Plan Review Details - Permit 21120144
Plan Review Stops For Permit 21120144
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2022-02-15 Cont ID  
Sent By rmcphers Date 2022-02-15 Time 15:03 Rev Time 0.00
Received By rmcphers Date 2022-02-15 Time 15:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-21 Cont ID  
Sent By rmcphers Date 2022-01-21 Time 15:03 Rev Time 0.00
Received By rmcphers Date 2022-01-21 Time 15:03 Sent To  
Notes
2022-01-21 15:10:00ROOF TO AC
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING M-02 SAYS "SEE STRUCTURAL DRAWINGS" FOR THE
 ADDITIONAL JOIST REINFORCING - PLEASE PROVIDE THE
 STRUCTURAL DRAWINGS FBC WPB 107.2.1 AND FBC 707.2
 ADDITION OR REPLACEMENT OF ROOFING OR REPLACEMENT OF
 EQUIPMENT. WHERE ADDITION OR REPLACEMENT OF ROOFING OR
 REPLACEMENT OF EQUIPMENT RESULTS IN ADDITIONAL DEAD
 LOADS, STRUCTURAL COMPONENTS SUPPORTING SUCH REROOFING
 OR EQUIPMENT SHALL COMPLY WITH THE GRAVITY LOAD
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-16 Cont ID  
Sent By medwards Date 2022-02-16 Time 07:25 Rev Time 0.00
Received By medwards Date 2022-02-11 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-21 Cont ID  
Sent By rmcphers Date 2022-01-21 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2022-01-04 Time 07:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-02-16 Cont ID  
Sent By medwards Date 2022-02-16 Time 07:21 Rev Time 0.00
Received By medwards Date 2022-02-16 Time 07:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-05 Cont ID  
Sent By medwards Date 2022-01-05 Time 11:41 Rev Time 0.00
Received By medwards Date 2022-01-05 Time 10:41 Sent To  
Notes
2022-01-05 11:41:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120144
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-02 INDICATES A WIND LOAD OF 132 MPH FOR THE
 PACKAGE UNIT ADDED ON THE ROOF, PLEASE PROVIDE THE
 CORRECT WIND LOAD DESIGN FOR THIS BUILDING.
  
 2) PLEASE SHOW THE FALL PROTECTION REQUIRED FOR THIS
 NEW RTU LOCATION. FBC M 304.11
  
 3) PLEASE SHOW THE ACCESS TO THIS NEW RTU INCLUDING THE
 HEIGHT FROM THE GROUND. FBC M 306.5
  
 4) PLEASE SHOW THE CONDENSATE PIPE SIZE, MATERIAL AND
 TERMINATION LOCATION. FBC M 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-16 Cont ID  
Sent By medwards Date 2022-02-16 Time 07:25 Rev Time 0.00
Received By medwards Date 2022-02-16 Time 07:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-05 Cont ID  
Sent By medwards Date 2022-01-05 Time 11:51 Rev Time 0.00
Received By medwards Date 2022-01-05 Time 11:51 Sent To  
Notes
***NONE***