELEVATIONS ON SHEET A-4, THE MULTIPLYING FACTOR TO USE
 FROM TABLE R301.2(3) IS 1.35 NOT 1.21. REVISE DESIGN
 PRESSURES AS REQUIRED. ALSO, WORST CASE SCENARIO IS FOR
 AN EFFECTIVE AREA OF 10PSF IN AN END ZONE. REVISE
 DESIGN PRESSURES ACCORDINGLY.
  
 B)REVISE ROOF COMPONENTS & CLADDING DESIGN PRESSURES.
 BASED ON HEIGHT OF BUILDING SHOWN ON EXTERIOR
 ELEVATIONS ON SHEET A-4, THE MULTIPLYING FACTOR TO USE
 FROM TABLE R301.2(3) IS 1.35 NOT 1.21. REVISE DESIGN
 PRESSURES AS REQUIRED. ALSO, WORST CASE SCENARIO IS FOR
 AN EFFECTIVE AREA OF 10PSF IN ROOF ZONE 3. REVISE
 DESIGN PRESSURES ACCORDINGLY.
 NOTE: PROPOSED ADDITION HAS A FLAT ROOF.
  
 C)REVISE BUILDING DESIGN PRESSURES SPECIFIED UNDER THE
 PRODUCT APPROVAL SUBMITTAL AFFIDAVIT LIST SHOWN ON
 SHEET T-1. COORDINATE WITH ITEM #2(A) ABOVE AND REVISE
 AS REQUIRED.
  
 D)DESIGNER OF RECORD TO SPECIFY ALL LIVE AND DEAD LOADS
 FOR SECOND FLOOR, CANTILEVERED BALCONY AND SECOND FLOOR
 ROOF. CLEARLY SPECIFY SECOND FLOOR LIVE AND DEAD LOADS
 (TOP AND BOTTOM CHORDS) AND ROOF LIVE AND DEAD LOADS.
 SEC. R301.4 FBC-RESIDENTIAL.
 SEC. R301.5 FBC-RESIDENTIAL AND TABLE R301.5
 FBC-RESIDENTIAL.
  
 3- PLANS DON'T PROVIDE ANY INFORMATION FOR CONSTRUCTION
 OF NEW SECOND FLOOR WALL SEATING ON TOP OF EXISTING
 STRUCTURE. PROVIDE COMPLETE DETAILS AND SPECIFICATION
 FOR THIS WALL. PROVIDE COMPLETE WALL SECTION SHOWING
 THE LOAD PATH AS REQUIRED BY SEC. R601.2
 FBC-RESIDENTIAL.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY CONSTRUCTION. PROVIDE DIMENSIONS, FRAMING
 INFORMATION, HANDRAIL SPECS, RISER AND TREAD SPECS,
 FIREBLOCKING, ETC. SHOWING COMPLIANCE WITH ALL THE
 REQUIREMENTS OF SEC. R311.7 FBC-RESIDENTIAL.
  
 5- SHEET D-1:
 A)FOUNDATION PLAN DOESN'T PROVIDE ANY INFORMATION FOR
 ATTACHMENT OF NEW FOOTING TO EXISTING STRUCTURE. SEC.
 107.2.1 CITY AMENDMENTS. SEC. R401.2 FBC-RESIDENTIAL,
 SEC. R601.2 FBC-RESIDENTIAL.
  
 B)FOOTING SIZE SPECIFIED ON WALLS SECTIONS ON SHEET
 A-3(DETAILS) DON'T MATCH FOOTING SIZE SPECIFIED ON
 FOUNDATION PLAN. REVISE AS REQUIRED TO MATCH. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 6- GARAGE FIRE RESISTANCE CONSTRUCTION:
 A) PROVIDE FIRE RATING SPECIFICATIONS FOR THE SWING
 DOOR LEADING FROM THE NEW GARAGE TO THE MAIN HOUSE AS
 REQUIRED BY SEC. R302. 5.1 FBC-RESIDENTIAL.
  
