Plan Review Details - Permit 21120322
Plan Review Stops For Permit 21120322
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-02-22 Cont ID  
Sent By dbattles Date 2022-02-22 Time 09:20 Rev Time 0.00
Received By dbattles Date 2022-02-22 Time 09:20 Sent To  
Notes
2022-02-22 09:21:11ADDED TO SUPPORTING DOCUMENTS

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By dbattles Date 2022-01-31 Time 11:30 Rev Time 0.00
Received By dbattles Date 2022-01-31 Time 11:30 Sent To  
Notes
2022-01-31 11:31:34PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: HTTP://PALM
 BEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICES/ENVIRONME
 NTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-RENOVATION.
 HTML. THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA
 EMAIL TO [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT
 LINE.
  
 W.P.B. PERMIT: 21120322
 REVIEWED: JANUARY 31, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-06-07 Cont ID  
Sent By shill Date 2022-06-07 Time 11:52 Rev Time 0.00
Received By shill Date 2022-06-07 Time 11:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-31 Cont ID  
Sent By dbattles Date 2022-03-31 Time 13:21 Rev Time 0.00
Received By dbattles Date 2022-03-31 Time 13:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-25 Cont ID  
Sent By dbattles Date 2022-02-25 Time 10:25 Rev Time 0.00
Received By dbattles Date 2022-02-25 Time 09:30 Sent To  
Notes
2022-02-25 10:25:13BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 21120322
 REVIEWED: JANUARY 31, 2022
 2ND REVIEW FEBRUARY 25, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2020)
 FBC[AMENDED] = 2020 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1. RESOLVED
  
 2. TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF
 CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT
 BELOW.
  
 3. PROVIDE REPORTS FOR SOUND TRANSMISSION( AND FLAME
 SPREAD (3 TOTAL)
 THE PROCORE PLUS DATA SHEET PROVIDES NO INFO ON THE
 SOUND TRANSMISSION.
 HOW ARE YOU ACHIEVING IIC OF 50 AND STC 50?
 IF THERE IS ANOTHER UNDERLAYMENT PLEASE PROVIDE SOUND
 REPORTS FOR IIC AND STC, OR PROVIDE REPORTS TO SHOW
 PROCORE MEETS SOUND TRANSMISSION..
  
 4. RESOLVED
  
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
  
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
  
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
  
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2
 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By dbattles Date 2022-01-31 Time 11:20 Rev Time 0.00
Received By dbattles Date 2022-01-31 Time 11:20 Sent To  
Notes
2022-01-31 11:29:55BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 21120322
 REVIEWED: JANUARY 31, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FLORIDA BUILDING CODE,6TH EDITION (2020)
 FBC[AMENDED] = 2020 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 1. FLOOR PLAN LAYOUT TO SHOW AREA AND TYPE OF FLOORING
 FOR EACH AREA.
  
 2. TYPE OF CEILING ASSEMBLE INCLUDING THICKNESS OF
 CONCRETE AND IF THERE IS A SOUND RATED ASSEMBLY IN UNIT
 BELOW.
  
 3. PROVIDE REPORTS FOR SOUND TRANSMISSION( AND FLAME
 SPREAD (3 TOTAL)
  
 4. PROVIDE PLAN FOR DEMO, PLUMBING AND ELECTRICAL
  
 1207.2 FBC[B] AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS AND
 SLEEPING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS OF
 NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED,
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E90.
  
 1207.3 FBC[B] STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS AND SLEEPING UNITS OR
 BETWEEN A DWELLING UNIT OR SLEEPING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS RATING OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, WHEN TESTED IN
 ACCORDANCE WITH ASTM E492.
  
 603.1 FBC[B] ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
  
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 804.1 FBC[B] GENERAL. INTERIOR FLOOR FINISH AND FLOOR
 COVERING MATERIALS SHALL COMPLY WITH SECTIONS 804.2
 THROUGH 804.4.2. EXCEPTION: FLOOR FINISHES AND
 COVERINGS OF A TRADITIONAL TYPE, SUCH AS WOOD, VINYL,
 LINOLEUM OR TERRAZZO, AND RESILIENT FLOOR COVERING
 MATERIALS THAT ARE NOT COMPRISED OF FIBERS.
  
 NOTES:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-05-31 Cont ID  
Sent By mpeterso Date 2022-05-31 Time 16:18 Rev Time 0.00
Received By mpeterso Date 2022-05-31 Time 16:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-04-27 Cont ID  
Sent By mpeterso Date 2022-04-27 Time 14:28 Rev Time 0.00
Received By mpeterso Date 2022-04-27 Time 14:28 Sent To  
Notes
2022-04-27 14:29:17ELECTRIC REVIEW FAILED
 1) PREVIOUS COMMENTS NOT ADDRESSED

