Plan Review Details - Permit 21120381
Plan Review Stops For Permit 21120381
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By rmcdouga Date 2022-03-14 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2022-03-14 Time 10:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-27 Cont ID  
Sent By rmcdouga Date 2022-01-27 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2022-01-27 Time 13:57 Sent To  
Notes
2022-01-27 14:09:16PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE GENERATOR PAD DETAILS AND GENERATOR TO PAD
 ANCHORING FOR WINDLOADING. FBC-R301.1
  
 2) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-03-18 Cont ID  
Sent By mpeterso Date 2022-03-18 Time 13:10 Rev Time 0.00
Received By mpeterso Date 2022-03-18 Time 13:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-10 Cont ID  
Sent By fgiaquin Date 2022-01-10 Time 22:00 Rev Time 0.00
Received By fgiaquin Date 2022-01-10 Time 21:38 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-03-08 Cont ID  
Sent By lcrespo Date 2022-03-08 Time 08:02 Rev Time 0.00
Received By lcrespo Date 2022-03-08 Time 08:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 11:56 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 11:56 Sent To  
Notes
2021-12-17 12:08:54GSS PLANS APPROVED UNDER 21010946 AND GAS SUB UNDER
 21081396

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-18 Cont ID  
Sent By mpeterso Date 2022-03-18 Time 13:11 Rev Time 0.00
Received By mpeterso Date 2022-03-03 Time 06:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-27 Cont ID  
Sent By rmcdouga Date 2022-01-27 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2021-12-09 Time 11:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-03-08 Cont ID  
Sent By lcrespo Date 2022-03-08 Time 08:02 Rev Time 0.00
Received By lcrespo Date 2022-03-08 Time 08:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 12:08 Rev Time 0.00
Received By lcrespo Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By rmcdouga Date 2022-03-14 Time 10:33 Rev Time 0.00
Received By rmcdouga Date 2022-03-14 Time 10:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-09 Cont ID  
Sent By rmcphers Date 2021-12-09 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2021-12-09 Time 15:10 Sent To  
Notes
2021-12-09 15:17:28SIGNATURE REVIEW
  
 DRAWINGS SP-002, E2.1, P1.1, P2.1 UP LOADED TO
 PROJECTDOX BY THE CITY ARE COPIES OF ELECTRONICALLY
 SIGNED DRAWINGS.
  
 WHEN YOU DELIVER DRAWINGS TO THE CITY TO UPLOAD TO
 PROJECTDOX - THEY WILL NEED TO BE THE ORIGINAL WET SEAL
 OR CRIMP SEAL FROM THE ARCHITECT OR ENGINEER.
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-03-15 Cont ID  
Sent By rmcdouga Date 2022-03-15 Time 15:08 Rev Time 0.00
Received By vbroglia Date 2022-03-15 Time 15:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By vbroglia Date 2021-12-17 Time 11:51 Rev Time 0.00
Received By vbroglia Date 2021-12-17 Time 11:51 Sent To  
Notes
***NONE***