 B)PROVIDE SPECIFICATIONS FOR CEILING DWELLING-GARAGE
 SEPARATION SHOWING COMPLIANCE WITH SEC. R302.6
 FBC-RESIDENTIAL AND TABLE R302.6 FBC-RESIDENTIAL.
  
 7- BALCONY INFORMATION ON SECOND FLOOR PLAN ON SHEET
 A-1 IS INCOMPLETE. IT DOESN'T SHOW ANY GUARDRAIL.
 PROVIDE COMPLETE INFORMATION AND SPECIFICATIONS. SEC.
 R312.1 FBC-RESIDENTIAL.
  
 8-SHEET A-3(ROOF PLAN):
 A)PROVIDE COMPLETE FRAMING PLAN FOR PROPOSED BALCONY.
 SPECIFY ALL FRAMING MEMBERS TYPE, SIZE AND SPACING.
 SPECIFY FASTENING AT THE END OF EACH STRUCTURAL MEMBER.
 SPECIFY BALCONY DECKING AND FASTENING SPECIFICATIONS.
 CLARIFY SUPPORT OF CANTILEVERED BALCONY. SEC. R301.1
 FBC-RESIDENTIAL AND SEC. R301.2.1 FBC-RESIDENTIAL.
  
 B)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 ATTACHMENT SECOND FLOOR TRUSSES TO NEW WALL SEATING ON
 EXISTING WALL. SEC. R301.1 FBC-RESIDENTIAL.
  
 C) COORDINATE STRUCTURAL LEDGER SPECIFICATIONS
 SPECIFIED ON THE SECOND FLOOR FRAMING PLAN WITH LEDGER
 SPECIFICATIONS SHOWN ON WALL SECTION DETAIL ON SHEET
 A-3 (DETAILS). NEED TO SPECIFY HOW MUCH EMBEDMENT IS
 REQUIRED FOR THE 5/8" WEDGE ANCHORS AND NEED TO
 COORDINATE ANCHOR SPACING TO MATCH. CHECK SECOND FLOOR
 LOADS DESIGN WHEN SPECIFYING THE ANCHOR SPACING.
 NOTE: THERE ARE TWO A-3 SHEETS SUBMITTED. A-3(ROOF
 PLAN) AND A-3(DETAILS). REVISE S REQUIRED TO AVOID
 CONFLICTS.
  
 9- SHEET A-4. GLAZING IN BALCONY GUARDRAIL:
 A)PROVIDE SIGNED/SEALED ENGINEERING (SHOP DRAWINGS) FOR
 GLAZED RAILINGS. SHOP DRAWINGS (REVIEWED BY ARCHITECT
 OF RECORD BEFORE SUBMITTAL). IMPORTANT NOTE: TABLE
 R301.5 FBC-RESIDENTIAL. NEED A SAFETY FACTOR OF 4. SEE
 NOTE "H"
 NOTE: THIS COULD BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. SPECIFY IN PLANS IF DEFERRED SUBMITTAL.
  
 B)REAR ELEVATION IS INCOMPLETE. SEE PLANS AND REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 10-SHEET A-3(DETAILS):
 A) REVISE ROOF ZONE DETAIL. SEE FIGURE R301.2(7) OF
 CURRENT 2020 RESIDENTIAL CODE FOR NEW ROOF ZONES
 DESIGNATIONS AND REVISE AS REQUIRED.
 NOTE: PROPOSED ROOF IS A FLAT ROOF.
  
 B)THERE ARE TWO DIFFERENT ROOF SHEATHING SPECIFICATIONS
 ON THIS SHEET.
 NEED TO PROVIDE ONLY ONE TO AVOID CONFLICTS/DELAYS.
 REVISE AS REQUIRED. NOTE: NEED TO USE RING SHANK NAILS
 AND ROOF SHEATHING NEEDS TO BE NAILED WITH AT 4 INCHES
 O.C. IN THE FIELD AND EDGES AS REQUIRED BY SEC.
 R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 11- BUILDING THERMAL ENVELOPE.
 A)ARCHITECT OF RECORD NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE AND SPECIFY INSULATION MATERIALS AND
 THEIR R-VALUES.(ROOF, WALLS, RAISED FLOOR ABOVE GARAGE,
 ETC.) AS REQUIRED BY SEC. R103.2 FBC-ENERGY
 CONSERVATION.
  
