| Plan Review Stops For Permit 21120080 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-06-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-24 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-23 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-26 |
Time |
18:07 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-21 |
Time |
15:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-27 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-26 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-19 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-18 |
Time |
11:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2022-06-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-24 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-24 |
Time |
07:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-26 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-26 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2022-04-26 18:05:57 | PLEASE UNDERSTAND UNTIL THE ENGINEER PROVIDES ME THE | | | INFORMATION REQUESTED IN PREVIOUS REVIEWS I CANNOT | | | APPROVE THIS DESIGN, IT IS NOT A COMPLETE DESIGN | | | WITHOUT THIS INFORMATION. IS THERE A REFRIGERATION | | | MECHANICAL ROOM? IF SO PLEASE SHOW ON THE DRAWINGS. | | | | | | I AM STILL MISSING THE ENGINEERS LETTER AND | | | CALCULATIONS SHOWING THE INFORMATION LISTED BELOW FROM | | | THE 1ST CYCLE REVIEW. | | | | | | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21120080 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THIS | | | REFRIGERATION SYSTEM. | | | | | | FBC M : SECTION 1102 | | | SYSTEM REQUIREMENTS | | | 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE | | | REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, | | | LOCATION LIMITATIONS, AND FIELD PRESSURE TEST | | | REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS: | | | | | | 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION, | | | IN ACCORDANCE WITH SECTION 1103.3. | | | | | | 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN | | | ACCORDANCE WITH SECTION 1103.1. | | | | | | 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF | | | REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON | | | TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND | | | OCCUPANCY. | | | | | | 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN | | | ACCORDANCE WITH SECTION 1104. | | | | | | 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND | | | INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF | | | CHAPTER 3. | | | | | | 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND | | | APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH | | | SECTION 1108. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-27 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-27 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2022-01-27 10:24:50 | I AM STILL MISSING THE ENGINEERS LETTER AND | | | CALCULATIONS SHOWING THE INFORMATION LISTED BELOW FROM | | | THE 1ST CYCLE REVIEW. | | | | | | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21120080 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THIS | | | REFRIGERATION SYSTEM. | | | | | | FBC M : SECTION 1102 | | | SYSTEM REQUIREMENTS | | | 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE | | | REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, | | | LOCATION LIMITATIONS, AND FIELD PRESSURE TEST | | | REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS: | | | | | | 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION, | | | IN ACCORDANCE WITH SECTION 1103.3. | | | | | | 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN | | | ACCORDANCE WITH SECTION 1103.1. | | | | | | 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF | | | REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON | | | TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND | | | OCCUPANCY. | | | | | | 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN | | | ACCORDANCE WITH SECTION 1104. | | | | | | 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND | | | INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF | | | CHAPTER 3. | | | | | | 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND | | | APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH | | | SECTION 1108. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-01-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-19 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-19 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2022-01-19 15:13:55 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21120080 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THIS | | | REFRIGERATION SYSTEM. | | | | | | FBC M : SECTION 1102 | | | SYSTEM REQUIREMENTS | | | 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE | | | REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, | | | LOCATION LIMITATIONS, AND FIELD PRESSURE TEST | | | REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS: | | | | | | 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION, | | | IN ACCORDANCE WITH SECTION 1103.3. | | | | | | 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN | | | ACCORDANCE WITH SECTION 1103.1. | | | | | | 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF | | | REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON | | | TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND | | | OCCUPANCY. | | | | | | 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN | | | ACCORDANCE WITH SECTION 1104. | | | | | | 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND | | | INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF | | | CHAPTER 3. | | | | | | 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND | | | APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH | | | SECTION 1108. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-06-24 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-24 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-24 |
Time |
07:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-04-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-04-26 |
Time |
18:06 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-04-26 |
Time |
18:06 |
Sent To |
|
|
| Notes |
| 2022-04-26 18:06:49 | PLEASE SEE PREVIOUS REVIEW COMMENT BELOW: | | | | | | THE ARCHITECT/ENGINEER/DESIGNER OF THE DRAWINGS MUST | | | DIGITALLY SIGN THE DOCUMENTS. FS 4741/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-27 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-27 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2022-01-27 10:27:30 | THE ARCHITECT/ENGINEER/DESIGNER OF THE DRAWINGS MUST | | | DIGITALLY SIGN THE DOCUMENTS. FS 4741/481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-01-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-19 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-19 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2022-01-19 13:36:51 | ENGINEER OF THE SYSTEM MUST DIGITALLY SIGN THE | | | DRAWINGS. THE ENGINEERS DIGITAL SIGNATURE MUT BE 3RD | | | PARTY VERIFIED. FS 471,481 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|