Plan Review Details - Permit 21120324
Plan Review Stops For Permit 21120324
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-12-14 Cont ID  
Sent By cwalker Date 2021-12-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-12-10 Cont ID  
Sent By cwalker Date 2021-12-10 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2021-12-10 11:11:38NFPA 96
  
 10.2.2* A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR
 EACH EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION
 SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE
 EXTINGUISHER.
 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN.
 AND 48 IN.)ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT
 OF A FIRE, BE LOCATEDIN A PATH OF EGRESS, AND CLEARLY
 IDENTIFY THE HAZARD PROTECTED. INDICATE MOUNTING HEIGHT
 AND LOCATION.
 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M
 (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S)
 WITHIN A PATH OF EGRESS
 OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ.
 INDICATE LOCATION ON A FLOOR PLAN.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 07:50 Rev Time 0.00
Received By medwards Date 2021-12-13 Time 08:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-10 Cont ID  
Sent By medwards Date 2021-12-10 Time 13:05 Rev Time 0.00
Received By medwards Date 2021-12-09 Time 08:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 07:50 Rev Time 0.00
Received By medwards Date 2021-12-16 Time 07:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-10 Cont ID  
Sent By medwards Date 2021-12-10 Time 13:02 Rev Time 0.00
Received By medwards Date 2021-12-10 Time 13:02 Sent To  
Notes
2021-12-10 13:03:50PLEASE SEE THE FIRE REVIEWERS COMMENTS BELOW:
  
  
 NFPA 96
  
 10.2.2* A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR
 EACH EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION
 SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE
 EXTINGUISHER.
 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN.
 AND 48 IN.)ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT
 OF A FIRE, BE LOCATEDIN A PATH OF EGRESS, AND CLEARLY
 IDENTIFY THE HAZARD PROTECTED. INDICATE MOUNTING HEIGHT
 AND LOCATION.
 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M
 (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S)
 WITHIN A PATH OF EGRESS
 OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ.
 INDICATE LOCATION ON A FLOOR PLAN.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 07:50 Rev Time 0.00
Received By medwards Date 2021-12-16 Time 07:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-12-10 Cont ID  
Sent By medwards Date 2021-12-10 Time 13:05 Rev Time 0.00
Received By medwards Date 2021-12-10 Time 13:05 Sent To  
Notes
***NONE***