 12-HOUSE IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT IS
 SPECIFYING ICYNENE SPRAY INSULATION. PROVIDE ICC
 EVALUATION REPORT FOR THE ICYNENE INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 13- ARCHITECT NEEDS TO SPECIFY CARBON MONOXIDE ALARM
 WITHIN ALL SLEEPING ROOMS, INCLUDING EXISTING BEDROOMS
 AS REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 14-PROVIDE COMPLETE STRUCTURAL BUCK DETAIL AND
 FASTENING SPECIFICATIONS FOR NEW OVERHEAD GARAGE DOOR.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 15-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. 1106
 FBC-EXISTING BUILDING AND SEC. R101.5 FBC-ENERGY
 CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 16- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING FRENCH DOORS AS SHOWN ON PLANS.
  
 B)ENTRY DOOR.
  
 C)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO AVOID DELAYS/CONFLICTS).
  
 17- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS,
 INCLUDING THE ONES ALREADY SUBMITTED AS REQUIRED BY
 SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: COORDINATE WITH PRODUCT APPROVAL LIST ON SHEET
 T-1. MAKE SURE ALL PRODUCT APPROVALS ARE LISTED AND
 NOA'S ARE CORRECT.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF THE
 REVISION MADE WILL HELP TO EXPEDITE THE REVIEW PROCESS.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-09 Cont ID  
Sent By mpeterso Date 2022-05-09 Time 11:53 Rev Time 0.00
Received By mpeterso Date 2022-05-09 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-02-09 Cont ID  
Sent By jleahy Date 2022-02-09 Time 11:49 Rev Time 0.00
Received By jleahy Date 2022-02-09 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 13:42 Rev Time 0.00
Received By shill Date 2022-08-26 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-18 Cont ID  
Sent By jgomez Date 2022-07-18 Time 17:15 Rev Time 0.00
Received By jgomez Date 2022-06-17 Time 07:32 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-25 Cont ID  
Sent By jgomez Date 2022-05-25 Time 16:14 Rev Time 0.00
Received By jgomez Date 2022-04-18 Time 12:55 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-03-28 Cont ID  
Sent By jgomez Date 2022-03-28 Time 18:07 Rev Time 0.00
Received By jgomez Date 2022-02-01 Time 11:23 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2022-09-26 Cont ID  
Sent By aoliver Date 2022-09-26 Time 13:05 Rev Time 0.00
Received By aoliver Date 2022-08-31 Time 13:25 Sent To  
Notes
2022-09-26 09:42:51RECEIPT MU-2022-041143-0000 - $1,945.04 PAID
2022-08-31 13:25:568/31/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By jgomez Date 2022-08-29 Time 14:07 Rev Time 0.00
Received By jgomez Date 2022-08-29 Time 14:07 Sent To  
Notes
2022-08-29 14:07:35IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By jgomez Date 2022-03-28 Time 18:05 Rev Time 0.00
Received By jgomez Date 2022-03-28 Time 18:05 Sent To  
Notes
2022-03-28 18:05:46IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-06-23 Cont ID  
Sent By medwards Date 2022-06-23 Time 14:22 Rev Time 0.00
Received By medwards Date 2022-06-23 Time 14:22 Sent To  
Notes
2022-06-23 14:24:36APPROVED WITH PRIVISO'S:
 THE DRYER EXHAUST MUST COMPLY WITH FRC M1502.4
 THE BATH ROMM EXHAUST MUST COMPLY WITH FRC 303.3
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-05-03 Cont ID  
Sent By medwards Date 2022-05-03 Time 09:37 Rev Time 0.00
Received By medwards Date 2022-05-03 Time 09:36 Sent To  
Notes
2022-05-03 09:37:021ST REVIEW FMC
 PERMIT: 21120435
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENERGY CALCULATIONS IS FOR 500 SQ FT AND FOR THE
 MASTER BATH ABOVE THE GARAGE. IF A MINI-SPLIT IS GOING
 TO BE INSTALLED IN THE GARAGE YOU MUST SUBMIT AN ENERGY
 CALCULATION SHOWING THE GARAGE SQ FT PLUS SHOWING THE
 GARAGE DOOR WITH THE WEATHER-STRIP. THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS HAS SHOWN THIS IN THE
 CALCULATIONS.
  