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-03-17 Cont ID  
Sent By mpeterso Date 2022-03-17 Time 09:30 Rev Time 0.00
Received By mpeterso Date 2022-03-17 Time 09:30 Sent To  
Notes
2022-03-17 09:33:53ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL ON DRAWING COMPLIANCE WITH THE
 FOLLOWING NEC REQUIREMENTS:
 A) NEC 210.8 GFCI PROTECTION
 B) NEC 210.12 AND NEC 406.4 ARC-FAULT PROTECTION
 C) NEC 220.52 RECEPTACLE SPACING
 D) NEC 406.12 AND NEC 406.4(D)(5) TAMPER RESISTANT
 RECEPTACLES
 E) NEC 250.140 RANGE GROUNDING
 F) SMOKE/CARBON ALARMS AS PER FBC 553.883
 G) PLEASE PROVIDE SPECIFICATIONS OF NEW LIGHTS. THEY
 ARE STATED AS LOW VOLTAGE. WILL THIS BE LOW VOLTAGE
 WIRING? WHERE WILL THE LED DRIVER BE LOCATED? IF LOW
 VOLTAGE WIRING, PLEASE DETAIL WIRE TYPE AND INDICATE
 WHETHER CEILING IS A PLENUM
 2) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
 3) PLEASE HAVE THE CONTRACTOR OR QUALIFIER WHO PREPARED
 THE DRAWING PROVIDE HIS/HER SIGNATURE ON IT- SECTION
 107.2.1 WPB, AND FLORIDA STATUTES 471.003(2)(H) &
 471.025.
  
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-02-25 Cont ID  
Sent By mpeterso Date 2022-02-25 Time 11:31 Rev Time 0.00
Received By mpeterso Date 2022-02-25 Time 11:31 Sent To  
Notes
2022-02-25 11:36:08ELECTRIC PLAN REVIEW FAILED
 1) PLEASE PROVIDE AN APPLICABLE DRAWING OF ALL ELECTRIC
 WORK TO BE DONE. DETAIL ANY EXISTING WIRING THAT IS TO
 BE MODIFIED OR ADDITIONAL WIRING AND PROPOSED NEW
 LOCATIONS. INCLUDE PANEL SCHEDULES, OVERCURRENT
 PROTECTION AS REQUIRED. FBC 107.2

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-02-16 Cont ID  
Sent By clfranci Date 2022-02-16 Time   Rev Time 0.00
Received By clfranci Date 2022-02-16 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By clfranci Date 2022-01-14 Time   Rev Time 0.00
Received By clfranci Date 2022-01-14 Time   Sent To  
Notes
2022-01-14 07:53:19THIS PLAN WAS REVIEWED AND FAILED BY CAITLIN L.
 FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING
 COMMENTS:
  
 1) THE APPLICATION INDICATES THERE WILL BE THE
 REPLACEMENT OF FLOORING AND CABINETS BUT NO DOCUMENTS
 IDENTIFIYING WHAT MATERIALS ARE BEING USED.
  
 2) WITH THE DOCUMENTS IDENTIFYING MATERIALS BEING USED,
 PLEASE PROVIDE THE PRODUCT SPECS FOR ALL MATERIALS
 (FLOORING, UNDERLAYMENT, CABINETS)
  
 PER NFPA 101 CHAPTER 10, 10.2.7.2
  
 SHALL MEET THE MINIMUM CRITICAL RADIENT FLUX.
  
 CAITLIN L. FRANCIS
 FIRE INVESTIGATOR
 561-804-4728
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-06-07 Cont ID  
Sent By shill Date 2022-06-07 Time 11:52 Rev Time 0.00
Received By shill Date 2022-05-11 Time 08:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-04-27 Cont ID  
Sent By mpeterso Date 2022-04-27 Time 14:29 Rev Time 0.00
Received By mpeterso Date 2022-04-19 Time 06:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-31 Cont ID  
Sent By dbattles Date 2022-03-31 Time 13:21 Rev Time 0.00
Received By dbattles Date 2022-03-02 Time 09:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-25 Cont ID  
Sent By mpeterso Date 2022-02-25 Time 11:36 Rev Time 0.00
Received By mpeterso Date 2022-02-15 Time 07:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-31 Cont ID  
Sent By dbattles Date 2022-01-31 Time 11:32 Rev Time 0.00
Received By dbattles Date 2022-01-12 Time 07:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2022-03-09 Cont ID  
Sent By medwards Date 2022-03-09 Time 15:56 Rev Time 0.00
Received By medwards Date 2022-03-09 Time 15:56 Sent To  
Notes
2022-03-09 15:57:04NO MECHANICAL WORK IN THE SCOPE OF WORK FOR THIS
 PROJECT. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-02-24 Cont ID  
Sent By medwards Date 2022-02-24 Time 14:42 Rev Time 0.00
Received By medwards Date 2022-02-24 Time 14:42 Sent To  
Notes
2022-02-24 14:43:32PLEASE PROVIDE A SCOPE OF WORK AND A MECHANICAL DRAWING
 FOR ALL MECHANICAL WORK BEING COMPLETED UNDER THIS
 PERMIT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2022-02-14 17:36:48PLAN SHOWS HOOD
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-02-16 Cont ID  
Sent By lcrespo Date 2022-02-16 Time 07:33 Rev Time 0.00
Received By lcrespo Date 2022-02-16 Time 07:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2022-06-07 Cont ID  
Sent By shill Date 2022-06-07 Time 11:52 Rev Time 0.00
Received By shill Date 2022-06-07 Time 11:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-25 Cont ID  
Sent By dbattles Date 2022-02-25 Time 10:29 Rev Time 0.00
Received By dbattles Date 2022-02-25 Time 09:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-31 Cont ID  
Sent By dbattles Date 2022-01-31 Time 11:31 Rev Time 0.00
Received By dbattles Date 2022-01-31 Time 11:31 Sent To  
Notes
2022-01-31 11:32:15PLEASE PUT THE NAME OF THE PERSON PERPARING DRAWINGS
 AND THE DATE.
  
 W.P.B. PERMIT: 21120322
 REVIEWED: JANUARY 31, 2022
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  