| Plan Review Stops For Permit 21120094 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
P |
Date |
2022-01-10 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-01-10 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-01-10 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2022-01-10 11:51:20 | THIS PERMIT IS FOR THE WORK DONE AT 411 CLAREMORE DR | | | WITH THE PCN 74434328060200120. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2021-12-30 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-12-30 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-30 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2021-12-30 14:07:32 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-12-23 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-12-23 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-23 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2021-12-23 11:32:58 | THE AREA OF WORK TO BE DONE ENCOMPASSES THE FOLLOWING | | | PARCELS; 74434328060200012, 74434328060200011, | | | 74434328060200040 AND 74434328060200050. EITHER A | | | REPLAT OR A UNIT OF TITLE NEEDS TO BE APPLIED FOR. YOU | | | WILL NEED TO CONTACT VINCE NOEL [email protected] OR CALL | | | 561-494-1040 TO START THE UNITY OF TITLE PROCEDURE, A | | | SINGLE PCN MUST BE ISSUED BY THE COUNTY. WHEN YOU | | | CONTACT THE PROPERTY APPRAISERS YOU NEED TO REQUEST | | | PRELIMINARY LETTER OF THE UNIFIED PCN. ONCE YOU HAVE | | | RECEIVED THE PRELIMINARY LETTER PLEASE CONTACT | | | [email protected] OR CALL 561-805-6659 TO BE ISSUED AN | | | ADDRESS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-17 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-17 |
Time |
09:05 |
Sent To |
|
|
| Notes |
| 2022-03-17 09:06:45 | ELECTRIC APPROVED FOR METER, PANEL AND (1) RECPTACLE | | | ONLY.3/17/22 M.P. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2022-02-25 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-25 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-25 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2022-02-25 13:52:50 | ELECTRIC REVIEW FAILED | | | 1) DRAWING SUBMITTED DOES NOT DEPICT WORK AS OUTLINED | | | ON APPLICATION. FBC 107.2 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-04 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-04 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2022-01-04 12:20:29 | 3RD ELECTRIC REVIEW FAILED | | | 1) PREVIOUS COMMENTS STILL NOT ADDRESSED | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2021-12-21 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-21 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-21 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2021-12-21 14:25:14 | FAILED SECOND ELECTRIC REVIEW | | | | | | 1) PROVIDE CLARITY IN DOCUMENTS SUBMITTED. INCLUDE | | | EQUIPMENT, CONDUCTORS WIRING METHODS, NOTING WHAT IS | | | NEW AND WHAT IS EXISTING FROM POINT OF ORIGIN TO | | | UTILIZATION EQUIPMENT. DETAIL EXISTING LOADS AND LOAD | | | CALCULATIONS FOR ALL EQUIPMENT WHETHER EXISTING OR NEW. | | | THE WORK SCOPE FOR THE PROJECT STATES" INSTALL SERVICE | | | WIRES FROM METER CAN TO NEW 200 AMP PANEL AND INSTALL | | | GFI RECEPTACLE FOR TEMPORARY POWER" IF THIS IS | | | INACCURATE THEN PLEASE SUBMIT A CORRECT WORK SCOPE. FBC | | | 107.2 | | | | | | 2) VALUE IS STATED AT $650. PLEASE PROVIDE AN ACCURATE | | | VALUATION FOR PROJECTS SUBMITTED AS PER THE W.P.B. | | | AMENDMENT 109.3 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-12-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-14 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-14 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2021-12-14 10:52:50 | FAILED ELECTRIC REVIEW | | | PLANS SUBMITTED ARE CONFLICTING, PLEASE SUBMIT CLEAR | | | PLANS THAT SHOW EXACT WORK TO BE DONE. SHOW NEW | | | EQUIPMENT, CONDUITS, CONDUCTORS AND OTHER NESSECARY | | | INFORMATION, WITH LOCATIONS WHERE THEY WILL BE | | | INSTALLED. A WRITTEN WORK SCOPE IS HELPFUL. IF | | | EQUIPMENT IS EXISTING AND INCORPORATED INTO WORK, SHOW | | | WHAT THE PREVIOUS USE OF THIS EQUIPMENT WAS FOR. | | | F.B.C.. 107.2 | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-17 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-28 |
Time |
12:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-02-25 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-25 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-06 |
Time |
08:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-04 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-01-04 |
Time |
12:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-12-21 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-21 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-21 |
Time |
14:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-12-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-14 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-14 |
Time |
10:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
N |
Date |
2022-03-17 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-17 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-17 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2022-03-17 09:13:07 | CONTRACTOR DRAWINGS NOT REQUIRED |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2022-02-25 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-02-25 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-25 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2022-02-25 13:55:53 | 4TH SIGNATURE REVIEW FAILED | | | 1) PREVIOUS COMMENTS ATILL REMAIN UNADDRESSED | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-01-04 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-01-04 |
Time |
12:21 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-04 12:23:03 | SIGNATURE REVIEW FAILED | | | ENGINEERS TITLE BLOCK STILL EXISTS WITH NO SEAL OR | | | SIGNATURE AS REQUIRED. | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-12-21 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-21 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-21 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2021-12-21 14:27:53 | SECOND SIGNATURE REVIEW FAILED, NO CHANGE HAS OCCURED | | | WITH SUBMITTED DOCUMENTS | | | | | | TITLE BLOCK FOR MAINSTREET ENGINEERING APPEARS ON | | | DRAWING. DRAWING HAS NO SEAL AND SIGNATURE FROM THE | | | ENGINEER OF RECORD. | | | . PLEASE CORRECT THESE ISSUES BY PROPERLY SIGNING AND | | | SEALING THEM AS DESCRIBED BELOW. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-12-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-12-14 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-12-14 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2021-12-14 10:57:22 | TITLE BLOCK FOR MAINSTREET ENGINEERING APPEARS ON | | | DRAWING. DRAWING HAS NO SEAL AND SIGNATURE FROM THE | | | ENGINEER OF RECORD. | | | . PLEASE CORRECT THESE ISSUES BY PROPERLY SIGNING AND | | | SEALING THEM AS DESCRIBED BELOW. | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|