 2) PLEASE ADDRESS THE PREVIOUS COMMENTS LISTED BELOW.
  
 3) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL AND THE
 TERMINATION LOCATION. FBC RES M1502
  
 4) PLEASE SHOW THE BATH EXHAUST FAN AND THE DUCT
 TERMINATION LOCATION. FBC RES M1507.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-15 Cont ID  
Sent By medwards Date 2022-02-15 Time 11:21 Rev Time 0.00
Received By medwards Date 2022-02-15 Time 11:21 Sent To  
Notes
2022-02-15 11:22:151ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120435
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENERGY CALCULATIONS THAT INCLUDE
 THE GARAGE DOOR AND THE WEATHER STRIPPING AROUND THE
 GARAGE DOOR. FBC EC 101.5.1.1.2
  
 2) PLEASE PROVIDE THE ENTIRE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS. FBC EC R403.7
  
 3) PLEASE SHOW THE DRYER EXHAUST DUCT MATERIAL AND THE
 TERMINATION LOCATION. FBC RES M1502
  
 4) PLEASE SHOW THE BATH EXHAUST FAN AND THE DUCT
 TERMINATION LOCATION. FBC RES M1507.4
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-08-29 Cont ID  
Sent By rwbrown Date 2022-08-29 Time 11:01 Rev Time 0.00
Received By rwbrown Date 2022-08-29 Time 11:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-06-23 Cont ID  
Sent By rwbrown Date 2022-06-23 Time 06:17 Rev Time 0.00
Received By rwbrown Date 2022-06-23 Time 06:17 Sent To  
Notes
2022-06-23 06:19:113RD PLUMBING REVIEW
  
 PLAN REVIEW RESULTS: DENIED
  
 1. 2020 FRC P3101.2.1 VENTING REQUIRED. -- THE LAUNDRY
 TRAP IS NOT VENTED IN ACCORDANCE WITH THE CODE. PLEASE
 SHOW A COMPLIANT VENT FOR THE LAUNDRY FIXTURE DRAIN.
  
 THE "FIXTURE DRAIN" ITSELF NEEDS A VENT BEFORE IT
 CONNECTS TO THE STACK. YOU WOULD NEED TO CONNECT A VENT
 SOMEWHERE BETWEEN THE TRAP AND THE STACK.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-04-19 Cont ID  
Sent By rwbrown Date 2022-04-19 Time 15:32 Rev Time 0.00
Received By rwbrown Date 2022-04-19 Time 15:30 Sent To  
Notes
2022-04-19 15:31:562ND PLUMBING REVIEW
  
 PLAN REVIEW RESULTS: DENIED
  
 1. 2020 FRC P3101.2.1 VENTING REQUIRED. -- THE LAUNDRY
 TRAP IS NOT VENTED IN ACCORDANCE WITH THE CODE. PLEASE
 SHOW A COMPLIANT VENT FOR THE LAUNDRY FIXTURE DRAIN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-02-10 Cont ID  
Sent By rwbrown Date 2022-02-09 Time 13:38 Rev Time 0.00
Received By rwbrown Date 2022-02-09 Time 13:36 Sent To  
Notes
2022-02-09 13:42:201ST PLUMBING REVIEW
  
