Plan Review Details - Permit 21120080
Plan Review Stops For Permit 21120080
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-24 Cont ID  
Sent By medwards Date 2022-06-24 Time 07:23 Rev Time 0.00
Received By medwards Date 2022-06-23 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 18:07 Rev Time 0.00
Received By medwards Date 2022-04-21 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-27 Cont ID  
Sent By medwards Date 2022-01-27 Time 10:28 Rev Time 0.00
Received By medwards Date 2022-01-26 Time 08:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-19 Cont ID  
Sent By medwards Date 2022-01-19 Time 15:22 Rev Time 0.00
Received By medwards Date 2022-01-18 Time 11:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-06-24 Cont ID  
Sent By medwards Date 2022-06-24 Time 07:23 Rev Time 0.00
Received By medwards Date 2022-06-24 Time 07:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 18:03 Rev Time 0.00
Received By medwards Date 2022-04-26 Time 18:03 Sent To  
Notes
2022-04-26 18:05:57PLEASE UNDERSTAND UNTIL THE ENGINEER PROVIDES ME THE
 INFORMATION REQUESTED IN PREVIOUS REVIEWS I CANNOT
 APPROVE THIS DESIGN, IT IS NOT A COMPLETE DESIGN
 WITHOUT THIS INFORMATION. IS THERE A REFRIGERATION
 MECHANICAL ROOM? IF SO PLEASE SHOW ON THE DRAWINGS.
  
 I AM STILL MISSING THE ENGINEERS LETTER AND
 CALCULATIONS SHOWING THE INFORMATION LISTED BELOW FROM
 THE 1ST CYCLE REVIEW.
  
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120080
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THIS
 REFRIGERATION SYSTEM.
  
 FBC M : SECTION 1102
 SYSTEM REQUIREMENTS
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
  
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
  
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
  
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
  
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
  
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
  
 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-01-27 Cont ID  
Sent By medwards Date 2022-01-27 Time 10:23 Rev Time 0.00
Received By medwards Date 2022-01-27 Time 10:23 Sent To  
Notes
2022-01-27 10:24:50I AM STILL MISSING THE ENGINEERS LETTER AND
 CALCULATIONS SHOWING THE INFORMATION LISTED BELOW FROM
 THE 1ST CYCLE REVIEW.
  
 1ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120080
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THIS
 REFRIGERATION SYSTEM.
  
 FBC M : SECTION 1102
 SYSTEM REQUIREMENTS
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
  
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
  
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
  
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
  
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
  
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
  
 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-01-19 Cont ID  
Sent By medwards Date 2022-01-19 Time 15:13 Rev Time 0.00
Received By medwards Date 2022-01-19 Time 13:37 Sent To  
Notes
2022-01-19 15:13:551ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21120080
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THIS
 REFRIGERATION SYSTEM.
  
 FBC M : SECTION 1102
 SYSTEM REQUIREMENTS
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
  
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
  
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
  
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
  
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
  
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
  
 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-06-24 Cont ID  
Sent By medwards Date 2022-06-24 Time 07:23 Rev Time 0.00
Received By medwards Date 2022-06-24 Time 07:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 18:06 Rev Time 0.00
Received By medwards Date 2022-04-26 Time 18:06 Sent To  
Notes
2022-04-26 18:06:49PLEASE SEE PREVIOUS REVIEW COMMENT BELOW:
  
 THE ARCHITECT/ENGINEER/DESIGNER OF THE DRAWINGS MUST
 DIGITALLY SIGN THE DOCUMENTS. FS 4741/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-27 Cont ID  
Sent By medwards Date 2022-01-27 Time 10:25 Rev Time 0.00
Received By medwards Date 2022-01-27 Time 10:25 Sent To  
Notes
2022-01-27 10:27:30THE ARCHITECT/ENGINEER/DESIGNER OF THE DRAWINGS MUST
 DIGITALLY SIGN THE DOCUMENTS. FS 4741/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-19 Cont ID  
Sent By medwards Date 2022-01-19 Time 13:35 Rev Time 0.00
Received By medwards Date 2022-01-19 Time 13:35 Sent To  
Notes
2022-01-19 13:36:51ENGINEER OF THE SYSTEM MUST DIGITALLY SIGN THE
 DRAWINGS. THE ENGINEERS DIGITAL SIGNATURE MUT BE 3RD
 PARTY VERIFIED. FS 471,481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  