| 2022-05-26 15:34:39 | INSUFFICIENT |
| | |
| | 1) AFTER REVIEW, THE CITY'S TRAFFIC ENGINEER AND |
| | PLANNING DIVISION DO NOT SUPPORT THE PROPOSED LOCATION |
| | OF THE POLE IN THE LANDSCAPE BULB OUT WITHIN THE |
| | TAMARIND AVENUE RIGHT-OF-WAY. |
| | |
| | A. THE PROPOSED LOCATION IS LOCATED DIRECTLY IN FRONT |
| | OF AN EXISTING RESIDENTIAL STRUCTURE ON THE EAST SIDE |
| | OF TAMARIND AVENUE. STAFF HAS REVIEWED THE AREA AND |
| | THERE DOES NOT APPEAR TO BE AN OPPORTUNITY TO SLIDE THE |
| | POLE NORTH OR SOUTH WITHIN THE TAMARIND AVENUE |
| | RIGHT-OF-WAY NORTH OF 21ST STREET AND BOTH MOVE FROM IN |
| | FRONT OF THE RESIDENTIAL STRUCTURE AND AVOID BEING A |
| | TRAFFIC HAZARD. |
| | B. STAFF SUGGESTS MOVING THE POLE BETWEEN THE SIDEWALK |
| | AND THE CURB ON 21ST STREET, WEST OF TAMARIND AVENUE. |
| | STAFF HAS SENT CHRISTIAN WARR A ROUGH MARK UP. |
| | |
| | 2) WHILE STAFF DOES NOT SUPPORT THE PROPOSED POLE |
| | LOCATION, COMMENTS RELATED TO THE PROPOSED INSTALLATION |
| | ARE INCLUDED BELOW AND WILL NEED TO BE TAKEN INTO |
| | ACCOUNT NO MATTER WHERE THE NEW POLE AND UNDERGROUND |
| | ELECTRIC ARE PLACED. |
| | |
| | A. THE PROPOSED BORE PIT FOR THE UNDERGROUND ELECTRIC |
| | AT THE POLE IS IN DIRECT CONFLICT WITH AN EXISTING PALM |
| | TREE IN THE BULB OUT. |
| | B. THE POLE AND THE BORE PIT DIRECTLY IMPACT AN |
| | EXISTING GAS LINE. IN ORDER TO VERIFY THAT THE |
| | INSTALLATION WILL NOT INTERFERE WITH THE EXISTING |
| | FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO |
| | OBJECTION FROM FPU. |
| | C. THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE |
| | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, LANDSCAPE |
| | AND SIDEWALK WILL NEED RESTORATION. PLEASE UPDATE THE |
| | NOTATIONS ACCORDINGLY. |
| | D. SHEET P-1 SHOWS THE EXCAVATION BOX FOR THE HANDHOLE |
| | EXTENDING PAST THE EDGE OF THE SIDEWALK, WHICH PUTS IT |
| | ON TO PRIVATE PROPERTY, WHICH IS NOT PERMITTED. ALL |
| | WORK MUST BE ONLY IN THE RIGHT-OF-WAY. |
| | E. PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC |
| | WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH |
| | EXISTING UTILITIES AND PALM TREE ROOT ZONES. |
| | |
| | 3) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP |
| | 7042 TRAFFIC GREY A. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |
| | |
| | |