Plan Review Details - Permit 21120121
Plan Review Stops For Permit 21120121
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-03 Cont ID  
Sent By pvalenti Date 2022-03-03 Time 13:30 Rev Time 0.00
Received By pvalenti Date 2022-03-03 Time 10:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By pvalenti Date 2022-01-27 Time 15:31 Rev Time 0.00
Received By pvalenti Date 2022-01-27 Time 15:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By pvalenti Date 2021-12-27 Time 07:10 Rev Time 0.00
Received By pvalenti Date 2021-12-23 Time 16:28 Sent To  
Notes
2021-12-27 07:15:44PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE MORE INFORMATION
 (SIGNED/SEALED WINDLOAD SHEETS INCLUDING CALCULATIONS
 FOR THE CURVATURE OF THE BUILDING). THIS INFORMATION IS
 IMPORTANT IN DETERMINING THAT THE WIND LOAD PRESSURE
 CAPACITY OF THE WINDOW/DOORS IS ACCEPTABLE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-03 Cont ID  
Sent By pvalenti Date 2022-03-03 Time 13:30 Rev Time 0.00
Received By pvalenti Date 2022-02-09 Time 06:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-27 Cont ID  
Sent By pvalenti Date 2022-01-27 Time 15:35 Rev Time 0.00
Received By pvalenti Date 2022-01-12 Time 17:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By pvalenti Date 2021-12-27 Time 07:15 Rev Time 0.00
Received By pvalenti Date 2021-12-07 Time 06:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-03 Cont ID  
Sent By pvalenti Date 2022-03-03 Time 13:30 Rev Time 0.00
Received By pvalenti Date 2022-03-03 Time 10:37 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-27 Cont ID  
Sent By pvalenti Date 2022-01-27 Time 15:32 Rev Time 0.00
Received By pvalenti Date 2022-01-27 Time 15:01 Sent To  
Notes
2022-01-27 15:35:25PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE 3RD PARTY APPROVED
 DIGITAL SIGNATURES ON THE WINDLOAD CHART AS PER
 COMMENTS BELOW:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-23 Cont ID  
Sent By pvalenti Date 2021-12-23 Time 16:44 Rev Time 0.00
Received By pvalenti Date 2021-12-23 Time 16:28 Sent To  
Notes
2021-12-23 16:59:38PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE PROVIDE MORE INFORMATION
 (SIGNED/SEALED WINDLOAD SHEETS INCLUDING CALCULATIONS
 FOR THE CURVATURE OF THE BUILDING).
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  
  