 PLAN REVIEW RESULTS: DENIED
  
 1. 2017 WPB CHPT 1 AMEND - 107.3.5.3 (12) - PLEASE
 SUBMIT THE MINIMUM CRITERIA OF A PLUMBING RISER
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-07-18 Cont ID  
Sent By jgomez Date 2022-07-18 Time 16:55 Rev Time 0.00
Received By jgomez Date 2022-07-18 Time 16:55 Sent To  
Notes
2022-07-18 16:55:55FLAT ROOF FL16709-R9.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2022-05-25 Cont ID  
Sent By jgomez Date 2022-05-25 Time 15:30 Rev Time 0.00
Received By jgomez Date 2022-05-25 Time 15:30 Sent To  
Notes
2022-05-25 15:30:19FLAT ROOF FL16709-R9.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2022-03-28 Cont ID  
Sent By jgomez Date 2022-03-28 Time 18:02 Rev Time 0.00
Received By jgomez Date 2022-03-28 Time 18:01 Sent To  
Notes
2022-03-28 18:02:41FLAT ROOF FL16709-R9.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-08-29 Cont ID  
Sent By rwbrown Date 2022-08-29 Time 11:02 Rev Time 0.00
Received By rwbrown Date 2022-08-29 Time 11:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-18 Cont ID  
Sent By jgomez Date 2022-07-18 Time 17:14 Rev Time 0.00
Received By jgomez Date 2022-07-18 Time 17:14 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-25 Cont ID  
Sent By jgomez Date 2022-05-25 Time 15:30 Rev Time 0.00
Received By jgomez Date 2022-05-25 Time 15:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-28 Cont ID  
Sent By jgomez Date 2022-03-28 Time 18:04 Rev Time 0.00
Received By jgomez Date 2022-03-28 Time 18:03 Sent To  
Notes
2022-03-28 18:04:54SIGNATURE REVIEW:
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 OF RECORD. ALL DRAWINGS NEED TO BE SIGNED AND SEALED AS
 REQUIRED BY CHAPTER 481 F.S. WHEN SUBMITTING
 DRAWINGS/DOCUMENTS FOR PUBLIC RECORDS.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH ARCHITECT'S
 DIGITAL SIGNATURE OR PROVIDE HARD COPY PLANS WITH
 ARCHITECT'S ORIGINAL SEAL AND SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2022-09-06 Cont ID  
Sent By vbroglia Date 2022-09-06 Time 10:20 Rev Time 0.00
Received By vbroglia Date 2022-09-06 Time 10:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-06-27 Cont ID  
Sent By vbroglia Date 2022-06-27 Time 16:42 Rev Time 0.00
Received By vbroglia Date 2022-06-27 Time 16:42 Sent To  
Notes
2022-06-27 16:44:376/27/2022 FAILED
  
 A SEPERATE PERMIT IS REQUIRED FOR LANDSCAPING, PLEASE
 APPLY FOR ONE TO ALLOW STAFF TO MOVE FORWARD
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-04-21 Cont ID  
Sent By vbroglia Date 2022-04-21 Time 14:40 Rev Time 0.00
Received By vbroglia Date 2022-04-21 Time 14:40 Sent To  
Notes
2022-04-21 16:17:404/21/2022**** FAILED ****
  
 THE VALUE OF THE CONSTRUCTION ($234,900.00) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($178,267) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(B) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), THE LANDSCAPE ON THE SITE SHALL BE
 IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS TO
 ARTICLE XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 ARTICLE XIV, THEN PRIOR TO THE ZONING APPROVAL OF THIS
 PERMIT A SEPARATE LANDSCAPE PERMIT AND IRRIGATION
 PERMIT SHALL BE SUBMITTED SHOWING MATERIAL TO BRING THE
 SITE INTO CONFORMITY
  
 PLEASE APPLY FOR A LANDSCAPE PERMIT THAT OBTAINS A
 PERMIT NUMBER TO ALLOW STAFF TO MOVE FOWARD
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-02-10 Cont ID  
Sent By vbroglia Date 2022-02-10 Time 10:09 Rev Time 0.00
Received By vbroglia Date 2022-02-10 Time 10:09 Sent To  
Notes
2022-02-10 10:15:172/10/2022 FAILED PLEASE PROVIDE A SITE PALN/SURVEY THAT
 SHOWS THE SETBACKS FROM ALL PROPERTY LINES.
  
 VALENTINA BROGLIA, ASSOCIATE PLANNER
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved