Plan Review Details - Permit 21120095
Plan Review Stops For Permit 21120095
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By rmcphers Date 2022-05-18 Time 10:54 Rev Time 0.00
Received By rmcphers Date 2022-05-18 Time 10:54 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By rmcphers Date 2022-04-27 Time 16:45 Rev Time 0.00
Received By rmcphers Date 2022-04-27 Time 16:45 Sent To  
Notes
2022-04-27 16:45:57PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By rmcphers Date 2022-05-18 Time 10:54 Rev Time 0.00
Received By rmcphers Date 2022-05-18 Time 10:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By rmcphers Date 2022-04-27 Time 16:46 Rev Time 0.00
Received By rmcphers Date 2022-04-27 Time 16:46 Sent To  
Notes
2022-04-27 16:53:45CHANGE BATH TO SHOWER -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE CIRCLE ON THE FLOOR PLAN WHICH TUB IS BEING
 CONVERTED TO A SHOWER
  
 2) PLEASE SHOW THE GRAB BAR BACKING DETAILS FOR THE
 SHOWER TO COMPLY WITH FBC FHA
  
 REQUIREMENT 6 -REINFORCED WALLS FOR GRAB BARS.
 SECTION 100.205(C)(3)(III)REQUIRES THAT COVERED
 MULTIFAMILY DWELLINGS WITH A BUILDING ENTRANCE ON AN
 ACCESSIBLE ROUTE SHALL BE DESIGNED AND CONSTRUCTED IN
 SUCH A MANNER THAT ALL PREMISES WITHIN COVERED
 MULTIFAMILY DWELLING UNITS CONTAIN REINFORCEMENTS IN
 BATHROOM WALLS TO ALLOW LATER INSTALLATION OF GRAB BARS
 AROUND TOILET, TUB, SHOWER STALL AND SHOWER SEAT, WHERE
 SUCH FACILITIES ARE PROVIDED.
  
 GUIDELINE
  
 REINFORCED BATHROOM WALLS TO ALLOW LATER INSTALLATION
 OF GRAB BARS AROUND THE TOILET, TUB, SHOWER STALL AND
 SHOWER SEAT, WHERE SUCH FACILITIES ARE PROVIDED, WOULD
 MEET SECTION 100.205(C)(3)(III) IF REINFORCED AREAS ARE
 PROVIDED AT LEAST AT THOSE POINTS WHERE GRAB BARS WILL
 BE MOUNTED. (FOR EXAMPLE, SEE FIG. 3, 4 AND 5.)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-13 Cont ID  
Sent By pleduc Date 2022-05-13 Time   Rev Time 0.00
Received By pleduc Date 2022-05-13 Time 12:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-03-22 Cont ID  
Sent By pleduc Date 2022-03-22 Time   Rev Time 0.00
Received By pleduc Date 2022-03-22 Time 13:57 Sent To  
Notes
2022-03-22 14:08:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION ON THE APPLICATION OF
 BATHROOM REMODEL, CHANGE TUB TO SHOWER.
  
 THERE IS ALSO A FLOOR PLAN SUBMITTED BUT IT DOES NOT
 INDICATE WHICH BATHROOM, OR BOTH, IS TO BE CHANGED.
  
 PER NFPA 1
  
 1.7.11 PLANS AND SPECIFICATIONS.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION,
 MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS
 AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND
 APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN
 SECTION 1.14.
  
  
 FOR THE OFFICIAL RECORD, PLEASE INDICATE WHICH BATHROOM
 OR BOTH IS TO BE BE CHANGED ON THE FLOOR PLAN.
  
  
 1A) THE FLOOR PLAN INDICATES THAT EACH BATHROOM WALL
 NEXT TO THE TUBS MAY BE FIRE RATED TENANT/CORRIDOR
 WALLS.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS, IF DAMAGED,
 ARE REPAIRED TO THE EXISTING FIRE RATED SEPARATION.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By rwbrown Date 2022-05-18 Time 14:41 Rev Time 0.00
Received By rwbrown Date 2022-05-12 Time 13:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-28 Cont ID  
Sent By rwbrown Date 2022-04-28 Time 05:30 Rev Time 0.00
Received By rwbrown Date 2022-03-21 Time 11:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-05-18 Cont ID  
Sent By rwbrown Date 2022-05-18 Time 14:41 Rev Time 0.00
Received By rwbrown Date 2022-05-18 Time 14:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-28 Cont ID  
Sent By rwbrown Date 2022-03-31 Time 16:18 Rev Time 0.00
Received By rwbrown Date 2022-03-31 Time 16:18 Sent To  
Notes
2022-03-31 16:22:001ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. - DESCRIPTION ON THE APPLICATION INDICATES A
 TUB TO SHOWER CONVERSION. PLEASE INDICATE THE EXISTING
 AND PROPOSED FLOOR PLANS SHOWING WHICH IS TO BE
 CHANGED. THIS SHOULD INCLUDE DIMINSION DRAWINGS
 INCLUDING THE SIZE OF THE SHOWER, PAN DETAILS, VALVE
 DETAILS, SHOWER DOOR, ETC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-05-18 Cont ID  
Sent By rmcphers Date 2022-05-18 Time 10:54 Rev Time 0.00
Received By rmcphers Date 2022-05-18 Time 10:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-04-27 Cont ID  
Sent By rmcphers Date 2022-04-27 Time 16:55 Rev Time 0.00
Received By rmcphers Date 2022-04-27 Time 16:55 Sent To  
Notes
***NONE***