Plan Review Details - Permit 21120159
Plan Review Stops For Permit 21120159
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-01-04 Cont ID  
Sent By jbrooks Date 2022-01-04 Time 14:11 Rev Time 0.00
Received By jbrooks Date 2022-01-04 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-29 Cont ID  
Sent By jbrooks Date 2021-12-29 Time 11:14 Rev Time 0.00
Received By jbrooks Date 2021-12-28 Time 08:17 Sent To  
Notes
2021-12-29 11:15:06JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL2533-R26 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO
 INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN
 BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE
 BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5 ONLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-14 Cont ID  
Sent By jbrooks Date 2021-12-14 Time 10:16 Rev Time 0.00
Received By jbrooks Date 2021-12-14 Time 07:58 Sent To  
Notes
2021-12-14 10:16:49JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL1654-R28 SELECTED SYSTEM NO. W-1 DO NOT MEET
 THE EXPOSURE CATEGORY C; ZONE 2 MINIMUM DESIGN PRESSURE
 REQUIREMENT OF -79.38 OR ZONE 3 MINIMUM DESIGN PRESSURE
 REQUIREMENT OF -108.17. PLEASE SELECT SYSTEM NO. THAT
 MEETS OR EXCEEDS REQUIREMENTS OR PROVIDE SIGNED AND
 SEALED ENGINEERED NAILING CALCULATION FOR ZONES 2 & 3
 AS PER LIMITATIONS: 5.7.2. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-04 Cont ID  
Sent By jbrooks Date 2022-01-04 Time 14:12 Rev Time 0.00
Received By jbrooks Date 2022-01-03 Time 14:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-29 Cont ID  
Sent By jbrooks Date 2021-12-29 Time 11:15 Rev Time 0.00
Received By jbrooks Date 2021-12-21 Time 10:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-14 Cont ID  
Sent By jbrooks Date 2021-12-14 Time 10:16 Rev Time 0.00
Received By jbrooks Date 2021-12-07 Time 07:18 Sent To  
Notes
***NONE***